Honeywell logouplink logoHoneywell Vista 50P
Wiring Uplink’s Communicators
and Programming the Panel

Vista 50P Wiring Uplink’s Communicators and Programming the Panel

CAUTION:

  • It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
  • Do not route any wiring over circuit board.
  • Full panel testing, and signal confirmation, must be completed by the installer.

NEW FEATURE: For 5530M Communicators, the status of the panel can be retrieved not only from the status PGM but now also from the Open/Close reports from the dialler.
IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the initial pairing procedure.
Wiring the 5530m communicators to Honeywell Vista 50P for events reporting and remote control via keybus:

Honeywell Vista 50P Wiring Uplink’s Communicators and Programming the Panel - keybus

Wiring and Programming Uplink Communicators to Honeywell Vista 50P
Wiring the 5530m communicators to Honeywell Vista 50P for events reporting and remote control via keyswitch:

Honeywell Vista 50P Wiring Uplink’s Communicators and Programming the Panel - keyswitch

Programming the Honeywell Vista 50P Alarm Panel via the Keypad

Enable Contact ID reporting:

Keypad Display Keypad Entry Action Description
Disarmed 4140,8,00 To enter programming mode.
Program mode *30, 1 To select Touch tone for dialing method.
PABX *32 To qo to “Primary subscriber Account #”.
Prim.Subs. Acct# 01, 02, 03, 04 Enter desired account number (in HEX). 1234 is just an example.
Primary Phone 123456, * Enter desired phone number (123456 is an example). Press * to save.
Enter fill field *45 To qo to “Primary format”.
Primary format 1 1 is the value for ContactlD.
Low Speed Format *81, 01, 01, * To enable Open/Close reports.
Enter fill field *99 To exit programming mode.

Enable Keyswitch Zone and Status Output:

Keypad Display Keypad Entry Action Description
Disarmed 4140,8,00 To enter programming mode.
Program mode *15, 1 To assign keyswitch to partition 1 (zone 07).
Confirmation of arming ding *40, 1 To enable Open/Close reports for Keyswitch.
Normally closed or EOLR *94, *94 Press *94 until “200” is shown in the lower right corner.
Alt Program Mode *20, 1 To configure pin 5 on 17 connector to follow Keyswitch RED behavior.
Enter fill field *99 Press *99 a couple of times until you exit programming mode.

Programming an Alpha Keypad Address

Keypad Display Keypad Entry Action Description
DISARMED 4140,8,00 To enter Programming Mode.
Program Mode #93 To go to “Menu Mode”
Zone Prog. ? 0 … 1 Press 0 until “Device Prog.” is shown. Press 1 to enter.
Device Address
01-30, 00=Quit
21* To enter Address 21
21 Device Type 1* To select Alpha Keypad Console
21 Console Part. 1* To assign the Alpha Keypad Console to Partition 1
21 Sound Option Press * to exit from Device Address 21 .
Device Address
01-30, 00=Quit
22 * To enter Address 22
Note: This Address is optional — if 2s partition is used
22 Device Type 1* To select Alpha Keypad Console
22 Console Part. To assign the Alpha Keypad Console to Partition 2
22 Sound Option Press * to exit from Device Address 22 .
Device Address
01-30, 00=Quit
00* To exit the Device Address menu.
Quit Menu Mode ? 1=YES 0=NO 1 To exit Menu Mode.
Program Mode *99 To exit Programming Mode
Note: The Vista 50P supports up to 8 Partitions.
You will need to repeat the programming steps for Device Addresses 23…28 according to the number of partitions.

Switching from Keyswitch to Keybus

  • Wire the device to the panel as described on the respective wiring schemeabove.
  • Use the Sync with Panel feature from the Settings menu of the Uplink mobileapp.

The device will apply the new configuration automatically.
NOTE 2: When switching the wiring of the device, make sure that the device is not powered on.
NOTE 3: When synchronizing or disabling and enabling the Arming/Disarming feature from the mobile application, make sure:

  •  the device is powered and connected to cellular network;
  • the panel is not in programming menu/mode.

After enabling the Arming/Disarming feature it may take up to 1 minute for the device to apply the new configuration.