SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol Warning icon . When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury.
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Warning icon WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing unit, always turn off all power to the unit. There may be more than one disconnect switch. Turn off the accessory heater power if applicable. Lock out and tag switch with a suitable warning label.
Warning icon WARNING
EXPLOSION HAZARD
Carrier 40MBFAQ Floor Console Ductless System 12K - icon Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
Warning icon CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at startup.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

PARTS LIST

Carrier 40MBFAQ Floor Console Ductless System 12K - parts1

  1. Air flow louver (at air outlet)
  2. Air inlet (with air filter installed)
  3. Display panel
  4. Drain pipe
  5. Connecting pipe
  6. Air inlet
  7. Air outlet

ACCESSORIES

Table 1 — Accessories

ACCESSORY  QUANTITY SHAPE
Literature package including owner’s manuals, installation instructions and warranty card 3 Carrier 40MBFAQ Floor Console Ductless System 12K - icon1
Wireless remote controller 1 Carrier 40MBFAQ Floor Console Ductless System 12K - icon2
Batteries 2 Carrier 40MBFAQ Floor Console Ductless System 12K - icon3
Heat insulation pipe 1 Carrier 40MBFAQ Floor Console Ductless System 12K - icon4
Copper nut 2 Carrier 40MBFAQ Floor Console Ductless System 12K - icon5
Air freshening filter 2 Carrier 40MBFAQ Floor Console Ductless System 12K - icon6

NOTES:
– If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall and enters the indoor unit. Doing so helps ensure rain drips from the connection pipe before it enters the wall.
– Piping and the interconnecting wiring are field supplied.
Table 2 — Indoor Unit Model Number

KBTUH V-PH-HZ ID MODEL NO.
12 208/230-1-60 40MBFAQ12XA3

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and servicing unit (see Fig. 3 — on page 6 for the minimum required distances between the unit and walls or ceilings).
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.

  • Minimum refrigerant line length, between the indoor and outdoor units, is 10 ft. (3 m).
  • Table 3 lists the pipe sizes for the indoor unit. Refer to the outdoor unit installation instructions for other allowed piping lengths and refrigerant information.

Table 3 — Indoor Unit Pipe Sizes

NAME 12K
LIQUID PIPE Ø1/4” (6.35)
GAS PIPE Ø1/2” (12.7)

WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied
14/3 power/communication wiring from the outdoor unit to the indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire.
To minimize communication interference: If installed in a high
Electromagnetic field (EMF) area and communication issues exist, a 14/2 stranded shielded wire can be used to replace L2 and (S) between outdoor unit and indoor unit – landing the shield onto ground in the outdoor unit only.
Warning icon WARNING
ELECTRICAL DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
Warning icon CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or any moving parts.
Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner.
NOTE: Before performing any electrical work, read these regulations.

  1. All wiring must comply with the local and national electrical codes, regulations and must be installed by a licensed electrician.
  2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
  3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and do not install the unit until the safety issue is properly resolved.
  4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
  5. If connecting power to wiring, a surge protector and main power switch should be installed.
  6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
  7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
  8. Make sure to properly ground the air conditioner.
  9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
  10. Do not allow wires to touch or rest against the refrigerant tubing, the compressor, or any moving parts within the unit.
  11. To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off, the power, always wait 10 minutes or more before touching the electrical components.
  12. Make sure that you do not cross your electrical wiring with your signal wiring. This may cause distortion and interference.
  13. The unit must be connected to the main outlet.
  14. No other equipment should be connected to the same power circuit.
  15. Connect the outdoor wires before connecting the indoor wires.

DIMENSIONS AND CLEARANCES

Carrier 40MBFAQ Floor Console Ductless System 12K - parts2

PRIOR TO INSTALLATION

REFRIGERANT PIPING CONNECTION
NOTE: When connecting refrigerant piping, do not allow substances or gases other than the specified refrigerant to enter the unit.
The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
NOTE: Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements listed in Table 4.
Table 4 — Maximum Length and Drop Height Based on Models

CAPACITY (BTU/H) PIPING LENGTH MAXIMUM DROP HEIGHT
12K 15/49 8/26

Warning icon CAUTION
The branching pipe must be installed horizontally. An angle of more than 10° may cause malfunction.
DO NOT install the connecting pipe until both indoor and outdoor units have been installed.
Insulate both the gas and liquid piping to prevent water leakage.
Step 1 – Cut Pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This ensures efficient operation and minimizes the need for future maintenance.

  1. Measure the distance between the indoor and outdoor units.
  2. Using a pipe cutter, cut the pipe a little longer than the measured distance.
  3. Ensure the pipe is cut at a perfect 90° angle.

Carrier 40MBFAQ Floor Console Ductless System 12K - parts3

Warning icon CAUTION
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting.
This drastically reduces the heating efficiency of the unit.
Step 2 – Remove Burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.

  1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
  2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.

Carrier 40MBFAQ Floor Console Ductless System 12K - parts4Step 3 – Flare Pipe Ends
Proper flaring is essential to achieving an airtight seal.

  1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
  2. Sheath the pipe with insulating material.
  3. Place are nuts on both ends of pipe. Ensure they are facing in the right direction, because you can not put them on or change their direction after flaring.Carrier 40MBFAQ Floor Console Ductless System 12K - parts5
  4. emove PVC tape from the pipe ends when ready to perform flaring work.
  5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.Carrier 40MBFAQ Floor Console Ductless System 12K - parts6
  6. Place the flaring tool onto the form.
    Table 5 — Specifications
    OUTER DIAM. IN.(MM) IN. (MM)
    MAX. MIN.
    Ø1/4” (6.35) 0.05 (1.3) 0.03 (0.7)
    Ø3/8” (9.52) 0.06 (1.6) 0.04 (1.0)
    Ø1/2” (12.7) 0.07 (1.8) 0.04 (1.0)
  7. Turn the flaring tool handle clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions.
    Table 6 — Piping Extension Beyond Flare Form
    Pipe Gauge Tightening Torque Flare Dimensions (A) (Unit: In/mm) Flare Shape
    Ø1/4” (Ø6.35) 13.27-14.75 lbsf-ft (180-00kgf.com) 0.33 /8.4 0.37 /8.7 Carrier 40MBFAQ Floor Console Ductless System 12K - parts7
    Ø3/8” (Ø9.52) 23.6-28.8 lbsf-ft (320-390kgf.cm) 0.52/ 13.2 0.53/ 13.5
    Ø1/2” (Ø12.7) 36.14-43.52 lbsf-ft (490-590kgf.cm) 0.64/ 16.2 0.65/ 16.5
  8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.

Step 4 – Connect the Pipes
Connect the copper pipes to the indoor unit first, then connect them to the outdoor unit. Connect the low pressure pipe then the high pressure pipe.

  1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
  2. Align the center of the two pipes to connect.Carrier 40MBFAQ Floor Console Ductless System 12K - parts8
  3. Tighten the flare nut as tight as possible by hand.
  4. Use an adjustable wrench, grip the nut on the unit tubing.
  5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in Table 6 on page 8.
    NOTE: Use an adjustable wrench and a torque wrench when connecting or disconnecting pipe to or from the unit.Carrier 40MBFAQ Floor Console Ductless System 12K - parts9Warning icon CAUTION
    • Be sure to wrap the insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
    • Ensure the pipe is properly connected. Over tightening may damage the bell mouth and under tightening may lead to leakage.
    NOTE: Carefully bend the tubing in the middle. DO NOT bend the tubing more than 90 degrees or more than three times.
  6. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.
    NOTE: DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
  7. Thread this pipeline through the wall and connect it to the outdoor unit.
  8. Insulate all the piping, including the valves of the outdoor unit.
  9. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.

Warning icon CAUTION
Ensure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).
NOTE: After connecting the piping, wrap the connecting pipe head with the insulation pipe in the accessory package.

INTERCONNECTING PIPING

Table 7 — Tightening

PIPE DIAMETER INCH (MM) TIGHTENING TORQUE
FT-LB N – M
Ø1/4” (6.35) 10 to 13 13.6 to 17.6
Ø3/8” (9.52) 24 to 31 32.5 to 42.0
Ø1/2” (12.7) 37 to 46 50.1 to 62.3
Ø5/8” (15.88) 50 to 60 67.7 to 81.3

Carrier 40MBFAQ Floor Console Ductless System 12K - parts10

CONDENSATE DRAIN CONNECTION

The unit is supplied with a drain connection to connect the drain piping. When installing condensate piping, follow these recommendations:

  • Condensate piping should slope downward in the direction of the condensate flow, with a minimum gradient of 1 in. per 100 inches.
  • When multiple units are connected to a common condensate drain, ensure the drain is large enough to accommodate the volume of condensate from all units. It is also recommended to place an air vent in the condensate piping to prevent any air locks.
  • Condensate piping must not be installed where it may be exposed to freezing temperatures.

Carrier 40MBFAQ Floor Console Ductless System 12K - parts11

ELECTRICAL

Connections
Remove the sensing device’s installation bearer (see Fig. 13).Carrier 40MBFAQ Floor Console Ductless System 12K - parts12

ELECTRICAL DATA

Table 8 — Electrical Data

INDOOR UNITS INDOOR FAN MAX FUSE CB AMP
V-PH-HZ FLA (A) HP SYSTEM POWER FACTOR (%)
12K 208-230/1/60 0.5 1/55 95.6 Refer to outdoor unit installation instructions. Indoor unit is powered by the outdoor unit.

CONNECTION DIAGRAM

Carrier 40MBFAQ Floor Console Ductless System 12K - parts13NOTE: For applications where gravity cannot be used for drainage, a condensate pump is required for proper draining.

WIRING DIAGRAM

Carrier 40MBFAQ Floor Console Ductless System 12K - parts14

INSTALLATION

NOTE: Panel installation should be performed after piping and wiring have been completed.
Step 1 – Select Installation Location
Before installing the indoor unit, select an appropriate location.
The following standards are provided to help select an appropriate location for the unit.
Proper installation locations meet the following standards:

  • Enough room exists for installation and maintenance
  • Enough room exists for the connection pipe and drainage
  • The ceiling is horizontal and its structure can sustain the weight of the indoor unit.
  • The air inlet and outlet are not blocked.
  • The airflow can fill the entire room.
  • There is no direct radiation from heaters.

DO NOT install the unit in the following locations:

  • Areas with oil drilling or fracking
  • Coastal areas with high salt content in the air
  • Areas with caustic gases in the air, such as hot springs
  • Areas that experience power fluctuations, such as factories
  • Enclosed spaces, such as cabinets
  • Kitchens that use natural gas
  • Areas with strong electromagnetic waves
  • Areas that store flammable materials or gas
  • Rooms with high humidity, such as bathrooms or laundry rooms

NOTE: Recommended distances between the indoor unit. The distance between the mounted indoor unit should meet the specifications illustrated (see Fig. 3 — on page 6).
Step 2 – Installing the Main Body

  1. After loosening the screws, remove the mounting plate from the unit.Carrier 40MBFAQ Floor Console Ductless System 12K - parts15NOTE: If the pipe comes out on the left, it is necessary to loosen the screws on the bottom mounting plate. If the pipe comes out in other directions, it is not necessary.
  2. Secure the mounting plate, with a tapping screw, onto the wall.
    NOTE: It is recommended to secure it to the wall according to the hanging hole indicated by the arrow on the mounting plate. The mounting plate must be installed horizontally.Carrier 40MBFAQ Floor Console Ductless System 12K - parts16
  3. Hang the indoor unit on the mounting plate. The unit’s bottom may touch the floor or remain suspended, however the unit must be installed vertically.

NOTE: After installation, the unit should remain horizontal without tilting.Carrier 40MBFAQ Floor Console Ductless System 12K - parts17Bottom Mounting Plate Installation
Installation with a baseboard
If there is a baseboard (see Figure 20) along the intended installation location, the bottom mounting plate (see Figure 21) needs to be straightened for unit installation. Use a pair of needle nose pliers (or a sheet metal hand seamer) to straighten the bottom mounting plate and then secure to the baseboard.
NOTE: The tab is used to secure the lineset when it comes from the left side of the unit (rear view). If the lineset comes from the right side, the tab is irrelevant and should be disregarded.Carrier 40MBFAQ Floor Console Ductless System 12K - parts18Installation without a baseboard
The bottom mounting plate is secured directly to the wall.Carrier 40MBFAQ Floor Console Ductless System 12K - parts19NOTE: To drain smoothly, the position of the drain pipe must resemble the position in Figure 22 when discharging on the right hand side.
Step 3 – Take the Indoor Unit Apart to Connect the Pipes

  1. Press and hold the two bottom straps, and then rotate to open the piping cover plate.Carrier 40MBFAQ Floor Console Ductless System 12K - parts20
  2. Remove the pipe cover plate and install the internal and external connecting pipes.

NOTE: Install the small piping first, and then the large piping.
Step 4 – Drill a Wall Hole for Connective Pipe

  1. Determine the location of the wall hole based on the location of the outdoor unit.
  2. Use a 2.5in (65mm) or 3.54in (90mm) hole saw, drill a hole in the wall.
    Ensure the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 0.5in (12mm). This ensures proper water drainage.
  3. Place the protective wall cuff in the hole. This protects the edges of the hole and helps seal it when you finish the installation.

Warning icon CAUTION
EQUIPMENT DAMAGE HAZARD
When drilling the wall hole, make sure to avoid wires and plumbing.Carrier 40MBFAQ Floor Console Ductless System 12K - parts21Step 5 – Connect the Drain Hose
The drainpipe is used to drain water away from the unit. An improper installation may cause unit and property damage.
Warning icon CAUTION
Insulate all piping to prevent condensation, which could lead to water damage.
If the drainpipe is bent or installed incorrectly, water may leak and cause a water-level switch malfunction.
In the HEAT mode, the outdoor unit discharges water. Ensure that the drain hose is placed in an appropriate area to avoid water damage and slippage.
DO NOT pull the drainpipe forcefully; doing so may disconnect it.
NOTE ON PURCHASING PIPES: Installation requires a polyethylene tube (exterior diameter = 1-1/2” (3.8cm), interior diameter = 1-1/4” (3.2cm), which can be obtained at your local hardware store or dealer.

  1. Cover the drainpipe with heat insulation to prevent condensation and leakage.
  2. Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the mouth of the hose and clip it firmly with a pipe clasp.Carrier 40MBFAQ Floor Console Ductless System 12K - parts22

NOTE ON DRAINPIPE INSTALLATION
When using an extended drainpipe, tighten the indoor connection with an additional protection tube. This prevents it from pulling loose.
The drainpipe should be pitch down at 1/8” per foot to prevent water from flowing back into the air conditioner.
Incorrect installation could cause water to flow back into the unit and flood.
When connecting multiple drainpipes, install the pipes as shown in Figure 26.Carrier 40MBFAQ Floor Console Ductless System 12K - parts23To ensure smooth drainage, the height difference between the wall outlet and the hanging plate must be greater than 19in(470mm).Carrier 40MBFAQ Floor Console Ductless System 12K - parts24Drainage pipe securing requirements
When installing the drainage pipe (field supplied), secure it with a tie or rope.Carrier 40MBFAQ Floor Console Ductless System 12K - parts25

WIRELESS REMOTE CONTROL HOLDER INSTALLATIONCarrier 40MBFAQ Floor Console Ductless System 12K - parts26

  1. Use the two screws supplied with the wireless remote control to attach the mounting bracket to the wall in a location selected by the customer and within operating range.
  2. Install the batteries in the remote control.
  3. Place the remote control into the remote control mounting bracket.

NOTE: For remote control operation, refer to the remote control’s owners manual.
OPTIONAL WIRED WALL-MOUNTED REMOTE CONTROL INSTALLATION
NOTE: For setup instructions, refer to the Wired Controller Installation Manual (KSACN0801AAA).
SYSTEM CHECKS

  1. Conceal the tubing where possible.
  2. Ensure the drain tube slopes downward along its entire length.
  3. Ensure all tubing and connections are properly insulated.
  4. Fasten tubes to the outside wall, when possible.
  5. Seal the hole through which the cables and tubing pass.

INDOOR UNIT

  1. Do all remote control buttons function properly?
  2. Do the display panel lights work properly?
  3. Does the air deflection louver function properly?
  4. Does the drain work?

Explain the Following Items To the Customer (with the aid of the Owner’s Manual):

  1. How to turn the air conditioner on and off; selecting COOLING, HEATING and other operating modes; setting a desired temperature; setting the timer to automatically start and stop the air conditioner operation; and all other features of the remote control and display panel.
  2. How to remove and clean the air filter.
  3. How to set the air deflection louver.
  4. Explain care and maintenance.
  5. Present the owner’s manual and installation instructions to customer.

TROUBLESHOOTING

Warning icon CAUTION
SAFETY PRECUATIONS
If any of the following conditions occurs, turn off your unit immediately:
The power cord is damaged or abnormally warm
You smell a burning odor
The unit emits loud or abnormal sounds
A power fuse blows or the circuit breaker frequently trips
Water or other objects fall into or out of the unit
DO NOT ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER IMMEDIATELY!
Common Issues
The issues listed in Table 9 are not malfunctions and in most situations will not require repairs.
Table 9 — Common Issues

ISSUE POSSIBLE CAUSES
Unit does not turn on when pressing ON/OFF The unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be restarted within three minutes of being turned off.
Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-heating/Defrost) indicators are illuminated, or the Operation light is illuminated and the LCD screen displays “dF”, the outdoor temperature is too cold and the unit’s anti-cold wind is activated to defrost the unit.
The unit changes from COOL mode to FAN mode The unit may change its setting to prevent frost from forming on the unit. Once the temperature increases, the unit starts operating in the previously selected mode again.
The set temperature has been reached, at which point the unit turns off the compressor. The unit continues operating when the temperature fluctuates again.
The indoor unit emits white mist In humid regions, a large temperature difference between the room’s air and the conditioned air can cause white mist.
Both the indoor and outdoor units emit white mist When the unit restarts in HEAT mode after defrosting, white mist may be emitted due to moisture generated from the defrosting process.
The indoor unit makes noises A squeaking sound is heard when the system is OFF or in COOL mode. The noise is also heard when the drain pump (optional) is in operation.
A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit’s plastic parts.
Both the indoor unit and outdoor unit make noises Low hissing sound during operation: This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units.
Low hissing sound when the system starts, has just stopped running, or is defrosting: This noise is normal and is caused by the refrigerant gas stopping or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts caused by temperature changes during operation can cause squeaking noises.
The outdoor unit makes noises The unit will make different sounds based on its current operating mode.
Dust emits from either the indoor or outdoor unit The unit may accumulate dust during extended periods of non-use, which will be emitted when the unit is turned on. This can be mitigated by covering the unit during long periods of inactivity.
The unit emits a bad odor The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.
The unit’s filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate During operation, the fan speed is controlled to optimize product operation.

NOTE: If problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as the model number.
NOTE: When troubles occur, check the following points before contacting a repair company.
Table 10 — Troubleshooting

RUNNING LAMP TIMER LAMP DISPLAY MALFUNCTION AND PROTECTION DEFINITION
Carrier 40MBFAQ Floor Console Ductless System 12K - icon141 time X E0 Indoor EEPROM malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon142 times X E1 Indoor and outdoor unit communication malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon144 times X E3 Indoor fan speed malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon145 times X E4 Indoor room temperature sensor error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon146 times X E5 Evaporator coil temperature sensor leak
Carrier 40MBFAQ Floor Console Ductless System 12K - icon147 times X EC Refrigerant leak detection system malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon148 times X EE Water level alarm malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon1411 times X Ed Wrong outdoor unit
Carrier 40MBFAQ Floor Console Ductless System 12K - icon141 time Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F0 Overload protection
Carrier 40MBFAQ Floor Console Ductless System 12K - icon142 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F1 Outdoor temperature sensor error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon143 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F2 Outdoor condenser pipe sensor error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon144 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F3 Discharge air temperature sensor error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon145 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F4 Outdoor EEPROM error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon146 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F5 Outdoor fan speed (DC fan motor only) malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon147 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F6 T2b sensor error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon148 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F7 Auto-lifting panel communication error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon149 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F8 Auto-lifting panel malfunction
Carrier 40MBFAQ Floor Console Ductless System 12K - icon1410 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 F9 Auto-lifting panel is open
Carrier 40MBFAQ Floor Console Ductless System 12K - icon141 time Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P0 Inverter module IPM protection
Carrier 40MBFAQ Floor Console Ductless System 12K - icon142 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P1 High/Low voltage protection
Carrier 40MBFAQ Floor Console Ductless System 12K - icon143 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P2 Compressor top overheating protection
Carrier 40MBFAQ Floor Console Ductless System 12K - icon144 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P3 Outdoor low temperature protection
Carrier 40MBFAQ Floor Console Ductless System 12K - icon145 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P4 Compressor drive error
Carrier 40MBFAQ Floor Console Ductless System 12K - icon146 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 Mode conflict
Carrier 40MBFAQ Floor Console Ductless System 12K - icon147 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P6 Compressor low-pressure protection
Carrier 40MBFAQ Floor Console Ductless System 12K - icon148 times Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 P7 Outdoor IGBT sensor error

NOTE: Carrier 40MBFAQ Floor Console Ductless System 12K - icon14 FLASH, Carrier 40MBFAQ Floor Console Ductless System 12K - icon15 LIGHT, X EXTINGUISHED

DUCTLESS START-UP CHECKLIST – Single Zone

Installation Data
Site Address:___________________________
City:________________________________
State:_______________________________
Zip Code:____________________________
Installing Contractor:_______________________
Contractor Contact #: ( ) _____-___________
Job Name:________________________________
Start-up Date:_____________________________
Distributor:_______________________________
System Details

UNITS MODEL NO. SERIAL NO. CONTROLLER
OUTDOOR UNIT
INDOOR UNIT A

Are the outdoor unit and indoor unit compatible?
YES:____________
NO:____________
Wiring Electrical
Wire Size and Type Used?
AWG:________________
TYPE:_______________
Are there any breaks, splices, wire nuts or butt connectors between the outdoor unit and the indoor unit?
YES:____________
NO:____________
Was the wiring from the outdoor unit port to the correct indoor unit verified?
YES:____________
NO:____________
REMARKS:_________________________________
Voltage Check
Wiring: Single Zone

Outdoor Unit Disconnect 1(L1):GND Outdoor Unit Terminal Block 1(L1):GND NOTES:                                                              
2(L2):GND 2(L2):GND
1(L1):L2(2) 1(L1):2(L2)
Indoor Unit Voltage Check @ Outdoor Unit 1(L1):GND Indoor Unit Voltage Check @ Indoor Unit 1(L1):GND NOTES:                                                              
2(L2):GND 2(L2):GND
1(L1):2(L2) 1(L1):2(L2)
2(L2):3(S) 2(L2):3(S)
Outdoor Unit Disconnect 1(L1):GND Outdoor Unit Terminal Block 1(L1):GND NOTES:                                                              
2(L2):GND 2(L2):GND
1(L1):L2(2) 1(L1):2(L2)
Indoor Unit Voltage Check @ Outdoor Unit 1(L1):GND Indoor Unit Voltage Check @ Indoor Unit 1(L1):GND NOTES:                                                              
2(L2):GND 2(L2):GND
1(L1):2(L2) 1(L1):2(L2)
2(L2):3(S) 2(L2):3(S)

Ductless Start-Up Checklist (CONT)
Piping
Leak Check:
System held 500 psig (max. 550psi) for a minimum of 30 minutes using dry nitrogen.
YES:____________
NO:____________
Evacuation Method:

  • Was the Triple Evacuation Method used as outlined in the installation manual? YES:______ NO:______
  • Was the Deep Vacuum Method used as outlined in the installation manual? YES:______ NO:_______
  • Did the System Hold 500 microns for 1 hour? YES:______ NO:_______
  • Does the line set match the diameter of the evaporator connections? YES:______ NO:_______
  • For Conventional Fan Coils, does the line set match the outdoor unit size? YES:______ NO:_______

Single Zone Piping:

Has the liquid pipe length been measured and the additional charge calculated? Size:___________ Length:_________ Charge:____________

NOTES:
PORT LIQUID SIZE SUCTION SIZE LENGTH CHARGE NOTES:                                                                  
A

Performance Check

For 1:1 Single Zone Systems: Adjust the set-point to create an operational call for the desired testing operation. Allow the system to run for a minimum of 10 min. and record the following details:
(Operational data recorded on applicable heads with the wireless remote controller’s Point Check function)
UNIT SET-POINT MODE T1 T2 T3 T4 Tb Tp Th LA/Lr
A

NOTE:

  • T1 – Ambient Space Temperature Sensor
  • T2 – IDU Coil Temperature Sensor
  • T3 – Outdoor Coil Temperature Sensor
  • T4 – Outdoor Ambient Temperature
  • Tb – Suction Line Temperature @PMV
  • Tp – Discharge Temperature Sensor
  • Th – IPM Board Temperature
  • LA/Lr – PMV Position

Error Codes
Were there any error codes present at start-up? YES:______ NO:______

Indoor Unit Error Code: Notes:
Outdoor Unit Error Code:
Wall Controller:
24V Interface:

Comments: ________________________________________

Carrier logo© 2023 Carrier. All rights reserved.
Edition Date: 01/23
Catalog No: IM-40MBFAQ-01