CARLO GAVAZZI DCT 1 A30 DC Transducer 150 to 1000 V Voltage Input Instruction Manual
CARLO GAVAZZI DCT 1 A30 DC Transducer 150 to 1000 V Voltage Input Instruction Manual

Warnings

Warning Icon DANGER! Live parts. Heart attack, burns and other injuries.

  • Disconnect the power supply and loads before connecting/disconnecting the electrical wires.
  • The transducer should only be installed by qualified personnel experienced in working in safety.
  • Access to the terminals is reserved for qualified personnel for maintenance operations.
  • The system installer is liable for the safety of any system that includes the transducer

NOTICE: only use the transducer at the specified voltage and current to avoid permanent damage.
NOTICE: no one is authorized to open the transducer. This operation is reserved exclusively for CARLO GAVAZZI technical service personnel. Protection may be impaired if the instrument is used in a manner not specified by the manufacturer
Note Icon This manual is an integral part of the product. It must be consulted for transducer installation. It must be kept in good condition and in a clean location accessible to all operators.
Cleaning
Disconnect the power supply and loads before cleaning. Use a slightly dampened cloth to clean the transducer. Do not use abrasives or solvents.
Responsibility for disposal
Disposal Icon The product must be disposed of at the relative recycling centers specified by the government or local public authorities. Correct disposal and recycling will contribute to the prevention of potentially harmful consequences to the environment and persons.
Service and warranty
In the event of malfunction, fault, requests for information or to purchase accessory modules, contact the CARLO GAVAZZI branch or distributor in your country. Installation and use of transducers other than those indicated in the provided instructions void the warranty.

Double insulation symbol Double insulation

Operating temperature From -25 to +70 °C/from -13 to +158 °F
Storage temperature From -40 to +85 °C/from -40 to +185 °F
Max temperature on the shunt 120 °C / 248 °F
Protection degree IP20
Protective class II
Overvoltage II, 6kV rated impulse voltage
Altitude Max 2000 m/6562 f
Power supply range 12 -24 V dc ±20%
Power supply consumption <0.9 W
Weight 270 g/ 0.60 lb

Note: R.H. < 90 % non-condensing @ 40 °C / 104 °F.

UL Notes:
All the devices shall be installed in a pollution degree 2 environment or better. For power supply terminals 5,6 voltage inputs terminals 2,3 communication terminals 7,8,9: use 75°C copper (CU) conductor with wire size 13-20 AWG (0.5 to 2.5mm^2) stranded or solid. Terminal tightening torque of 4.4 Lb-In (0.5Nm) For current terminals 1,4 with maximum input current up to 600A:
Use minimum 120°C copper (CU) conductor with double wire size 300 AWG (150mm^2) stranded or solid or double busbar size 30mm x 5mm. Terminal tightening torque of 177 Lb-In (20Nm) For current terminals 1,4 with maximum input current below 600A:
Use minimum 120°C copper (CU) conductor with wire size or busbar size evaluated in the end product in order to guarantee the wire or busbar temperature below 120°C. Terminal tightening torque of 177 Lb-In (20Nm)
The suitability of the connection between the shunt and the end-use busbar shall be evaluated in the end product. A short circuit current rating matching that of the system where this device is installed must be tested if the shunt is relied upon for continuity of the busbar
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired

Standards:
Electromagnetic compatibility (EMC) – emissions and immunity: EN 61000-6-2, EN61000-6-3, IEC 62052-11
Electrical safety: EN 61010-1, IEC 62052-31, UL 61010-1, UL 61010-2-030, CAN/CSAC22.2 No. 61010-1-12, CSA C22.2 No. 61010-2-030
Metrology: VDE Anwendungsregel VDE-AR-E 2418-3-100 Annex A(Accuracy class A)
Security: WELMEC 7.2 (SW),

LED

Color Description
Green Status
Fixed: power on Blinking: communication
Amber Warning Fixed: fatal error Blinking overrange (temperature, current or voltage)
Red Pulse weight (kWh+): proportional to energy consumption: 0.001 kWh per pulse
Red Pulse weight (kWh-): proportional to exported energy: 0.001 kWh per pulse

Installing

  1. NOTICE: The product can only be installed inside a cabinet with IP54 degree of protection for outdoor installation and IP51 for indoor installation
    Installation
  2. Mount DCT1 on DIN rail (optional)
    Installation
  3. Fix the DCT1 to the bottom of cabinet (mandatory) with the screws (not included)
    A
    Installation
    B
    Installation
  4. Connect current (option A or B) and voltage inputs.
    Installation
    NOTICE: The use of a cable with cross section 150 mm2 or a 30mm x 5mm busbars is recommended
  5. Connect RS485 Modbus or SML port
    Installation
  6. If termination is needed, apply a 120 Ohm resistance among B+ and A7.
    Installation
  7. Connect power supply
    Installation
  8. Close the terminal cover
    Installation
  9. Seal the terminal cover
    Installation
  10. Turn on power and check correct operation
    Installation
  11.  Configure DCT1. Default parameters:
    Installation
    Address: 1. Baud rate: 9.6 kbps
  12. NOTICE: during operation, the controllling system must guarantee that the shunt temperature does not exceed 120° C/248° F
    Installation
  13. Dismantling DCT1
Voltage 150 … 1000 V dc
Min. current 2.5 A
Max. current 300 A
Start up current 0.2 A
Symbol Description
Warning Icon Danger
Note Icon Manual symbol
Disposal Icon The product is not to be discarded with normal household waste
Double insulation symbol Double insulation
Note Icon The indicated measurement is strongly recommended for the correct functioning of the device

User Manual User manual https://www.gavazziautomation.com/images/PIM/MANUALS/ENG/DCT1_IM_USE.pdf
User Manual UCS Desktop
https://www.gavazziautomation.com/images/PIM/OTHERSTUFF/ucs.zip

CARLO GAVAZZI Controls SpA via Safforze, 8 32100 Belluno (BL)Italy
www.gavazziautomation.com
info@gavazzi-automation.com
info: +39 0437 355811 /
fax: +39 0437 355880
QR Code
Company Logo

Documents / Resources

CARLO GAVAZZI DCT 1 A30 DC Transducer 150 to 1000 V Voltage Input [pdf] Instruction Manual
DCT 1 A30 DC Transducer 150 to 1000 V Voltage Input, DCT 1 A30, DC Transducer 150 to 1000 V Voltage Input, Transducer 150 to 1000 V Voltage Input, Voltage Input