Temperature Quality:

The product is designed to maintain a good temperature quality within the specified range. The low window threshold indicates the lower limit at which the temperature should be maintained for optimal performance, while the high window threshold represents the upper limit.

Humidity Quality:

Similarly, the product ensures good humidity quality within the defined range. The low window threshold signifies the minimum humidity level, while the high window threshold indicates the maximum humidity level for optimal operation.

Frequently Asked Questions

  • Q: What should I do if the temperature exceeds the high window threshold?
    • A: If the temperature surpasses the high window threshold, consider adjusting the settings of the product to lower the temperature within the recommended range.
  • Q: How can I monitor the humidity levels of the product?
    • A: You can use a separate humidity monitor or device to track the humidity levels and ensure they are within the specified low and high window thresholds.

Copyright ©2024. All rights reserved. This document contains Senva Sensors proprietary information and may not be reproduced or distributed without written permission.

Rev. Release Date By Description of Change ECR
OA   NAK Initial Release
OB 6/10/2022 NJS Updates for engineering Cl release
oc 9/22/2022 NJS Updates for CO and Ozone readings
OD 1/9/2024 NJS Updates for new features
         

See Also:

152-0401

154-0043

154-0044

Display Navigation

Congratulations on installing your new Senva TotalSense Air Quality Sensor! This OLED Parameter Map assumes the first stage of installation is complete, with the TotalSense connected and powered. The OLED display should show the home screen when any button is pressed. If you see a lock icon, hold the up and down arrows for 5 seconds to unlock.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (4)

If you see a lock icon, hold the up and down arrows for 5 seconds to unlock.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (5)

To change any setting, press enter to see setup menu and navigate to desired parameter and press enter again to choose. For example, to adjust display parameters, access the setup menu by pressing the ‘enter’ button once to access the setup and once more to access the “display” menu and then select “center display”.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (6)

Select your value for center display and then select “go back” until you are back at the home screen.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (7)

To adjust a numerical setting, set each digit individually and press enter to move cursor to the left. When all digits are set, the value will be saved when enter is pressed again.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (8)

To view comms, navigate to “view comms” in the main menu.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (9)

To view current readings without configuring display, navigate to “view readings” in the main menu.TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (10)

Display SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (11) TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (12)

 

Parameter

 

Description

 

Selections

 

Functionality

 

Settings> Display> Screen Lock

 

Lock out access to home screen and settings

 

Enable

Screen lock mode will initiate after 60s of inactivity. Screen saver will be shown until device is unlocked by holding the up and down buttons for Ss.
Disable (default) Display will show home screen when any button is pressed.
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings> Display> Screen Saver

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Choose what to display when inactive

 

Off

Display will turn off after 60s if inactivity. No screen saver will be displayed. Screen will remain blank until any button is pushed.
 

Air Quality Icon

The AQ leaf icon will be displayed when inactive in either

green, yellow, or red depending on Error! Reference source not found..

Air Quality Msg (default) Good air quality (green), Fair air quality (yellow), or poor (red) air quality will be displayed when inactive based on

Error! Reference source not found..

 

CO2 reading

 

Current CO2 reading will be displayed in PPM.

 

Temp reading

Current Temp reading will be displayed in either °For 0 C. See Temp Settings.
 

RH reading

 

Current RH reading will be displayed in%.

 

PM

PMx value will be displayed in center (µg/m 3 . Choose

)

particle size in PM Settings. Readings over 999 will be shown as mg/m 3

 

TVOC PPB

 

Current TVOC reading will be displayed in center (PPB).

 

TVOC µ g/m3

Current TVOC reading will be displayed in center (µg/m 3 .

)

Readings over 999 will be shown as mg/m 3

co  

Current CO readings will be shown (PPM).

 

Ozone

 

Current Ozone (03) readings will be shown (PPB).

 

Home Readings

Display will cycle through all present sensor readings that are chosen to be displayed on the main screen. See parameters: Center, Upper right, Lower Left, and Lower

Right.

 

All Readings

Display will cycle through all present sensor readings from this list: temp, RH, CO2, TVOC, PM, and Air Quality.
Settings> Display> Menu Brightness Adjust the brightness of the screen Low, medium, high

(default: high)

 

Adjust the value to increase or decrease the brightness of home screen and menu display.

 

Parameter

 

Description

 

Selections

 

Functionality

Settings> Display>

ss

Brightness

Adjust the brightness of the screen saver Low, medium, high (default: low)  

Adjust value to increase or decrease the brightness of the screen saver.

Settings> Display>

ss

Timeout

Adjust hoe Jong before the screen saver comes on  

1-120 minutes

(Default: 1)

 

This will set how long the main screen shows before it times out and the screen saver comes on.

Analog Parameters

 

Parameter

 

Description

 

Selections

 

Functionality

     

None

 

No signal will be generated

     

CO2

CO2 reading will be output by analog output 1. Adjust output scale in PPM in CO2 Settings.
     

RH

Relative humidity reading will be output by analog output 1. Adjust output scale in% in

RH Settings.

   

Analog out 1 reading (terminals 01

or02)

 

Temp

Temp reading will be output by analog output 1. Adjust output scale in °Fin Temp Settings.
 

TVOC

 

TVOC reading will be output by analog output 1. Adjust output scale in PPM in lVOC Settings.

Settings> Analog Output 1> Source  

Default will be set to first available sensor in this order: CO2, TVOC,RH,

Temp, slider

 

Temp Slider

Slider reading will be output by analog output 1. Please

note this reading is in addition to a resistive reading that can be read on “slider” terminals.

 

PIO Temp

Sets the output to a PIO controller using the temperature setpoint as the baseline, adjust this setpoint in Temp Settings.
PIO CO2 Sets the output to a PIO controller using the CO2

setpoint as the baseline, adjust this setpoint in CO2

Settings.

    PIO Temp Set- Point Sets the output to a PIO controller using the temperature slider as the baseline, adjust this setpoint in Temp Settings.
    co CO reading will be output by analog output 1. Adjust output scale in PPM in lVOC Settings.
     

Ozone

Ozone (03) reading will be output by analog output 1. Adjust output scale in PPM in lVOC Settings.
Settings>     This value corresponds to the lowest point on an analog
Analog Min voltage 0-lOV scale. For a 0-1OV signal, set to OV. For a 2-1OV signal,
Output 1> output for O1 (default OV) set to 2V. This will override any analog dip switch
MinV     settings.
Settings>     This value corresponds to the highest point on an
Analog Max voltage 0-lOV analog scale. For a 0-1OV signal, set to 1OV. For a 0-SV
Output 1> output for O1 (default 1OV) signal, set to SV. This will override any analog dip switch
MaxV     settings.
Settings> Analog Output 1> Min A  

Min current output for 02

 

0-20mA

(default 4mA)

This value corresponds to the lowest point on an analog scale. For a 4-20mA signal, set to 4mA. For a 0-20mA signal, set to OmA.
Settings> Analog Output 1> Max A  

Max current output for 02

 

0-20mA

(default 20mA)

 

This value corresponds to the highest point on an analog scale. For a 0-20mA or 4-20mA signal, set to 20mA.

 

 

 

 

Settings> Analog Output 1> PIO Invert

 

 

 

 

 

PID Invert

Enable This setting will invert the overall error signal (R- SP instead of (SP – R)
Disable This setting disabled will leave the overall error signal calculated as SP-R
For CO2 and cooling applications do not enable the PID invert. These

applications require more cooling or airflow when the temperature or CO2 level increases and vice versa, no inversion is necessary.

Enable PID if you need the analog signal to decrease when your measurement increases and vice-versa. For example, a heating process would need to increase the amount of heat when the temperature

decreases.

Settings> Analog Output 1> PIO KP  

Proportional Coefficient

 

0-100

(default 0)

 

Sets the Proportional gain PID Coefficient

Settings> Analog Output 1>

PIOK;

 

Integral Coefficient

 

0-100

(default 0)

 

Sets the Integral gain PID Coefficient

Settings> Analog Output 1>

PIO Kci

 

Derivative Coefficient

 

0-100

(default 0)

 

Sets the Derivative gain PID Coefficient

Settings for Analog Out 2 (four outputs 03 and 04) and Analog Out 3 (for outputs 05 and 06) will have the same options asshown above*.

  • Default source setting for analog out 2 (if at least 2 of ‘source’ sensors are present) is first available sensor in this order: TVOC, RH, Temp, slider.
  • Default source setting for analog out 3 (if at least 3 of ‘source’ sensors are present) is first available sensor in this order: RH, Temp, slider.
  • PID output controls are only available on Analog output 1 or Analog output 3 for the comms +analog device.

Air Quality Settings14 13TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 14

Source Parameters

CO2 SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 15

PM SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 16 TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 17

RH SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 21

Temp SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 19TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 20

TVOC SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 21

CO SettingsTotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig 22

 

CO Settings

>CO

 

Current reading of the CO

 

 

Ready Only

 

This will allow the user to view the current CO readings in the menu, so the user can see when sensor readings have stabilized while calibrating.

CO Settings

> Apply Span

Starts the CO calibration process —- To calibrate the sensor this setting is to be used. See the Total sense CO calibration guide for further instructions.
APPLY
CO Settings

> Apply Zero

Applies a Zero offset to the CO —- To apply a zero calibration to the sensor this setting is

to be used. See the Total sense CO calibration guide for further instructions.

APPLY
CO Settings

> Reset Factory Cal

Resets device calibration —- This setting will be used to reset the CO sensor to it factory default calibration scaling.
APPLY
CO Settings

> Analog Out Min

 

Min scale for

CO analog

 

0-200

(default: 0)

This value corresponds to the lowest point on an analog scale for a CO reading. This will correspond to any analog output that has CO selected as a source in Analog Parameters.
CO Settings

> Analog Out Max

 

Max scale for

CO analog

 

0-200

(default: 200)

This value corresponds to the highest point on an analog scale for a CO reading. This will correspond to any analog output that has CO selected as a source in Analog Parameters.

Ozone Settings

 

Parameter

 

Description

 

Selections

 

Functionality

03 Settings

>Cal Expiration

Days left until calibration  

Read only

This will show how many days until the device needs to be recalibrated.
03 Settings

> Sensor Life

 

Days left of sensor life

 

Read Only

This will show how many days are left in the sensor’s lifetime. The ozone sensor has a 5-year expected lifetime.
 

03  Settings

> Test Gas

 

Calibration Test gas used

 

default: 1000PPM

This is to set the concentration of Ozone gas that is used for device calibration. This value will be used to adjust the readings of the Ozone sensor when calibration is performed.
 

03 Settings

> Ozone

 

The current reading of the CO

 

 

Ready Only

 

This will allow the user to view the current Ozone readings in the menu, so the user can see when sensor readings have stabilized while calibrating.

03 Settings

> Apply Span

Starts the CO calibration process —- To calibrate the sensor this setting is to be used. See the Total Sense ozone calibration guide for further instructions.
APPLY
 

03 Settings

> Apply Zero

 

Applies a Zero offset to the CO

   

To apply a zero calibration to the sensor this setting is to be used. See the Total Sense ozone calibration guide for further instructions.

 

APPLY

03 Settings

> Reset Factory Cal

Resets device calibration —- This setting will be used to reset the ozone sensor to it factory default calibration scaling.
APPLY
03 Settings

> Analog Out Min

 

Min scale for

CO analog

 

0-200

(default: O)

This value corresponds to the lowest point on an analog scale for ozone reading. This will correspond to any analog output that has ozone selected as a

source in Analog Parameters.

03 Settings

> Analog Out Max

 

Max scale for

CO analog

 

0-200

(default: 200)

This value corresponds to the highest point on an analog scale for ozone reading. This will correspond to any analog output that has ozone selected as a

source in Analog Parameters.

Temp Setpoint Settings

 

Parameter

 

Description

 

Selections

 

Functionality

Temp setpoint Settings> Show Update Display slider changes Show this will set the device so that the display will show when the Temp setpoint is adjusted.
Hide
 

Temp setpoint Settings > Min Temp

 

Min scale for slider analog and display

 

 

-40 to 122°F

(default: 50°F)

This value corresponds to the lowest position of the slider and, if using slider as analog output, the minimum analog point. This will correspond to any analog output that has temp slider selected as a source in Analog Parameters. This will not affect the slider

resistive output.

 

Temp Setpoint Settings> Max temp

 

Max scale for slider analog and display

 

 

-40 to 122°F

(default: 95°F)

This value corresponds to the highest position of the slider and, if using slider as analog output, the maximum analog point. This will correspond to any analog output that has temp slider selected as a source in Analog Parameters. This will not affect the slider’s resistive output.

Relay Settings

 

Parameter

 

Description

 

Selections

 

Functionality

 

 

 

 

 

Relay Settings> Source

 

 

 

 

Which measurement will activate setpoint relay

 

None

 

Relay will never change from “normal” state.

 

CO2 (default)

Relay will change state when CO2 reading exceeds Turn-On value, set as a%.
RH Relay will change state when RH reading exceeds Turn-

On value, set as a%.

 

Temp

Relay will change state when Temp reading exceeds Turn-On value, set as a%.
 

TVOC

Relay will change state when TVOC reading exceeds Turn-On value, set as a%.
 

Parameter

 

Description

 

Selections

 

Functionality

     

PIR

 

Relay will change state when PIR senses motion.

 

Air Quality

Relay will change state when any sensor reading exceeds “fair” thresholds described in Error! References

ource not found..

co Relay will change state when CO reading exceeds Turn- On value, set as a%.
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay Settings> Turn On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Threshold for relay activation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0-100.00%

(default: depends on source selection)

Based on full scale range of the selected sensor, set the value above which the relay will activate. For example, if CO2 is selected, its full available range is 0-10,000 PPM, so a setpoint of 800 PPM would correspond to an 8.00% threshold setting. For temperature, the full range is -40 to 122°F, so a setpoint of 70°F would correspond to a threshold value of 68%. Use this equation to determine threshold setting for temp in °F: (T+40)/162*100. This setting is ignored for PIR and G/F source selections.

Display will show the calculated value as you adjust this setting. The below shows the values that are set by default when each source is selected as well as the calculated value for each.

  Source Selection Range Default Turn-on Threshold Calculated Turn-on value Default Turn-off Threshold Calculated Turn-off value  
CO2 0-10,000

PPM

8.0% 800 PPM 7.0% 700 PPM  
RH 0-100% RH 60% 60%RH 55% 55% RH  
Temp* -40-122

OF

74% 80°F 73% 78°F  
TVOC 0-10000

µg/m3

4.0% 400

µg/m3

3.5% 350

µg/m3

 
co 0-200

PPM

50% l00PPM 40% S0PPM  
Ozone 0-500

PPM

20% l00PPM 16% S0PPM  
 

Relay Settings> Turn Off

 

Threshold for relay deactivation

0-100.00%

(default: depends on source

selection)

Based on full scale range of the selected sensor, set the value below which the relay will de-activate. For example, to deactivate relay when CO2 setting reaches 790, set this threshold value to 7.90%.
 

Parameter

 

Description

 

Selections

 

Functionality

 

Relay Settings> Polarity

 

N.O./N.C.

selection

 

N.O. (default), N.C.

A N.O. (normally open) relay will be in the open state until it is activated, i.e., turn-on threshold is met, at which time it will close. A N.C. (normally closed) relay will be in the closed state until it is activated, at which

time it will open.

Relay Settings> Min On  

Min on time

 

1-240s

(default: 3s)

When relay activates, it will not deactivate until this time has lapsed, regardless of the turn-off setting. The relay will deactivate only when this time has expired

AND the turn-off threshold is met.

Relay Settings> Min Off  

Min off time

 

1-240s

(default: 3s)

When relay de-activates, it will not activate again until this time has lapsed, regardless of the turn-on setting. The relay will re-activate only when this time has

expired AND the turn-on threshold is met.

PIR Settings

 

Parameter

 

Description

 

Selections

 

Functionality

 

PIR Settings

>

Sensitivity

 

Adjust sensitivity of PIR motion sensor

 

 

0-100

(default: 80)

Sensor sensitivity can be adjusted from 0-100. The default of 80 achieves the specified distance and degree. If nuisance triggers occur or a further sensing distance is required, this value can be decreased and increased accordingly. See Figure 3 for a visual

representation of this sensitivity value.

 

PIR Settings

>

Occupied Delay

 

 

Time PIR stays active after event

 

 

1-120 min

(default: 10 min)

This is the number of minutes the occupancy state will remain active after each motion event is detected. This applies to the “occupancy” BACnet and Modbus point as well as the output relay state, if set to PIR in
      Relay Settings.

TotalSense-154-0042-0D-Outside-Air-PIR-Wall-fig (13)

Advanced Settings & Diagnostics

Advanced Settings

 

Parameter

 

Description

 

Selections

 

Functionality

Advanced Settings>

Reset

Reset factory defaults No (default), Yes  

Set to “yes” to restore all factory default settings.

Diagnostics

 

Parameter

 

Description

 

Status

 

Action

 

 

 

 

 

 

Advanced Settings> Diagnostics

> System Status

 

 

 

 

This will display several possible statuses in binary. All zeros indicate no errors or warnings are present.

 

00000001 = EEPROM

hardware fault

 

Consult factory.

 

00000010 = EEPROM data

corruption

 

Consult factory.

00000100 = EEPROM write

error

 

Consult factory.

00001000 = Device is currently using factory defaults  

Reset to factory defaults. Consult factory.

 

00010000 = Sensor alert

See individual sensor statuses for more information. Balded statuses will trigger this alert.
 

 

 

 

 

 

Advanced Settings> Diagnostics

>CO2

Status

 

 

 

This will display several possible statuses in binary. All zeros indicate no errors or warnings are present.

 

00000001 = Sensor hardware fault

 

Consult factory.

 

00000010 = Sensor data error

 

Consult factory.

 

00000100 = Sensor not Ready

 

Consult factory.

 

 

00001000 = Pressure Compensation not applied

 

 

No action necessary. Default value (101kPA) is used for pressure compensation.

 

Parameter

 

Description

 

Status

 

Action

  This will display several 00000001 = Sensor hardware fault  

Consult factory.

Advanced possible    
Settings> statuses in    
Diagnostics

> RH Status

binary. All

zeros indicate no errors or

00000010 = Sensor data error  

Consult factory.

  warnings are    
  present.    
 

 

Advanced Settings> Diagnostics

>Temp Status

This will display several possible statuses in binary. All zeros indicate no errors or 00000001 = Sensor hardware fault  

Consult factory.

 

00000010 = Sensor data error

 

 

Consult factory.

  warnings are    
  present.    
    00000001 = Sensor hardware (12C) fault  

Consult factory.

    00000010 = Sensor error (bad initialization range)  

Consult factory.

   

 

This will

00000100 = Sensor error (Gas timeout)  

Consult factory.

  display    
 

 

Advanced Settings> Diagnostics

>TVOC

Status

several possible statuses in binary. All zeros indicate no errors or warnings are

present.

00001000 = Sensor error (other) error  

Consult factory.

 

00010000 = Training cycle not complete

No action necessary. Sensor is in “training mode”. This may take up to 7 days. See Installation Manual for explanation.
   
    00100000 = Sensor not ready (4-minute warmup) No action is necessary. Please wait for the 4- minute warm up period to expire.
     

01000000 = Temperature

 

No action is necessary. Default value (25C) is

    compensation not applied used for temperature compensation.
 

Parameter

 

Description

 

Status

 

Action

     

10000000 = Pressure compensation not applied

 

No action necessary. Default value (101kPA) is used for pressure compensation.

 

 

 

 

 

 

 

 

Advanced Settings> Diagnostics

>PM

Status

 

 

 

 

 

 

This will display several possible statuses in binary. All zeros indicate no errors or warnings are present.

00000001 = Sensor communication error  

Consult factory.

00000010 = Sensor Data Error  

Consult factory.

 

00000100 = Sensor not ready

 

 

Consult factory.

00001000 = Sensor fan speed warning  

Warning only. No action necessary.

 

00010000 = Sensor fan failure

 

 

Consult factory.

00100000 = Sensor laser failure  

Consult factory.

 

 

 

Advanced Settings> Diagnostics

> Pressure

Status

This will display several possible statuses in binary. All zeros indicate no errors or warnings are present. 00000001 = Sensor hardware fault  

Consult factory.

00000010 = Sensor data error  

Consult factory.

 

00000100 = Sensor not ready

 

 

Consult factory.

TVOC Molecular Weights

Senva’s TVOC sensor uses an Ethanol reading to determine a raw TVOC value. Additionally, conversion from ug/m uses the molecular weight of Ethanol. To scale based on a different gas baseline, choose the appropriate gas from the list below and enter the scale factor in TVOC Settings. Please note that the sensor is measuring TOTAL VOCs, so adjusting the scale factor will not necessarily result in a gas-specific reading unless, in special cases, that is the only expected VOC present in the area. It is recommended to use the 1.0 scale factor in most cases. The RESET standard suggests calculating TVOC based on the molecular weight of Isobutelyne (scale factor: 1.218).

Data Source: http://aqt-vru.com/emissions/complete-list-of-vocs/

 

Contamination

 

Name

 

Molecular Weight

 

Scale factor

ACETYLENE ACETYLEN 26.04 0.565
FORMALDEHYDE FORMALD 30.03 0.652
METHANOL MEOH 32.04 0.695
PROPANE PROPANE 44.1 0.957
ETHANOL ETOH 46.07 1.000
DIMETHYL ETHER ME-O-ME 46.07 1.000
METHYL CHLORIDE CH3-CL 50.49 1.096
1,3-BUTADIENE 13-BUTDE 54.09 1.174
ISOBUTENE ISOBUTEN 56.11 1.218
N-BUTANE N-C4 58.12 1.262
ISOBUTANE 2-ME-C3 58.12 1.262
ACETIC ACID ACETACID 60.05 1.303
ISOPROPYL ALCOHOL I-C3-OH 60.1 1.305
ETHYLENE GLYCOL ET-GLYCL 62.07 1.347
ISOPRENE ISOPRENE 68.12 1.479
BUTANAL 1C4RCHO 72.11 1.565
N-PENTANE N-C5 72.15 1.566
ISOPENTANE 2-ME-C4 72.15 1.566
HYDROXY ACETONE HOACET 74.08 1.608
ISOBUTYL ALCOHOL I-C4-OH 74.12 1.609
BENZENE BENZENE 78.11 1.695
TOLUENE TOLUENE 92.14 2.000
M-XYLENE M-XYLENE 106.17 2.305
O-XYLENE O-XYLENE 106.17 2.305
P-XYLENE P-XYLENE 106.17 2.305
TERPENE TERPENE 136.24 2.957