RS PRO 264-1025 BACnet Module for Power Quality Analyser Owner’s Manual

Features

  • Extends the capability of the 264-1020 Multifunction Network Analysers
  • Automatically recognised by 264-1020
  • Baud rate: 1200/2400/4800/9600/ 19200 bps
  • Real-time data measurement from RIF550

RS Professionally Approved Products bring to you professional quality parts across all product categories. Our product range has been tested by engineers and provides a comparable quality to the leading brands without paying a premium price.

Product Description

The 264-1025 is a BACnet/MSTP communication module used to extend the bus communication function of the 264-1020 Network Analyser.

Baud rate: 1200/2400/4800/9600/19200 bps

Based on MSTP communication method

Relevant parameters can be configured through the host computer or 264-1020 Network Analyser.

Installation and Operation

Disconnect the power supply of Network Analyser and then connect the 264-1025 module to slot X2 (take X2 slot as an example)

Connect the Network Analyser to the power supply, and then enter the module interface of the Analyser to check the information of slot X2.

If the connection between the meter and the module is correct, the parameters of 264-1025 module will be shown.

In the BACnet/MSTP network, users can read the real-time measurement data of 264-1020 Network analyser (with 264-1025 module) through standard protocol, or realize remote parameter configuration through fixed instructions.

Configuration

In the BACnet/MSTP network, users can read the real-time measurement data of Network Analyser (with 264-1025 module) through standard protocol, or realize remote parameter configuration through fixed instructions.

Configuring the 264-1025 module through the 264-1020 Analyser

Configuring the 264-1025 module via computer with RI-FXX Viewer software.

After opening the 264-1020 Network Analyser host computer:

  1. Change the slave address (this address is the Modbus address of the 264-1020 Network Analyser)
  2. Open serial port settings from setup options
  3. Modify port number, baud rate, data format, etc.
  4. Click ‘Accept’ to save the communication settings.

BACnet Protocol Implementation

Supporting private propertiesWntabIe properties

Attribute Idenblter : 9600 Type of Data : Integer Meaning : Baud Rate0: 1200 bps1 : 2400 bps2: 4800 bps3: 9600 bps (default)4: 19200 bpsAttribute Identifier : 9601Type of Data : IntegerMeaning : MAC address (0…127)Object identifierMAXIMUM number of primary nodes 96009601

Writable properties

Analogue input object

Analogue output object

Analogue value object

Binary input object

Binary output object

Binary value object

Data link layer options

Object identifier

Maximum number of primary nodes 9600

9601

Supporting private properties : No Writable properties : No

Supporting private properties : No Writable properties : No

Supporting private properties : No Writable properties : The current value.

Supporting private properties : No Writable properties : No

Supporting private properties : No Writable properties : The current value.

Supporting private properties : No Writable properties : No

MS/TP Master (Chapter 9)

Baud rate: 1200, 2400. 4800, 9600. 19200 bps.

Note : The baud rates of 1200, 2400 and 4800 bps are not recommended because they are not standard baud rates in the protocol.

Technical Parameters

Communication Interface RS485
Baud rate 1200/2400/4800/9600/19200 bps
Operating type MACnet/MSTP Master
Communication protocol MACnet/MSTP

Environmental

Operating Temperature -25˚C…+75˚C
Storage Temperature -40˚C…+85˚C
Relative humidity 0…95%, non-condensing

Dimensions

All dimensions in millimeters

Safety Instruction
It is recommended to use this module as a reference to the following content: 264-1020 Network Analyser User Manual, BACnet Standard 135-2008. Please read this user manual carefully before using this module. This module must be installed and serviced only by professional personnel. Manufacturer shall not be held responsible for failure to comply with the instructions in this manual.