Honeywell Vista 50P
Wiring Uplink’s Communicators
and Programming the Panel
Vista 50P Wiring Uplink’s Communicators and Programming the Panel
CAUTION:
- It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
- Do not route any wiring over circuit board.
- Full panel testing, and signal confirmation, must be completed by the installer.
NEW FEATURE: For 5530M Communicators, the status of the panel can be retrieved not only from the status PGM but now also from the Open/Close reports from the dialler.
IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the initial pairing procedure.
Wiring the 5530m communicators to Honeywell Vista 50P for events reporting and remote control via keybus:
Wiring and Programming Uplink Communicators to Honeywell Vista 50P
Wiring the 5530m communicators to Honeywell Vista 50P for events reporting and remote control via keyswitch:
Programming the Honeywell Vista 50P Alarm Panel via the Keypad
Enable Contact ID reporting:
Keypad Display | Keypad Entry | Action Description |
Disarmed | 4140,8,00 | To enter programming mode. |
Program mode | *30, 1 | To select Touch tone for dialing method. |
PABX | *32 | To qo to “Primary subscriber Account #”. |
Prim.Subs. Acct# | 01, 02, 03, 04 | Enter desired account number (in HEX). 1234 is just an example. |
Primary Phone | 123456, * | Enter desired phone number (123456 is an example). Press * to save. |
Enter fill field | *45 | To qo to “Primary format”. |
Primary format | 1 | 1 is the value for ContactlD. |
Low Speed Format | *81, 01, 01, * | To enable Open/Close reports. |
Enter fill field | *99 | To exit programming mode. |
Enable Keyswitch Zone and Status Output:
Keypad Display | Keypad Entry | Action Description |
Disarmed | 4140,8,00 | To enter programming mode. |
Program mode | *15, 1 | To assign keyswitch to partition 1 (zone 07). |
Confirmation of arming ding | *40, 1 | To enable Open/Close reports for Keyswitch. |
Normally closed or EOLR | *94, *94 | Press *94 until “200” is shown in the lower right corner. |
Alt Program Mode | *20, 1 | To configure pin 5 on 17 connector to follow Keyswitch RED behavior. |
Enter fill field | *99 | Press *99 a couple of times until you exit programming mode. |
Programming an Alpha Keypad Address
Keypad Display | Keypad Entry | Action Description |
DISARMED | 4140,8,00 | To enter Programming Mode. |
Program Mode | #93 | To go to “Menu Mode” |
Zone Prog. ? | 0 … 1 | Press 0 until “Device Prog.” is shown. Press 1 to enter. |
Device Address 01-30, 00=Quit |
21* | To enter Address 21 |
21 Device Type | 1* | To select Alpha Keypad Console |
21 Console Part. | 1* | To assign the Alpha Keypad Console to Partition 1 |
21 Sound Option | Press * to exit from Device Address 21 . | |
Device Address 01-30, 00=Quit |
22 * | To enter Address 22 Note: This Address is optional — if 2s partition is used |
22 Device Type | 1* | To select Alpha Keypad Console |
22 Console Part. | To assign the Alpha Keypad Console to Partition 2 | |
22 Sound Option | Press * to exit from Device Address 22 . | |
Device Address 01-30, 00=Quit |
00* | To exit the Device Address menu. |
Quit Menu Mode ? 1=YES 0=NO | 1 | To exit Menu Mode. |
Program Mode | *99 | To exit Programming Mode |
Note: The Vista 50P supports up to 8 Partitions. You will need to repeat the programming steps for Device Addresses 23…28 according to the number of partitions. |
Switching from Keyswitch to Keybus
- Wire the device to the panel as described on the respective wiring schemeabove.
- Use the Sync with Panel feature from the Settings menu of the Uplink mobileapp.
The device will apply the new configuration automatically.
NOTE 2: When switching the wiring of the device, make sure that the device is not powered on.
NOTE 3: When synchronizing or disabling and enabling the Arming/Disarming feature from the mobile application, make sure:
- the device is powered and connected to cellular network;
- the panel is not in programming menu/mode.
After enabling the Arming/Disarming feature it may take up to 1 minute for the device to apply the new configuration.