Partitioned Security System with Scheduling 

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System

Programming Guide

VISTA 32FB Commercial Fire and Burglary Partitioned Security System

The purpose of this document is to provide a quick and easy way to program your entire system. A recommended programming procedure is included, followed by a list of  program fields with the corresponding program group they belong to (system-wide, partition-specific, scheduling, etc.). Two program forms are included, one contains all the programming fields, and the other contains the partition-specific fields. If you are setting up a single-partition system, the partition-specific fields become system-wide fields.
Following the program forms are system layout worksheets. We recommend that you use these sheets to plan your system before programming is performed. If you need  further information about specific programming options, see the VISTA-32FB Installation and Setup Guide.

  • Make sure that one 2-line alpha keypad is connected to the control and is set to device address “00.”

Single Partition System

  • The system default is for a single partition system. Use the VISTA-32FB SINGLE PARTITION PROGRAMMING FORM when programming for single partition  usage. Follow the steps outlined in RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.

Multiple-Partition System

  • You must enter the number of partitions you are using in data field 2*00 to set the system for multiple partitions. Use the VISTA-32FB SINGLE PARTITION and the  PARTITION-SPECIFIC PROGRAM FORMS when programming the system for multiple partitions. Follow the steps outlined in RECOMMENDED PROGRAMMING PROCEDURE of this document for proper programming procedure.

SUMMARY OF PROGRAMMING COMMANDS

  • To enter program mode, enter installer code + [8] + [0] + [0]
  • To set standard defaults, press *97
  • To change to next page of program fields, press *94
  • To return to previous set of fields, press *99
  • To erase account & phone number field entries, press [*] + field number + [*]
  • To assign zone descriptors, press #93 + follow menu prompts
  • To add custom words, press #93 + follow menu prompts
  • To enter Installer’s Message, press #93 + follow menu prompts
  • To exit program mode, press *99 OR *98: *99 allows re-access to programming mode by installer code. *98 prevents re-access to programming mode by installer code.
    Standard default (*97) values are shown in brackets [ ], otherwise default = 0.

Recommended Programming Procedure
The following is a step-by-step procedure recommended for programming your VISTA-32FB system.

  1. Set the keypads (and other peripheral devices) to the appropriate addresses.
  2. Set factory defaults by pressing ✱97.
    This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these addresses
  3. Program system-wide (global) data fields.
    Using the programming form as a guide, enter program mode and program all system wide programming fields. These options affect the entire system, regardless of  partitions. They include control options, downloader and dialer options, RF options, event logging options, etc. Refer to the COMPLETE LIST OF PROGRAMMING  FIELDS for a listing of the program fields arranged by function.
    Note that field 2✱00 (number of partitions) must be programmed before continuing.
  4. Program partition-specific fields.
    After the system-wide fields have been programmed, program all partition-specific programming fields by first pressing ✱91 to select a partition (while still in data field  program mode). Then enter the first partition-specific field number ✱09. The next partition-specific field will automatically be displayed when you are finished entering  the value for field ✱09. Partition-specific fields can have different values for each partition. To program the fields for the next partition, press ✱91, enter the desired  partition number, then enter field ✱09.
    Refer to the MECHANICS OF PROGRAMMING section in the VISTA-32FB Installation and Setup Guide for detailed instructions.
  5. Use #93 Menu Mode for device programming.
    Refer to the Device Programming in this guide to assign keypad ID numbers and default partitions for each keypad, and to selectively suppress certain keypad sounding  options. Also use this mode to assign RF receivers, relay modules, the VIP module, the ECP Long Range Radio, and the Vista Gateway Module.
  6. Use #93 Menu Mode for zone programming.
    Refer to the Zone Programming in this guide to program zone response types, assign right loop zones and wireless zones, assign zones to partitions, and to program  alarm report codes.
  7. Use #93 Menu Mode for programming outputs.
    Refer to the Output Programming in this guide to program desired output operation.
  8. Program Communication options.
    Refer to System Communication section in the VISTA-32FB Installation and Setup Guide for detailed instructions, then use #93 menu mode to program report codes.
  9. Use #93 Menu Mode for programming alpha descriptors.
    Refer to the Alpha Programming in this guide to enter zone and partition descriptors and a custom installer’s message.
  10. Use #93 Menu Mode for relay voice descriptors and custom word substitutes.
    Refer to the Relay Voice Descriptors in this guide for further instructions for programming relay descriptors to be annunciated by the VIP module, as well as the Custom  Index section for custom word substitutes.
  11. Use #80 Mode for programming schedules.
    Refer to the Scheduling Menu Prompts in the guide to program open/close schedules, temporary and holiday schedules, limitation of access schedules, and time driven  events.
  12. Define user access codes.
    Refer to User Access Codes section in the VISTA-32FB Installation and Setup Guide to program authority level, O/C reporting option, partition assignments, and  wireless key assignments for each user.
  13. Exit Programming Mode.
    Exit programming mode by pressing either ✱98 or ✱99. Additional entries of ✱99 is required if the exit is being done from fields 1✱00 and above.
    To prevent re-access to programming mode using the Installer’s code, use ✱98. The only way to re-access programming mode is by depressing both the [✱] and [#] keys  at the same time within 30 seconds of power up.
    Exiting by using ✱99 always allows reentry into programming mode using the Installer’s code. Either way of exiting will allow access via downloading. Note that if local  programming lockout is set via downloading, programming mode cannot be entered at the keypad.

Program Field Categories
In the following pages, the programming fields have been arranged by category. Use this index to cross reference the numerical ordered fields on the programming form.

Field Group
*00 System-Wide
*08 System-Wide
*09 Partition-Specific
*10 Partition-Specific
14 Partition-Specific
*12 Partition-Specific
*13 Partition-Specific
*15 System-Wide
*16 Partition-Specific
17 System-Wide
*19 System-Wide
*20 System-Wide
*22 Partition-Specific
*23 Partition-Specific
*24 System-Wide
*95 System-Wide
*26 Communications
*97 Communications
*28 System-Wide
*29 Partition-Specific
*30 Communications
*34 Communications
*32 Partition-Specific
*33 Communications
*34 Communications
*35 System-Wide
*36 System-Wide
*37 System-Wide
*38 Partition-Specific
*39 Partition-Specific
*40 Communications
*44 System-Wide
*42 Communications
*43 Communications
*44 Communications
*45 Communications
*46 Communications
*A7 Communications
*48 Communications
*49 Communications
*50 Communications
*54 Communications
*52 Communications
*53 Communications
*56 Communications
*57 Communications
*58 Communications
*59 Communications
*64 Communications
*65 Communications
*66 Communications
*67 Communications
Field Group
*68 Communications
*69 Communications
*70 Communications
71 Communications
72 Communications
73 Communications
74 Communications
75 Communications
76 Communications
79 Communications
*80 Communications
*83 Communications
“84 Partition-Specific
*85 Partition-Specific
87 Partition-Specific
*88 Partition-Specific
*89 Communications
*90 Partition-Specific
1701 #93 Menu Mode
1*02 #93 Menu Mode
1*03 #93 Menu Mode
1*04 #93 Menu Mode
1*05 #93 Menu Mode
1706 #93 Menu Mode
1*07 #93 Menu Mode
1708 #93 Menu Mode
1*09 #93 Menu Mode
117 System-Wide
1″18 Partition-Specific
119 Partition-Specific
1*20 System-Wide
1°21 System-Wide
1*22 System-Wide
1*23 System-Wide
1*24 System-Wide
1*25 System-Wide
1*26 System-Wide
1*28 System-Wide
1*29 System-Wide
1*30 System-Wide
1*31 System-Wide
1*33 Communications
1*34 Communications
1*42 Communications
1*43 Partition-Specific
1*44 System-Wide
1*45 Partition-Specific
1*47 Partition-Specific
1*48 System-Wide
1*49 System-Wide
1*52 Partition-Specific
1°53 System-Wide
Field Group
1*56 System-Wide
1*57 System-Wide
1*58 System-Wide
1*60 System-Wide
1*70 System-Wide
1*71 System-Wide
1*72 System-Wide
1*73 System-Wide
1*74 System-Wide
1*75 System-Wide
1°76 Partition-Specific
1*77 System-Wide
2*00 System-Wide
2*01 System-Wide
2*02 System-Wide
2*05 Partition-Specific
2*06 Partition-Specific
2*07 Partition-Specific
2*08 Partition-Specific
2*09 Partition-Specific
2*10 Partition-Specific
2*11 System-Wide
2*18 Partition-Specific
2*19 Partitioning
2*20 Partition-Specific
2*21 System-Wide
2*22 Partition-Specific
2*23 Partition-Specific
2*24 Partition-Specific
3*00 System-Wide
3*01 System-Wide
3*12 System-Wide
3*13 System-Wide
3*14 System-Wide
3*15 System-Wide
3*16 System-Wide
3*17 System-Wide
3*18 System-Wide
3*19 System-Wide
3*20 System-Wide
3*21 System-Wide
3*30 System-Wide
3*31 System-Wide
3*50 System-Wide
3*55 System-Wide
3*56 System-Wide
3*57 Partition-Specific
3*59 Partition-Specific
3*60 Partition-Specific
3*61 System-Wide
3*82 System-Wide
3*85 System-Wide

VISTA 32FB Programming Form
Some fields are programmed for each partition (shown as shaded fields). If Programming a Multiple Partition System, see the PARTITION-SPECIFIC section for  programming these fields. Standard default (*97) values are shown in brackets [ ],
otherwise default = 0.

*00 INSTALLER CODE Enter 4 digits, 0-9 [5140]ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon
*08 TEMPORAL SIREN PULSE [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1 = Yes; 0 = No
*09 ENTRY DELAY #1 [02] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds
Maximum “03” for UL Commercial Burglary installations.
*10 EXIT DELAY #1 [03] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds
Maximum “04” for UL Listed installations.
*11 ENTRY DELAY #2 [06]ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds (must be longer than Entry Delay #1).
Maximum “03” for UL Commercial Burglary installations.
*12 EXIT DELAY #2 [08] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds (must be longer than Exit Delay #1)
Maximum “04” for UL Commercial Burglary installations.
*13 BELL 1 TIMEOUT [04] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
01-15 times 2 minutes. Minimum 16 min. for UL Commercial Burglary and 6 min. for Commercial Fire.
*15 KEYSWITCH ASSIGNMENT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter partition in which keyswitch used, 1-2; 9=Silences bells if fire present; 0=disable
*16 BELL 1 CONFIRMATION OF ARMING DING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable. Must be “1” for UL Burglary Installations.
*17 AC LOSS KEYPAD SOUNDING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no
*19 RANDOMIZE AC LOSS REPORT [2] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=10-40 min; 2=6-12 hrs; 0=normal report (about 2 min.
after AC loss). Must be “2” for Central and Remote Station Fire alarm systems.
*20 VIP MODULE PHONE CODE ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter 01 – 09 for the first digit; enter [00] , [11] 11 for ” ” or 12 for “#” for the second digit. This field *
Must be set to “0” for Commercial Fire & UL Commercial Burglary installations.
*22 KEYPAD PANIC ENABLE [001] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable 995 996 999
*23 MULTIPLE ALARMS [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no
*24 IGNORE EXPANSION ZONE TAMPER [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=Ignore; 0=Enable tamper for RF and RPMs. Must be “0” for UL installations if using these devices.
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes, (no report sent if any other report was recently sent); 0=no.. Must be 0 for Commercial Fire & UL Commercial Burglary.
*27 TEST REPORT INTERVAL [024] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
Enter interval in hours, 001-999; 000=no report ; Max. 024 for Commercial Fire & UL.
*28 POWER UP IN PREVIOUS STATE [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no; “1” for UL.
*29 QUICK ARM [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no
*30 MAIN DIALER (TOUCHTONE OR ROTARY) [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=TouchTone; 0=rotary
*31 PABX ACCESS CODE ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-09; B-F (11-15)
*32 PRIM. SUBS. ACCT # ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter 00-09; B-F (11-15) [15 15 15 15] *33 PRIMARY PHONE NUMBER
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*34 SECONDARY PHONE NUMBER
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*35 DOWNLOAD PHONE No.
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*36 DOWNLOAD ID No.
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15] *37 DOWNLOAD COMMAND ENABLES
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Dialer System Not Remote Remote Remote UploadDownload Shutdwn Shutdwn Used Bypass Disarm Arm Program Program See field 1*53 for Callback disable option;  [1=enable]; 0=disable; For Commercial Fire & UL installations, all entries must be “0.”
*38 PREVENT ZONE XXX BYPASS [000] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
001-032; 00 if all zones can be bypassed
*39 ENABLE OPEN/CLOSE REPORT FOR [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
INSTALLER CODE 1=enable; 0=disable
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
*41 NORMALLY CLOSED or EOLR (Zones 3-8) [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=N.C.loops; 0=EOLR supervision; Must be “0” for Commercial Fire & UL.
*42 DIAL TONE PAUSE [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=5 seconds; 1=11 seconds; 2=30 seconds; Must be “0” Commercial Fire & UL.
*43 DIAL TONE DETECTION [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=wait for true dial tone; 0=pause, then dial
*44 RING DETECTION COUNT [00] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
01-14; 15=answering machine; 00=no detection. Must be “00” for Commercial Fire & UL Burglary.
*45 PRIMARY FORMAT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Low Speed; 1=Contact ID; 2=Ademco High Speed; 3=Ademco Express
*46 LOW SPEED FORMAT (Primary) [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Ademco Low Speed; 1=Sescoa/Radionics
*47 SECONDARY FORMAT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Low Speed; 1=Contact ID; 2=Ademco High Speed;
3=Ademco Express
*48 LOW SPEED FORMAT (Sec.) [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Ademco Low Speed; 1=Sescoa/Radionics
*49 CHECKSUM VERIFICATION [0] [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no Prim Sec
*50 SESCOA/RADIONICS SELECT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=Sescoa; 0=Radionics
*51 DUAL REPORTING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no If used with Spilt Reporting “1” option (1*34), alarms and alarm restores go to both primary & secondary numbers, while all other reports go to secondary only.  If used with Split Reporting “2” option, alarms and alarm restores go to both, open/close and test messages go to secondary only, while all other reports go to primary.  If used with Split Reporting “3” option, fire alarms and fire supervisory signals go to both primary and secondary, while all other reports go to secondary only.
*52 STANDARD/EXPANDED REPORT FOR PRIMARY [0 0 0 0 0 0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Alarm Rstr Bypass Trbl Opn/Cls Low Bat 0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
*53 STANDARD/EXPANDED REPORT FOR SECONDARY [0 0 0 0 0 0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Alarm Rstr Bypass Trbl Opn/Cls Low Bat 0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
*56 USE LRR ONLY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No, 1=Yes, if built-in dialer will not be used.
*57 LRR IF DIALER FAILS [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No, 1=Yes, if radio is to be used as a backup to dialer
*58 LRR ENABLE CS #1 [0 0 0 0 0 0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=disable, 1=enable for reports for primary subs id of LRR
*64 PAGER INSTALLED [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No, 1=Yes, alpha numeric pager interface is installed.
*65 PAGER PHONE # FOR ALARMS
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*66 PAGER ID # FOR ALARMS
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter up to 10 digits for the pager id #
*67 PAGER PHONE # FOR SUPERVISION
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*68 PAGER ID # FOR SUPERVISION
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter up to 10 digits for the pager id #
*69 PAGER PHONE # FOR BYPASSES
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*70 PAGER ID # FOR BYPASSES
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter up to 10 digits for the pager id #
*71 PAGER PHONE # FOR OPENS/CLOSES
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*72 PAGER ID # FOR OPENS/CLOSES
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter up to 10 digits for the pager id #
*73 PAGER PHONE # FOR SYSTEM
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*74 PAGER ID # FOR SYSTEM
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter up to 10 digits for the pager id #
*75 PAGER PHONE # FOR TEST
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*76 PAGER ID # FOR TEST

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1 2  3 4 5 6 7 8 9 10
1=enable; [0=disable] *83 FIRST TEST REPORT TIME ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 0059; 00 in all boxes=instant (Day 01=Monday)
*84 SWINGER SUPPRESSION [03] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
01-15 alarms; Must be “00” (disabled) for UL.
*85 ENABLE DIALER REPORTS [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
FOR PANICS & DURESS 995 996 999 Duress
1=enable; 0=disable
*87 ENTRY WARNING [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=16 seconds; 0=no delay. Must be “0” for UL Commercial Burg. installations.
*89 RESTORE REPORT TIMING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Instant; 1=After bell timeout if zone is restored; 2=when system is disarmed. Must be “0” for fire or UL Commercial Burg. installations.
*90 SEC. SUBS. ACCT # ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter 00-09; B-F (11-15) [15 15 15 15] 1*17 LOBBY PARTITION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter the “common lobby” partition (1-2) 1
*18 AFFECTS LOBBY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 1 if this partition affects the common lobby; enter 0 if it does not. Must be “0” for Commercial Fire & UL installations.
1*19 ARMS LOBBY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 1 if arming this partition attempts to arm lobby; enter 0 if it does not. Must be “0” for Commercial Fire & UL installations.
1*20 EXIT ERROR LOGIC [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No, 1=Bypass E/E and Interior zones faulted after exit delay. Must be “0” for Commercial Fire & UL installations.
1*21 EXIT DELAY RESET [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No; 1=Resets Exit Delay to 60 seconds after zone is closed. Must be “0” for Commercial Fire & UL installations.
FIELDS 1*22-1*25: Allow four sets of two zones each to be linked so that both must fault within a five minute period to cause an alarm.
1*22 CROSS-ZONING PAIR ONE ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
1*23 CROSS-ZONING PAIR TWO ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
1*24 CROSS-ZONING PAIR THREE ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
1*25 CROSS-ZONING PAIR FOUR ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
1*26 PANIC BUTTON OR SPEEDKEY [00, 00, 00, 00] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter speedkey macro # (01-35) to use keys A-C for macro.
Otherwise enter 00 to use as panic. For D key, enter macro # or 00 to select macro when key is pressed.
MISCELLANEOUS WIRELESS OPTIONS
Fields 1*28 – 1*31 are not applicable to Commercial Fire or UL installations.
1*28 RF TX LOW BATTERY SOUND [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=immediate; 0=when disarmed
1*29 RF TX LOW BATTERY REPORT ENABLE [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
1*30 RF RCVR CHECK-IN INTERVAL [06] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
02-15 times 2 hours; 00 disables supervision
1*31 RF TRANSMITTER CHECK-IN INTERVAL[12] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
02-15 times 2 hours; 00 disables transmitter supervision
1*33 TOUCH-TONE W/ROTARY BACKUP [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
1*34 COMM. SPLIT REPORT SELECTION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=no; 1=alarms and alarm restores primary, others secondary; 2=open/close, test secondary, others primary; 3 = fire alarms & troubles primary, all secondary. See ✴51 for  comments if using with dual reporting.

1*35 ACCESS CONTROL DIALER ENABLES
[0 0 0 0 0 0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3   ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Trace Trbl Byps Not used Syst Alm
1=enable; 0=disable
1*42 CALL WAITING DEFEAT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=Yes; 0=No.
1*43 PERM. KEYPAD BACKLIGHT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable When disabled, display lights when any key is pressed, and turns off after period of keypad inactivity.
1*44 WIRELESS KEYPAD [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
TAMPER DETECT ENABLE 1=enable; 0=disable. Must be “0” for Commercial Fire and UL installations.
1*45 EXIT DELAY SOUNDING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable. Produces quick beeping during exit delay if enabled.
1*47 CHIME ON BELL 1 [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=disable; enter partition in which RF keypad used, 1-2.
Must be “0” for Commercial Fire and UL installations.
1*49 SUPPRESS TX SUPERVISION SOUND [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=disable; 0=enable. Must be “0” for Commercial Fire and
UL installations.
1*52 SEND CANCEL IF ALARM + OFF [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=no restriction; 0=within bell timeout period only
1*53 DOWNLOAD CALLBACK [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=callback not required; 0=callback required; Must be “0” for Commercial Fire and UL installations.
1*56 50/60 Hz CLOCK SPEED [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=50 Hz; 0=60 Hz.
1*57 ENABLE 5800 RF BUTTON GLOBAL ARM [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
1*58 5800 RF BUTTON FORCE ARM [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter “1” to enable. If a zone is faulted after pressing button, console will beep once. User should press button again within 4 sec. to force bypass those zones. Enter “0” to disable.
Must be “0” for Commercial Fire and UL installations.
1*60 ZONE 5 AUDIO ALARM VERIFICATION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is not.
Must be “0” for Commercial Fire and UL installations.
1*70 EVENT LOG TYPES [1 0 0 0 1 0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Alrm Chck Byps O/C Syst Test
1=enable; 0=disable
1*71 12/24 HOUR TIME STAMP FORMAT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=12 hour; 1=24 hour
1*72 EVENT LOG PRINTER ON-LINE [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=disable; 1=enable
1*73 PRINTER BAUD RATE 1=300; 0=1200 [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Must be 1200 if using pager interface

1*74 RELAY TIMEOUT XX MINUTES [000] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter the relay timeout, 0-127 in multiples of 2 minutes, desired for #80 Menu Mode time driven event relay command numbers “04/09” and #93 Menu Mode Output Programming command “56”.
1*75 RELAY TIMEOUT YY SECONDS [000] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
Enter the relay timeout, 0-127 seconds, desired for #80
Menu
Mode time driven event relay command numbers “05/10” and #93 Menu Mode Output Programming command “57”.
1*76 ACCESS CONTROL RELAY FOR PART.[00] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Relay will be pulsed for 2 seconds whenever code + [0] is pressed. Enter 00-96; 00=none. Must be “00” for
Commercial Fire & UL..
1*77 LOG FIRST MAINTENANCE SIGNAL [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No Log; 1=Log first maintenance signal from each smoke detector

3rd Page Programming Fields (press *94) 
2*00 NUMBER OF PARTITIONS [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 1-2
2*01 DAYLIGHT SAVINGS TIME [04, 10]

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Start      End
START/END MONTH
00-12; if no daylight savings time, enter 00,00
2*02 DAYLIGHT SAVINGS TIME [1, 5] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
START/END WEEKEND #
ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Start      End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=3rd from last [1,5; 1st Sunday in April, last in Oct.] 2*05 AUTO-ARM DELAY [15] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter the time between the end of the arming window and the start of auto-arming warning period, in values of 1-14 times 4 minutes 00=instant; [15=no auto arm at all]. When this delay expires, the Auto-Arm Warning Period begins.
2*06 AUTO-ARM WARNING PERIOD [15] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
This is the time during which the user is warned to exit the premises prior to the auto-arming of the system (beeps every 15 seconds; “ALERT” displayed). Enter 01-15 minutes. 00=instant at end of arming delay .
2*07 AUTO-DISARM DELAY[15] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
This is the time between the end of the disarming window and the start of auto-disarming. Enter 01-14 times 4 minutes; 00=instant at end of window; 15=no auto-disarm.
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=disable; 1=enable
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable; If enabled, only openings and closings occurring outside the scheduled opening/closing windows will trigger dialer reports. Opening reports will also be suppressed during the closing window, in order to prevent false reports when the user arms the system and then reenters the premises to retrieve a forgotten item.
2*10 ALLOW DISARMING ONLY DURING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ARMING/DISARMING WINDOWS
0=disable; 1=enable
See system-wide field 2*11 if enabling field 2*10. This feature adds high security to the installation.
2*11 ALLOW DISARM OUTSIDE WINDOW [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
IF ALARM OCCURS
Used only if field 2*10 (partition-specific field) is set to “1”. If this field is enabled (“1”) the system can be disarmed outside the disarm window if an alarm has occurred. If “0”, disarming can only be done during the disarm window. If field 2*10 is set to “0” for a partition, this field has no effect for that partition.
2*21 ENABLE SUPERVISION PULSES FOR LRR
TRIGGER OUTPUTS
Used for supervised connection to 7920SE.
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary; S= Silent panic/duress. Enter 1 for Commercial Burglary and UL.

2*22 DISPLAY FIRE ALARMS OF [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
OTHER PARTITIONS
0=No; 1=Yes.
2*23 DISPLAY BURG & PANIC ALARMS OF [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
OTHER PARTITIONS
0=No; 1=Yes.
2*24 DISPLAY TROUBLES OF OTHER [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
PARTITIONS
0=No; 1=Yes.

4th Page Programming Fields (press *94)
3*00 DISPLAY TRBL INSTEAD OF CHECK [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
3*01 FIRE DISPLAY LOCK [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=scroll all alarms; 1=lock display of first fire alarm.
3*12 ZN TYPE 18 DELAY USE [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Check Displayed; 1=Trbl Displayed
3*13 SUPV. N.O./N.C. SELECTION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Supv. on short/trouble on open; 1=supv. on short or open
3*14 WATERFLOW SILENCE OPTION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Silence on Code + OFF; 1=Silence when waterflow restores
3*15 ALARM BELL SOUND [1,0]
0=pulsed; 1=steady Bell 1Bell 2
3*16 DELAY for ZONE TYPES 17 & 18 [00] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
(Waterflow & FIre Supv) Enter 00-15 times 2 seconds
3*17 ALTERNATE FUNCTION (TAMPER)[0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
FOR ZONE 6 0=disabled; 1=enabled
3*18 EXTENDED DELAY FOR TYPES 17&18 [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=No; 1=Yes
3*19 ENABLE J2 HEADER PRINTER PORT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=pins 5&9 function as per field 3*20; 1=pins 5&9 act as printer RXD & DTR
3*20 TRIGGER OUTPUTS SELECTION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0= LORRA full connection & Remote Console Sounder; 1=LORRA limited conn. & Keyswitch LEDs; 2=LORRA fire only conn. & 5140LED
3*21 MAX # OF DIALER ATTEMPTS [8] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1-8 (3, 4 or 5 for NFPA72 compliant systems when a secondary phone number is programmed (field *34)
3*30 DIALER SELECTION [1,0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enabled; 0=disabled                 Main Backup
3*31 BACKUP DIALER TOUCHTONE/ROTARY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=TouchTone; 0=Rotary
3*50 ZONE TYPE RESTORE ENABLES
FOR ZONE TYPES 16-18 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 316 17 18
1 = enabled; [0 = disabled] 3*55 RESET ON SECOND OFF FOR BELL 1 [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1 = enabled; 0 = disabled
3*56 RESET ON SECOND OFF FOR BELL 2 [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1 = enabled; 0 = disabled
3*57 BELL 2 & AUX. RELAY CONFIRM  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 Bell 2 AUX.
ARM DING
1=enable; [0=disable] . Must be 1 for UL Commercial Burglary.
3*59 ENABLE BELL 2 & AUX. RELAY ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 Bell 2 AUX
CHIME ANNUNCIATION
1=enable; [0=disable] 3*60 BELL 2 & AUX. RELAY TIMEOUT ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 2 minutes; 00=no timeout [00,00] Bell 2 AUX
Must be minimum of 16 minutes for UL Burglary installations.
3*61 AUX. RELAY FUNCTION [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=Trouble/supervisory; 1=Alarm, silenced by code + OFF
2=Smoke Detector Reset; 3=Battery Save; 4=Alarm, silenced by code + [#] + 67
3*82 ENABLE BURG. FEATURES ON PART. 1 [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable; “0” disables AWAY, STAY, MAX, TEST, INSTANT & CHIME functions
3*85 ENABLE FIRE & SYSTEM ZONE BYPASS [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=not enabled; 1=only installer can bypass]; 2=only installer & master user can bypass. Applies to fire zone types 9, 16, 17 & 18 and system
zones 970-977. Applies to Partition 1 only.

SUMMARY OF PROGRAMMING COMMANDS

  • To enter program mode, enter installer code + [8] + [0] + [0]
  • To set standard defaults, press *97
  • To change to next page of program fields, press *94
  • To return to previous set of fields, press *99
  • To erase account & phone number field entries, press [*] + field number + [*]
  • To assign zone descriptors, press #93 + follow menu prompts
  • To add custom words, press #93 + follow menu prompts
  • To enter Installer’s Message, press #93 + follow menu prompts
  • To exit program mode, press *99 OR *98: *99 allows re-access to programming mode by installer code. *98 prevents re-access to programming mode by installer code.

Partition-Specific Fields

(Duplicate this page for each partition in the installation.)
To program these fields,

  1. Press *91 to select a partition.
  2. Enter a partition-specific field number (ex. *09).
  3. Make the required entry.
  4. Repeat steps 1-3 for each partition in the system.

PARTITION #____ PROGRAM FIELDS

1st Page Fields
*09 ENTRY DELAY #1 [02] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds. Maximum 03 for UL Listed installations.
*10 EXIT DELAY #1 [03] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds. Maximum 04 for UL Listed installations.
*11 ENTRY DELAY #2 [06] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds. Maximum 03 for UL Commercial Burglary installations.
*12 EXIT DELAY #2 [08] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
00-15 times 15 seconds. Maximum 04 for UL Commercial
Burglary installations.
*13 BELL 1 TIMEOUT [04] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
01-15 times 2 minutes. Minimum 16 minutes for UL.
Commercial Burglary and 6 minutes for Commercial Fire installations.
*16 CONFIRMATION OF ARMING DING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable. Must be “1” for UL Commercial
Burglary installations.
*22 KEYPAD PANIC ENABLES [001] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 995 996 999
1=enable; 0=disable
*23 MULTIPLE ALARMS [1]ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no. Enter 1 for Commercial Fire & UL Commercial
Burglary installations.
*29 QUICK ARM [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=yes; 0=no
*32 PRIM. SUBS. ACCT # ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter 00-09; B-F (11-15) [15 15 15 15] *38 PREVENT ZONE XXX BYPASS [000] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 1
001-032; 000 if all zones can be bypassed
*39 ENABLE OPEN/CLOSE REPORT [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
FOR INSTALLER CODE
1=enable; 0=disable
*84 SWINGER SUPPRESSION [03] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
01-15 alarms; Must be “00” (disabled) for Commercial Fire &
UL installations..
*85 ENABLE DIALER REPORTS[0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
FOR PANICS & DURESS ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3 995 996 999 Duress
1=enable; 0=disable
*87 ENTRY WARNING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=16 seconds; 0=no delay. Must be “0” for UL Commercial
Burglary installations.
*90 SEC. SUBS. ACCT # ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter 00-09; B-F (11-15) [15 15 15 15] 1*18 AFFECTS LOBBY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 1 if this partition affects the common lobby; enter 0 if it does not.
1*19 ARMS LOBBY [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
Enter 1 if arming this partition attempts to arm lobby; enter 0 if it does not

2nd Page Fields
1*26 PANIC BUTTON OR SPEEDKEY
[00, 00, 00, 00] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 A B C D
Enter speedkey macro # (01-35) to use keys A-C for macro.
Otherwise enter 00 to use as panic. For D key, enter macro
# or 00 to select macro when key is pressed.
1*43 PERM. KEYPAD BACKLIGHT [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable When disabled, display lights when any key is pressed, and turns off after period of keypad inactivity.
1*45 EXIT DELAY SOUNDING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable Produces quick beeping during exit delay if enabled.
1*47 CHIME ON BELL 1 [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable
1*52 SEND CANCEL IF ALARM + OFF [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=no restriction; 0=within Bell Timeout period only
1*76 ACCESS CONTROL RELAY FOR PART.[00] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Relay will be pulsed for 2 seconds whenever code + [0] is pressed. Enter 00-96; 00=none. Must be “00” for Commercial Fire & UL.

3rd Page Fields
2*05 AUTO-ARM DELAY [15] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
Enter the time between the end of the arming window and the start of auto-arming warning period, in values of 1-14 times 4 minutes 00=instant; [15=no auto arm at all]. When this delay expires, the Auto-Arm Warning Period begins.
2*06 AUTO-ARM WARNING PERIOD [15] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
This is the time during which the user is warned to exit the premises prior to the auto-arming of the system (beeps every 15 seconds; “ALERT” displayed). Enter 01-15 minutes. 00=instant at end of arming delay .
2*07 AUTO-DISARM DELAY [15] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2
This is the time between the end of the disarming window and the start of auto-disarming. Enter 01-14 times 4 minutes; 00=instant at end of window; 15=no auto-disarm.
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=disable; 1=enable.
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=enable; 0=disable; If enabled, only openings and closings occurring outside the scheduled opening/closing windows will trigger dialer reports. Opening reports will also be suppressed during the closing window, in order to prevent false reports when the user arms the system and then reenters the premises to retrieve a forgotten item.
2*10 ALLOW DISARMING ONLY DURING [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
ARMING/DISARMING WINDOWS
See system-wide field 2*11 if enabling field 2*10. This feature adds high security to the installetion.
0=disable; 1=enable
2*18 ENABLE GOTO FOR THIS PARTITION [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
1=Allow log-on from other partitions; 0=disable
2*20 ENABLE J2 TRIGGERS by PARTITION [1] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
0=disable for displayed partition; 1=enable for displayed partition
2*22 DISPLAY FIRE ALARMS OF [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
OTHER PARTITIONS 0=No; 1=Yes
2*23 DISPLAY BURG/PANIC ALARMS OF [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
OTHER PARTITIONS
10=No; 1=Yes
2*24 DISPLAY TROUBLES OF OTHER [0] ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 3
PARTITIONS
0=No; 1=Yes

4th Page Fields
3*57 BELL 2 & AUX. RELAY CONFIRM  ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 Bell 2 Relay
ARM. DING 1=enable; [0=disable] Must be “1” for UL.
3*59 ENABLE BELL 2 & AUX. RELAY ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 Bell 2 Relay
CHIME ANNUNCIATION 1=enable; [0=disable] 3*60 BELL 2 & AUX. RELAY TIMEOUT ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - icon 2 Bell 2 Relay
00-15 times 2 minutes; 00=no timeout [00,00] Minimum 16 min. for UL Burglary installations.

SUMMARY OF PROGRAMMING COMMANDS

  • To enter program mode, enter installer code + [8] + [0] + [0]
  • To set standard defaults, press *97
  • To change to next page of program fields, press *94
  • To return to previous set of fields, press *99
  • To erase account & phone number field entries, press [*] + field number + [*]
  • To assign zone descriptors, press #93 + follow menu prompts
  • To add custom words, press #93 + follow menu prompts
  • To enter Installer’s Message, press #93 + follow menu prompts
  • To exit program mode, press *99 OR *98: *99 allows reaccess to programming mode by installer code. *98 prevents re-access to programming
    mode by installer code.

Programming With #93 Menu Mode

NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should be programmed via Device programming.
After programming all system related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.
UL For UL installations, verify that wireless and audio alarm verification features are disabled.

#93 MENU MODE KEY COMMANDS
The following is a list of commands used while in the menu mode.

#93 Enters Menu mode
[✱] Serves as ENTER key. Press to have keypad accept entry.
[#] Backs up to previous screen.
0 Press to answer NO
1 Press to answer YES
 001-009 All data entries are either 2-digit or 3-digit entries.
000 Exits menu mode, back into field programming mode, when entered at the first question for each category.

Menu selections are as follows:
ZONE PROG?
1 = YES 0 = NO
For programming the following:

  • Zone Number
  • Zone Response Type
  • Partition Number for Zone
  • Dialer report code for zone
  • Bell/aux. relay assignment for zone
  • Input Device Type for zone (whether RF, polling loop, etc.)
  • Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.

EXPERT MODE?
1 = YES 0 = NO
Same as Zone Programming except:

  • Done with a minimum number of keystrokes.
  • Can program wireless keys using pre-defined templates.

REPORT CODE PROG?
1 = YES 0 = NO
For programming the following:

  • Alarm report codes for zones
  • Restore & supervisory codes
  • All other system report codes

ALPHA PROG?
1 = YES 0 = NO
For entering alpha descriptors for the following:

  • Zone Descriptors
  • Installer’s Message
  • Custom Words
  • Partition Descriptors
  • Relay Descriptors

DEVICE PROG?
1 = YES 0 = NO
For defining the following device characteristics for addressable devices, including keypads, RF receivers (5881), output relay modules  (4204/4204CF), 4285/4286 VIP Module, ECP long  range radio (7820), and vista gateway module:

  • Device Address
  • Device Type
  • Keypad Options (incl. partition assignment)
  • RF House ID
  • LRR Options (incl. programming radio)

OUTPUT PGM?
1 = YES 0 = NO
For defining output device functions.

RLY VOICE DESCR?
1 = YES 0 = NO
For entering voice descriptors for relays to be used with the 4285/4286 VIP Module.

CUSTOM INDEX ?
1 = YES 0 = NO
For creating custom word substitutes for VIP Module annunciation.

ACCESS POINT PGM
1 = YES 0 = NO
For defining the parameters for each of the VistaKey access point including which group(s) have access through an access point (door). See the VistaKey-SK Installation and Setup Guide for the detailed programming instructions.

ACCESS GRP PGM
1 = YES 0 = NO
For defining the capabilities (privileges) for each group of users. See the VistaKey-SK
Installation and Setup Guide for the detailed programming instructions.

EVENT/ACTION PGM
1 = YES 0 = NO
For defining events and time windows for an access group. See the VistaKey-SK Installation and Setup Guide for the detailed programming instructions.

Zone Programming

ZONE PROG?
1=YES 0=NO
Press 1 to enter ZONE PROGRAMMING mode. The following screens will appear. Press [✳] to display the next screen. Press # to display a previous screen.

SET TO CONFIRM?
0 = NO 1 = YES 0
This prompt will appear once upon entering Zone Programming.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been entered later.

ENTER ZONE NO.
000 = QUIT 010
Zone 010 entered ↑
Enter the 3-digit zone number to be programmed, as follows:
Protection Zones = 001–032
Relay Zones = 601–616.
ECP Device Supervisory Zones = 800–831.
System Supervisory Zones = 988, 990, 992 (duress), 997 Keypad Panic Zones = 995, 996, 999.
Press [✱] to continue.

010 ZT P RC In L
00 1 10 00 1
This display will appear, showing a summary of the zone’s current programming. ZT = Zone
Type, P = Partition, RC = Report Code, B = Bell/Aux. Relay assignment for zone, In = the input type of device, and L = the device’s loop number to which the sensor is connected.
Some devices can support more than one zone by means of individual loops (for example, 5801, 5804, 5816, 5817, etc.). If the zone is not programmed, the display will appear as shown here. If checking a zone’s programming, and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.
Press [✱] to continue.

↓ Zone Number
010 ZONE TYPE
PERIMETER 03
Zone Type 03 entry shown † These are special zone types used with  5800 Series Wireless Pushbutton Units which will result in arming the system in the STAY or AWAY mode, or disarming of the system, depending on the selection made.

Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. Refer to the Zone Type Definitions section in the VISTA-32FB Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary). Available zone types are listed below.

00 = Assign for Unused Zones
01 = Entry/Exit #1, Burglary
02 = Entry/Exit #2, Burglary
03 = Perimeter, Burglary
04 = Interior Follower, Burglary
05 = Trouble Day/Alarm Night
06 = 24 Hr. Silent Alarm
07 = 24 Hr. Audible Alarm
08 = 24 Hr. Auxiliary
09 = Fire Without Verification
10 = Interior Delay, Burglary
16 = Fire With Verification
17 = Fire Waterflow
18 = Fire Supervisory
19 = 24-Hour Trouble
20 = Arm–STAY†
21 = Arm AWAY†
22 = Disarm†
23 = No Alarm Response
(e.g., Relay activation)
27 = Access Point
28 = MLB Supervision
(if VGM installed)
29 = Momentary on Exit*

* Used with VistaKey door access modules.
Press [✱] to continue.

010 PARTITION
1
Enter the partition number (1–2) you are assigning this zone to.
Press [✱] to continue.

010 REPORT CODE
1st 03 2nd 12 3C
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of “3C”, enter 03 for “3” and 12 for “C.” (Refer to System Communication section for more information about report codes and report code formats.)

010 INPUT TYPE
RF Xmitter 3
Note that input types 4 & 5 are valid for certain 5800 Series transmitters only (e.g., 5801, 5802, 5802CP & 5803).
Input type 10 is applicable only if PassPoint ACS is installed with the Vista Gateway Module.
If response type 28 was selected, the input type MUST be 00.

Enter the input device type as follows:
00 = not used
01 = hardwired
03 = supervised RF transmitter (RF type)
04 = unsupervised RF transmitter (UR type)
05 = RF button-type transmitter (BR type)
06 = serial number polling loop device (SL type)
07 = DIP switch-type polling loop device
08 = right loop of DIP switch type device.
09 = keypad input (code + #73)
10 = PassPoint ACS input
11 = VistaKey Door Status Monitor (DM)*
12 = VistaKey Request to Exit (RE)*
13 = VistaKey General Purpose (GP*)
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which allow hardwired devices to be monitored by the polling loop.
If programming hardwired, or DIP switch polling loop devices, the summary display appears after completing this entry.
* Only used with VistaKey door access modules.
Press [✱] to continue.

010 ACCESS POINT
(00-31) 01
If response type 27, 29 or input types 11 – 13 was selected, this prompt will be displayed.
Enter the access point to be controlled by the input type (00-31 for type 27; 01-15 for type 29; 01-15 for types 11 – 13).
Note: This prompt also appears when the input type selected is 06. For standard SL, the selected address must be 00.
Note: If you are using the VistaKey module, the access point must match the address that was set in the module.

010 ENTRY OR EXIT 0
If response type 27 selected, this prompt will be displayed. Enter whether the access point is an entry or exit point.
0 = entry;
1 = exit

010 BELL/RLY SEL 0
Each zone can be assigned to activate either one or both bell outputs and/or the system’s auxiliary relay. Enter one of the following assignments:
0=none; 1=Bell 1; 2=Bell 2; 3=Bells 1 and 2; 4=Aux Relay; 5=Bell 1 and Aux Relay; 6=Bell 2 and Aux Relay; 7=Bells 1 and 2 and Aux Relay.
Press [✱] to continue.

010 V-PLEX RELAY?
1 = YES 0 = NO
If input type 6 was selected, this prompt is displayed. Enter 1 if using a 4101SN relay module for this zone. Otherwise enter 0.

010 CONS ECP ADDR
(00-30) 01
If input type 09 was selected, this prompt is displayed. Enter the ECP address of the keypad that is being used for entry/exit for this access point (00-30).

010 ACS ZONE #
(00-31) 01
If input type 10 was selected, this prompt is displayed. Enter the PassPoint ACS zone ID that this VISTA zone maps to (00-31).

010 INPUT S/N: L
AXXX-XXXX 1
Serial Number Entry and Loop Number Entry.
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad. Then press the [✱] key, the cursor will move to the “L” position. You can edit the loop number, if necessary. When the loop number is acceptable, press [✱].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several input loops).
Press [✱] to accept.

010 INPUT S/N: L
A022-4064 1
The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number displayed.
Enter the loop number (refer to 5800 Series Transmitters Loop Designations section).
To Delete an Existing Serial Number, enter “0“ in the loop number field. The serial number will change to “0”s.
If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display.
Press [✱] to accept.

010 INPUT S/N: L
A022-4064 1
The system will then check for a duplicate serial/loop number combination.
If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display the serial number along with a “?” for the loop number, allowing you to re-enter the correct loop number.
If the serial/loop number combination is not a duplicate in the system, a display showing the serial number and loop number entry will appear.
Press [✱] to continue.

5800 Series Transmitters Loop Designations

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - 5800 Series Transmitters Loop Designations

Note: For information on any transmitter not shown above, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.

The 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, 5827BD, and 5850 transmitters are not intended for use in UL installations.

XMIT TO CONFIRM
PRESS ✱TO SKIP
Confirmation Option: This prompt will only appear if you answered “Yes” at the first prompt. The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you may press the [✱] key on the keypad to save the serial and loop number combination without confirming.

Entd A022-4063 1
Rcvd A022-4064
If the serial number transmitted does not match the serial number entered, a display similar to the one at the left will appear. If the loop number does not match, it will also be displayed.
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary display does not appear), press the [#] key twice and then enter or transmit the correct serial number.

010 ZT P RC In L
01 2 00 RF 1s
If the serial number transmitted does match the serial number entered, the system will beep 3 times and a summary display will appear, showing that zone’s programming. Note that an “s” indicates that a transmitter’s serial number has been enrolled. Press [✱] to accept the zone information.

ENTER ZONE NO.
000 = QUIT  011
The system will now return you to the “ENTER ZONE No.” prompt for the next zone.
When all zones have been programmed, enter “000” to quit.

After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in the appropriate column on the worksheets provided in the Programming Guide; then enter the other information (zone number, zone type, etc.) relevant to that device.

When you have finished programming all zones, test each using the system’s Test Mode. Do not use the Transmitter ID Sniffer Mode for this. The system will check only for transmission of one zone on a particular transmitter, NOT the zones assigned to each additional loop, and also will not verify polling loop type zones.

Expert Mode Zone Programming
Expert Mode allows you to program zones using the minimum number of screens and keystrokes.
Enter the Programming Mode with [Installer Code] + 8 0 0
Before programming your zones, do the following:

  1. Program field 2✱00: Number of Partitions.
  2. Enable your RF Receiver in Device Programming menu mode.
    To program your zones, press ✱93 to display the “ZONE PROG?” prompt. Enter “0” (N0) to each prompt until the “EXPERT MODE?” prompt appears.

EXPERT MODE?
1 = YES 0 = NO
Press 1 to enter Expert mode.

SET TO CONFIRM?
0 = NO 1 = YES 0
This prompt will appear once upon entering Expert Mode.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been entered later.

Zn ZT P RC In L
001 03 1 10 HW –
A summary display will appear, showing zone 1’s current programming or default values.

Zn ZT P RC In L
010 03 1 10 RF 1s
Enter the desired 3-digit zone number and press [✱].
Note: If you want to exit the expert mode, enter “000” + [✱].
If an “s” appears after the loop number, it indicates that the transmitter’s serial number has been enrolled.
Use the [D] key to enter and duplicate wireless keys (see “Entering Wireless Keys” later)

Zn ZT P RC In L
010 03 1 10 RF –
Enter all zone information except for Loop number, or press “C” to copy the zone information on this screen from last saved zone (including Loop).
ZT = Zone Type
P = Partition
RC = Report Code
In = Input Device Type
L = Loop number to which the sensor is connected.
NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the input type. Verify this information is correct for this zone. On this screen,

  • Use the [A] key to move to the right
  • Use the [B] key to move to left and to back up to “ZT” field

Press [✱] to accept the existing or newly-entered zone information

ZN B M V A C E AD
010 2 1 1 0 1 1 01
Enter the remainder of the zone’s information, or press the [C] key to copy the zone attributes on this screen from the last saved zone.
B = Bell/Relay Assignment
M = Maintenance? (only used if “In” = 3 or 6)
V = V-plex Relay? (only used if “In” = 6)
AC = Access Point (only used if ZT = 27, 29 or In = 6, 11, 12, 13)
E = Entry or Exit? (only used if ZT = 27)
AD = Address (only used if “In” = 9 or 10)
If “In” = 9, enter the Device Address
If “In” = 10, enter the PassPoint Zone Number)
NOTE: Pressing the [C] copies the zone attributes from the last saved zone. Verify the attributes for this zone are correct.
NOTE: When response type 29 is selected, the access point (AC) must be from 01-15.
When the input type selected is 06, the access point selected must be 00.

On this screen,

  • Use the [A] key to move to the right
  • Use the [B] key to move to left and to back up to “B” field

Press [✱] to accept existing information

010 INPUT S/N: L
A XXX-XXXX –
If you entered RF, BR, UR or SL for the Input Type, this screen displays. Otherwise the summary screen for the next zone displays.
Enter the 7-digit serial number, using one of the following methods:
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad. Then press the [✱] key, the cursor will move to the “L” position. You can edit the loop number, if necessary. When the loop number is acceptable, press [✱].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several input loops).
Remember, you can use the [A] key to move to the right or the [B] key to move to the left and to back up to the previous screen.
You can also use the [#] key to back up without saving.

010 INPUT S/N: L
A022-4064 1
Press [✱] to accept the serial number and advance to the “L” position (if method “a” or “c” was used), then enter the loop number.
If necessary, press the [#] key to back up without saving, and re-enter or edit the serial number before pressing [✱] to save
The system checks for a duplicate. If a duplicate exists, a long error beep and display the serial number along with a “?” for the loop number, allowing you to re-enter the correct loop number..

010 INPUT S/N: L
A000-0000 1
To Delete a Serial Number
To delete an existing serial number, enter “0“ in the loop number field. The serial number will change to “0”s.
If “0” was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display.

XMIT TO CONFIRM
PRESS ✱TO SKIP
The prompt to confirm appears. This prompt will only appears if you answered “Yes” at the “SET TO CONFIRM?” prompt.
The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you may press the [✱] key on the keypad to save the serial and loop number combination without confirming.

Entd A022-4063 1
Rcvd A022-4064
If the serial number transmitted does not match the serial number entered, a display similar to the one at the left will appear. If the loop number does not match, it will also be displayed.
If so, activate the loop input or button on the transmitter once again. If a match is not obtained, press the [#] key twice and then enter or transmit the correct serial number.
Activate the button on the wireless key again after re-entering the serial number.

Zn ZT P RC In L
011 00 1 10 00 1
If the serial number transmitted matches the serial number entered, the system will beep 3 times and advance to the summary display for the next zone’s programming.

After all the serial numbers have been entered, enter 000 for the zone number to quit. After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in the appropriate column on the worksheets provided in the Programming Guide; then enter the other information (zone number, zone type, etc.) relevant to that device.
Entering Wireless Keys
If the D key was previously pressed to enter defaults for 5804 and/or 5804BD wireless keys, the following screens will appear:

FROM TEMPLATE
1–6 1
Enter Template number (1–6).
1–3 = 5804 templates; 4–6 = 5804BD templates. See the defaults provided for each template in the chart that follows these procedures.
Select from templates. Press [✱] to display template (template 1 shown selected).
Note: If necessary, press [#] to back up and re-enter template number.
Press [#] if you want to return to zone attributes screen.

L 01 02 03 04
2T 23 22 21 23 1
When [✱] is pressed, the selected template will be displayed.
Top line of display represents loop numbers, bottom line represents zone type.
Press [✱] to accept template.

PARTITION
1
Enter Partition number for wireless key.
Press [✱] to continue.

ENTER ZONE NO
000 = QUIT 024 ↑
Example of zone number suggested by the system. This indicates that zones 24, 25, 26, and 27 are available.

The system will search for the highest available, consecutive 4-zone group, (the four zones required for the 5804 and 5804BD), and display the lowest zone number of the group.
If you want to start at a different zone, enter the zone desired and press [✱].
If that zone number is displayed, the system has the required number of consecutive zones available, beginning with the zone you entered. If not, the system will again display a suggested zone that can be used.
If the required number of consecutive zones is not available at all, the system will display “00” Press [✱] to accept.

024 INPUT S/N L
AXXX-XXXX 1
To enter the serial number:
Press and release a button on the wireless key.
OR
Manually enter the 7-digit serial number printed on the device’s label, using the Alpha keypad.
Press [✱] to accept serial number. The system will check for duplicate.
If a duplicate exists, a long error beep will sound and the serial number reverts back to all
“X”s allowing you to re-enter the serial number.
Use the [A] key to move forward within the screen, and the [B] key to back up

XMIT TO CONFIRM
PRESS ✱TO SKIP
If YES was entered at the SET TO CONFIRM prompt previously (see first prompt following entry into the Expert Programming Mode), the display on the left will appear.
To confirm, activate the button on the wireless key that corresponds to this zone.

Entd A022-4063
Rcvd A022-4064
If the serial number transmitted does not match the serial number entered, a display similar to the one at the left will appear.
If so, activate the loop input or button on the transmitter once again. If a match is not obtained, press the [#] key and then enter the correct serial number.
Activate the button on the wireless key again after re-entering the serial number.

ENTER ZONE NO
000 = QUIT 028
If the serial number transmitted matches the serial number entered, the system will beep 3 times and revert to the summary display on the “Start Zone No.” prompt and will show the lowest numbered zone of the next available 4-zone group (consecutive zones) that is available for programming.
When all zones have been programmed, enter “000” to quit.

After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in the appropriate column on the worksheets provided in the Programming Guide; then enter the other information (zone number, zone type, etc.) relevant to that device.

Wireless Key Default Templates

5804 5804BD
Template 1 Loop Function Zone Type Template 4 Loop Function Zone Type
1 No Response 23 1 No Response 23
2 Disarming 22 2 No Response 23
3 Arm AWAY 21 3 Arm AWAY 21
4 No Response 23 4 Disarming 22
Template 2 Loop Function Zone Type Template 5 Loop Function Zone Type
1 No Response 23 1 No Response 23
2 Disarming 22 2 Arm STAY 20
3 Arm AWAY 21 3 Arm AWAY 21
4 Arm STAY 20 4 Disarming 22
Template 3 Loop Function Zone Type Template 6 Loop Function Zone Type
1 24-Hour Panic 7 1 24-Hour Panic 7
2 Disarming 22 2 Arm STAY 20
3 Arm AWAY 21 3 Arm AWAY 21
4 Arm STAY 20 4 Disarming 22

Report Code Programming
All report codes are entered using # 93 Menu Mode Programming, either through Report Code Programming or through the Zone Programming while entering other zone information. In the VISTA-32FB, reports are divided into six categories. These categories represent the main menu options found in Report Code Programming. Reports and the categories in which they are found are as follows:

ALARM CODES RESTR, SUPV. CODES
(for groups of 16 zones)
SYSTEM GROUP #1
Zone Alarm Reports Alarm Restore
Trouble
Trouble Restore
Bypass
Bypass Restore
Closing (Arm Away)
Opening (Disarm)
System Low Battery
Low Battery Restore
AC Loss
AC Restore
Periodic Test
Power
Cancel
Program Tamper
SYSTEM GROUP #2 SYSTEM GROUP #3 SYSTEM GROUP #4
Arm STAY
Time Set, Log Reset
Log 50%, 90% Full
Event Log Overflow
Exit Error by Zone
Exit Error by User
Recent Close
Early Open
Early Close
Late Open
Late Close
Failed to Open
Failed to Close
Auto-Arm Failed
Schedule Change
Fire Walk-Test Start
Fire Walk-Test End
Off-Normal

The programming sequence that follows assumes that all reports for the system will be entered at one time. In actuality, it is possible to skip from one main menu option to another by pressing 0 (NO) at each main menu option. Main menu options are highlighted in bold text. To enter report codes, do the following:
Enter Program Mode [Installer Code] + [8 0 0]. Then press #93. Enter 0 (NO) at each main menu option until the REPORT CODE PROG prompt is displayed.

REPORT CODE PROG
1 = YES 0 = NO 0
Press 1 (YES) to enter Report Code Programming.

Zone Alarm Reports
ALARM, ID DIGIT?
1 = YES 0 = NO 0
Press 1 (YES) to enter Alarm Report Codes for zones. Press 0 (NO) to skip to the next main menu option.

ENTER ZONE NO.
000 = QUIT 001
Enter the zone number for which you are entering the report code.
Press [✱] to continue.

001 REPORT CODE
1st 00 2nd 00 000
Enter the first digit of the Alarm report code (double-digit entry) and press [✱]. Enter the second digit of the Alarm Report Code.
Press [✱] to continue.

ENTER ZONE NO.
000 = QUIT 001
Enter the zone number for which the Report Code is being entered. When all zone Alarm Codes have been programmed, enter 000 to Quit.
Press [✱] to continue.

QUIT REPORT MENU
1 = YES 0 = NO 0
If you have completely finished entering report codes, press 1 (YES) to quit Report Code
Programming. If you wish to enter other system report codes, enter 0 (NO).
Press [✱] to continue.

Restore/Supervisory Codes
RESTR, SUPV. CODE
1 = YES 0 = NO 0
Press 1 (YES) to enter Restore and Supervisory Codes for zones.

ENTER ZN FOR GRP
000 = QUIT 001
Enter one zone for each group of 16 zones (001-016, 017-032).

ALARM RESTORE
GRP 001-016 00
Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry).
The second digit (for two-digit reporting formats) is automatically the ID (second) digit of the
Alarm Report Code for each zone (if programmed).
Press [✱] to continue.

TROUBLE
GRP 001-016 00
Enter the first digit of the Trouble Report Code for this group of zones (double-digit entry). The second digit (for two-digit reporting formats) is automatically the ID (second) digit of the Alarm
Report Code for each zone (if programmed).
Press [✱] to continue.

TROUBLE RESTORE
GRP 001-016 00
Enter the first digit of the Trouble Restore Code (single-digit entry) and press [✱]. The second digit (for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report
Code for each zone (if programmed).
Press [✱] to continue.

BYPASS
GRP 001-016 00
Enter the first digit of the Bypass Report Code (double-digit entry) and press [✱]. The second digit (for two-digit reporting formats) is automatically the ID (second) digit of the Alarm Report Code for each zone (if programmed)..
Press [✱] to continue.

BYPASS RESTORE
GRP 001-016 00
Enter the first digit of the Bypass Restore Report Code (double-digit entry) and press [✱]. The second digit (for two-digit reporting formats) is automatically the ID (second) digit of the Alarm
Report Code for each zone (if programmed).
Press [✱] to continue.

ENTER ZN FOR GRP
000 = QUIT 017
Enter one zone for each group of 16 zones. When finished entering Restore and Supervisory
Codes for all zone groups, enter 000.
Press [✱] to continue.

QUIT REPORT MENU
1 = YES 0 = NO 0
When all of the report codes have been entered, press 1 (YES) to quit Report Code
Programming. To enter other system report codes, enter 0 (NO).
Press [✱] to continue.

System Group #1 Codes
SYSTEM GROUP #1?
1 = YES 0 = NO 0
To enter System Group #1 codes, press 1 (YES).

CLOSE
1st 00 2nd 00
Enter the first digit of the Closing (Arm-AWAY) report. Press [✱]. Enter the second digit of the report. If the user number is desired as the second digit, enter 01 (not necessary for Contact ID or High-Speed formats).
Press [✱] to continue.

Enter the rest of the codes in the same manner. Other report codes in System Group #1 are:

  • Opening (Disarm). Enable this if you desire Callback Requested reports (the panel answers a phone call from the downloader).
  • System Low Battery.
  • Low Battery Restore.
  • AC Loss.
  • AC Restore.
  • Periodic Test.
  • Power.
  • Cancel.
  • Program Tamper.

Once the report codes have been entered, the system will prompt:

QUIT REPORT MENU
1 = YES 0 = NO 0
If all of the report codes have been entered, press 1 (YES) to quit Report Code Programming. To enter other system report codes, enter 0 (NO).
Press [✱] to continue.

System Group #2 Codes
SYSTEM GROUP #2 ?
1 = YES 0 = NO 0
To enter System Group #2 codes, press 1 (YES).

STAY
1st 00 2nd 00
Enter the first digit of the Arm-STAY report. Press [✱]. Enter the second digit of the report. If the user number is desired as the second digit, enter 01 (not necessary for Contact ID or HighSpeed formats).
Press [✱] to continue.

Enter the rest of the codes in the same manner. Other codes in System Group #2 are:

  • Time Set, Log Reset.
  • Log 50%, 90% Full.
  • Event Log Overflow.
  • Exit Error by Zone.
  • Exit Error by User.
  • Recent Close.

Once the report codes have been entered, the system will prompt:

QUIT REPORT MENU
1 = YES 0 = NO 0
If all of the report codes have been entered, press 1 (YES) to quit Report Code Programming. To enter other system report codes, enter 0 (NO).
Press [✱] to continue.

System Group #3 Codes
SYSTEM GROUP #3 ?
1 = YES 0 = NO 0
To enter System Group #3 codes, press 1 (YES).

EARLY OPEN
1st 00 2nd 00
Enter the first digit of the Early Opening Report Code. Press [✱]. Enter the second digit of the report code. If the user number is desired as the second digit, enter 01 (not necessary for Contact ID or High-Speed formats).
Press [✱] to continue.

Enter the rest of the codes in the same manner. Other codes in System Group #3 are:

  • Early Close.
  • Late Open.
  • Late Close.
  • Failed to Open.
  • Failed to Close.
  • Auto-Arm Failed.
  • Schedule Change.

Once the report codes have been entered, the system will prompt:

QUIT REPORT MENU
1 = YES 0 = NO 0
If all of the report codes have been entered, press 1 (YES) to quit Report Code Programming. To enter other system report codes, enter 0 (NO)
Press [✱] to continue.

System Group #4 Codes
SYSTEM GROUP #4 ?
1 = YES 0 = NO 0
To enter System Group #4 codes, press 1 (YES).

WALK TEST START
1st 00 2nd 00
Enter the first digit of the Fire Test Start Report Code. Press [✱]. Enter the second digit of the report code.
Press [✱] to continue.

Enter the rest of the codes in the same manner. Other codes in System Group #4 are:

  • Walk-Test End.
  • Off-Normal.

Once the report codes have been entered, the system will prompt:

QUIT REPORT MENU
1 = YES 0 = NO 0
If all of the report codes have been entered, press 1 (YES) to quit Report Code Programming.

QUIT MENU MODE?
1 = YES 0 = NO 0
Enter 1 to exit back to normal Programming mode. Enter 0 to stay in Menu Mode.

Alpha Descriptors Programming

General Information

  • A user-friendly English language description/location for all protection zones, Outputs, keypad panics, polling loop short, and RF receiver supervision troubles can be programmed.
  • Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an s or ‘s added to it.
    NOTE: Due to the use of 3-digit zone numbers, the first word of the descriptor is limited to 6 characters if you want it to fit on the top line of the display.
  • In addition, up to 60 installer-defined words can be added to those already in memory. Thus, when an alarm or trouble occurs in a zone, an appropriate description for the location of that zone will be displayed at the keypad.
  • A custom Installer’s Message can be programmed for each partition, which will be displayed when the system is ready (e.g., THE PETERSONS).
    1. To program alpha descriptors, enter Programming mode, then press #93 to display ZONE PROG?
    2. Press 0 (NO) twice to display ALPHA PROG?.
    3. Press 1 to enter Alpha Programming.
  • There are 6 sub-menu selections that will be displayed one at a time.
  • Press 1 to select the mode desired.
  • Press 0 to display the next mode available. The alpha menu selections are:
    ZONE DESCRIP? for entering zone descriptors.
    DEFAULT SCREEN? for creating custom message; displayed when system ready.
    CUSTOM WORD? for creating custom words for use in descriptors.
    PART DESCRIP? for creating 4-character partition names.
    EXIT EDIT MODE?  Pres  Press 1 to exit back to # 93 Menu Mode.

    4. Refer to the sections that follow for procedures for adding alpha descriptors.

Zone Descriptors

  1. Select ZONE DESCRIPTOR mode.
    The keypad keys perform the following functions:
    [3] Scrolls both alphabet and actual words in ascending alphabetical order.
    [1] Scrolls both alphabet and actual words in descending alphabetical order.
    [2] Adds or removes an s or ‘s to a vocabulary word.
    [6] Switches between alphabet and actual word list; used to accept entries.
    [8] Saves the zone description in the system’s memory.
    [#] [#] plus zone number displays the description for that zone.
  2. Enter the zone number to which you want to assign a descriptor.
    For example, key [✱]001 to begin entering the description for zone 1 (key [✱]002 for Zone 2, [✱]003 for Zone 3, etc.).
    The following will be displayed: ✱ZN 001 A.
    Note that the first letter of the alphabet appears after the zone number, and that the zone number is automatically included with the  description.
  3. Enter the descriptor for that zone.
    Use one of the following two methods:
    (Assume, for example, that the desired description for zone 1 is BACK DOOR.)
    a) Press [#] followed by the 3-digit number of the first word from the fixed dictionary shown later in this section (e.g., [013] for BACK).
    Press 6 in order to accept the word and proceed, or press 8 to store the complete descriptor and exit; or
    b) Select the first letter of the desired description (note that A is already displayed). Use the 3 key to advance through the alphabet and the 1 key to go backward.
    Press 3 key repeatedly until B appears (press 1 to go backwards if the letter was passed), then press 6 to display the first available word beginning with B.
    Press 3 repeatedly to advance through the available words until the word BACK is displayed.
    To add an s or ‘s, if needed, press 2. The first depression adds an s, the second depression adds an ‘s, the
    third depression displays no character (to erase the character), the fourth depression adds an s, etc.
  4. Accept the word.
    To accept the word, press 6, which switches back to the alphabet list for the next word, or press 8 to store the comdescriptor and then exit.
  5. Select the next word.
    For selection of the next word (DOOR), repeat step 3a (word #057) or 3b, but selecting the word DOOR.
    To accept the word, press 6, which again switches back to alphabet list.
  6. Store the descriptor.
    When all desired words have been entered, press 8 to store the description in memory.
    To review the zone descriptors, press [#] + [zone number] (e.g., #001).
    To edit zone descriptors, press [✱] + [zone number] (e.g., ✱001).
  7. Exit Zone Description Mode: enter 000.
    Default Screen (Custom Message Display)
    Normally, when the system is in the disarmed state, the following display is present on the keypad.

Default Screen (Custom Message Display)
Normally, when the system is in the disarmed state, the following display is present on the keypad.

✱✱✱✱DISARMED✱✱✱✱
READY TO ARM

Part or all of the above message can be modified to create a custom Installer Message for each partition. For example, ****DISARMED**** on the first line or READY TO ARM on the second line could be replaced by the installation company name or phone number for service. Note that there are only 16 character spaces on each of the two lines. To create a custom display message, proceed as follows:

  1. Select Default Screen Mode.
    The keypad will ask for the partition number for this message.
    Enter the partition number. Press [✱] to accept entry.
    The following will appear:
    ✱✱✱✱DISARMED✱✱✱✱
    READY TO ARM
    A cursor will be present at the extreme left of the first line (over the first star). Press 6 to move the cursor to the right and
    4 to move the cursor to the left. Press 7 to insert spaces or erase existing characters.
  2. Create the message.
    For example, to replace READY TO ARM with the message SERVICE 424-0177, proceed as follows:
    Press 6 to move the cursor to the right, and continue until the cursor is positioned over the first location on the second line.
    Press 3 to advance through the alphabet to the first desired character (in this case, S). Press 1 to go backward, when necessary. When the desired character is reached, press 6.
    The cursor will then move to the next position, ready for entry of the next character (in this example, E). When the cursor reaches a position over an existing character, press 3 or 1 to advance or back up from that character in the alphabet.
    Proceed in this manner until all characters in the message have been entered.
  3. Save the message.
    Store the new display message in memory by pressing 8.
  4. The system will ask for a new partition number.
    Enter 0 to quit or 1-2 for a new partition number.

Custom Words
Up to 60 installer-defined words can be added to the built-in vocabulary. Each of the 60 words can actually consist of several words, but bear in mind that a maximum of 10 characters can be used for each word string.

  1. Select CUSTOM WORD Mode. The keys perform the following functions:
    [3] Advances through alphabet in ascending order.
    [1] Advances through alphabet in descending order.
    [6] Selects desired letter; moves the cursor one space to the right.
    [4] Moves the cursor one space to the left.
    [7] Inserts a space at the cursor location, erasing any character at that location.
    [8] Saves the new word in the system’s memory.
    [✱] Returns to Description Entry Mode.
  2. Enter the custom word number (01-60) to be created.
    For example, when creating the first word (or word string), enter 01; when creating the second word, enter 02, and so on.
    A cursor will now appear at the beginning of the second line.
  3. Type the word using one of the following methods:
    a) Press [#] + [the 2-digit entry for the first letter to be displayed] (e.g., [65] for A).
    When the desired character appears, press 6 to select it. The cursor will then move to the right, in position for the next character. Press [#] + [the 2-digit entry for the next letter of the word]. or
    b) Press 3 to advance through the list of symbols, numbers, and letters.
    Press 1 to move back through the list.
    When the desired character has been reached, press 6 to select it. The cursor will then move to the right, in position for the next character.
  4. Repeat step 3 to create the desired custom word (or words).
    Press 4 to move the cursor to the left, if necessary.
    Press 7 to enter a blank (or to erase an existing character).
    Each word or word string cannot exceed 10 characters.
  5. Save the word by pressing 8.
    The CUSTOM WORD? Prompt will be redisplayed. The custom word (or string of words) will be automatically added to the built-in vocabulary at the end of the group of words beginning with the same letter.
    Custom words are retrieved as word numbers 255 to 314 for words 1 to 60, respectively, when using method 3a to enter alpha descriptors.
    When using method 3b to enter alpha descriptors, each word will be found at the end of the group of words that begin with the same letter as it does.
  6. Repeat steps 2 through 6 to create up to 60 custom words (or word strings).
  7. Exit Custom Word Mode by entering 00 at the CUSTOM WORD prompt.

Partition Descriptors

  1. Select Part. DESCRIPT. Mode. The system will ask for the partition number desired. Enter the number as a single-key entry 1-2.
  2. Follow the same procedure as for custom words, except that partition descriptors are limited to 4 characters (e.g., WHSE for warehouse).

Alpha Descriptor Vocabulary

(For Entering Alpha Descriptors. To select a word, press [#] followed by the word’s 3-digit number.)
NOTE: This vocabulary is not to be used for relay voice descriptors. See the RELAY VOICE DESCRIPTORS section when programming relay voice descriptors.

000 (Word Space)
• 001 AIR
• 002 ALARM
003 ALCOVE
004 ALLEY
005 AMBUSH
006 ANTENNA
• 007 AREA
• 008 APARTMENT
009 ART
• 010 ATTIC
011 AUDIO
012 AUX
013 AUXILIARY
• 014 BABY
• 015 BACK
• 016 BAR
017 BARN
• 018 BASEMENT
• 019 BATHROOM
• 020 BED
• 021 BEDROOM
022 BELL
023 BELL 1
024 BELL 2
• 025 BLOWER
• 026 BOILER
027 BOTTOM
028 BOX
029 BREAK
• 030 BUILDING
031 BURNER
032 CABINET
• 033 CALL
034 CAMERA
035 CAR
036 CASE
037 CASH
038 CCTV
039 CEILING
040 CELLAR
• 041 CENTRAL
042 CIRCUIT
043 CLIP
• 044 CLOSED
045 COIN
046 COLD
047 COATROOM
048 COLLECTION
049 COMBUSTION
• 050 COMPUTER
051 CONTACT
• 052 DAUGHTERS
053 DELAYED
• 054 DEN
055 DESK
• 056 DETECTOR
057 DIALER 1
058 DIALER 2
• 059 DINING
060 DISCRIMINAT061 DISPLAY
062 DOCK
• 063 DOOR
064 DORMER
• 065 DOWN
• 066 DOWNSTAIRS
067 DRAWER
• 068 DRIVEWAY
069 DRUG
• 070 DUCT
• 071 EARTH
072 EAST
073 ELECTRIC
074 EMERGENCY
075 ENTRY
• 076 EQUIPMENT
077 EXECUTIVE
• 078 EXIT
079 EXTERIOR
• 080 FACTORY
081 FAILURE
082 FAMILY
• 083 FATHERS
• 084 FENCE
085 FILE
• 086 FIRE
• 087 FLOOR
088 FLOW
089 FOIL
• 090 FOYER
091 FREEZER
• 092 FRONT
093 FUR
094 FURNACE
095 GALLERY
• 096 GARAGE
• 097 GAS
098 GATE
• 099 GLASS
100 GROUND
101 GUEST
102 GUN
• 103 HALL
• 104 HEAT
105 HIGH
106 HOLDUP
107 HOUSE
108 INFRARED
• 109 INSIDE
110 INTERIOR
111 INTRUSION
112 JEWELRY
• 113 KITCHEN
• 114 LAUNDRY
• 115 LEFT
116 LEVEL
• 117 LIBRARY
• 118 LIGHT
119 LINE
120 LIQUOR
• 121 LIVING
• 122 LOADING
123 LOCK
124 LOOP
125 LORRA
126 LOW
• 127 LOWER
• 128 MACHINE
129 MAGNETIC
130 MAIDS
131 MAIN
• 132 MASTER
133 MAT
• 134 MEDICAL
135 MEDICINE
136 MICROWAVE
137 MONEY
138 MONITOR
• 139 MOTHERS
• 140 MOTION
141 MOTOR
142 MUD
• 143 NORTH
144 NURSERY
• 145 OFFICE
146 OIL
• 147 OPEN
148 OPENING
• 149 OUTSIDE
150 OVERFLOW
151 OVERHEAD
152 PAINTING
• 153 PANIC
154 PASSIVE
• 155 PATIO
156 PERIMETER
• 157 PHONE
158 PHOTO
159 POINT
160 POLICE
161 POOL
• 162 POWER
163 QUAD
164 RADIO
• 165 REAR
166 RECREATION
167 REFRIG
168 REFRIGERATION
169 RELAY 1
170 RF
• 171 RIGHT
• 172 ROOM
173 ROOF
174 SAFE
175 SCREEN
176 SENSOR
• 177 SERVICE
• 178 SHED
179 SHOCK
• 180 SHOP
181 SHORT
182 SHOW
• 183 SIDE
184 SKYLIGHT
185 SLIDING
• 186 SMOKE
187 SONIC
• 188 SONS
• 189 SOUTH
190 SPRINKLER
191 STAMP
• 192 STATION
193 STEREO
194 STORE
• 195 STORAGE
196 STORY
197 STRESS
198 STRIKE
199 SUMP
200 SUPERVISED
201 SUPERVISION
202 SWIMMING
203 SWITCH
204 TAMPER
205 TAPE
206 TELCO
207 TELEPHONE
208 TELLER
• 209 TEMPERATURE
210 THERMOSTAT
• 211 TOOL
212 TRANSMITTER
213 TRAP
214 TRIGGERS
215 ULTRA
• 216 UP
• 217 UPPER
• 218 UPSTAIRS
• 219 UTILITY
220 VALVE
221 VAULT
222 VIBRATION
223 VOLTAGE
224 WALL
225 WAREHOUSE
226 WASH
• 227 WEST
• 228 WINDOW
229 WINE
• 230 WING
231 WORK
232 XMITTER
233 YARD
234 ZN-1
• 235 ZONE
• 236 0
• 237 1
• 238 1ST
• 239 2
• 240 2ND
• 241 3
• 242 3RD
• 243 4
• 244 4TH
• 245 5
• 246 5TH
• 247 6
• 248 6TH
• 249 7
• 250 7TH
• 251 8
• 252 8TH
• 253 9
• 254 9TH
255 Custom Word 1
to
314 Custom Word 60

CHARACTER (ASCII) CHART
(For Adding Custom Words)

32 (space) 42 * 52 4 62 > 72 H 82 R
33 ! 43 + 53 5 63 ? 73 I 83 S
34 ! 44 , 54 6 64 @ 74 J 84 T
35 45 55 7 65 A 75 K 85 U
36 # 46 . 56 8 66 B 76 L 86 V
37 % 47 / 57 9 67 C 77 M 87 W
38 & 48 0 58 : 68 D 78 N 88 X
39 49 1 59 ; 69 E 79 O 89 Y
40 ( 50 2 60 < 70 F 80 P 90 Z
41 ) 51 3 61 = 71 G 81 Q 91

*Notes:
This factory-provided vocabulary of words is subject to change.
Bulleted words in bold face type are those that are also available for use by the 4285/4286 VIP Module. If using a VIP Module, and words other than these are selected for alpha descriptors, the Voice Module will not provide annunciation of those words.

Device Programming
This menu is used to program keypads, receivers and relay modules.
From Data Field Programming Mode, press #93 to display “ZONE PROG?”. Press 0 repeatedly to display “DEVICE PROG?”.

DEVICE PROG?
1=YES 0=NO
Press 1 to enter Device Programming.
DEVICE ADDRESS
01-31, 00=QUIT
The device address identifies the device to the control. Enter the 2-digit device address
number to match the device’s physical address setting (01-30).
Press [✱] to accept entry.
Note: Device Address 04 must be used for the 4285/4286 Voice Module, if one is installed. If not, it can be used for another device type.

Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options, and these settings cannot be changed.

DEVICE TYPE Select the type of addressable device as follows:
0 = device not used
1 = alpha keypad (6139/6139R)
3 = RF receiver (5881)
4 = output relay module (4204/4204CF)
5 = Voice (VIP) Module (4285/4286)
6 = Long Range Radio
8 = Fire Display
9 = Vista Gateway Module (VGM)
Press [✱] to accept entry.

Alpha Keypad

CONSOLE PART. If device type 1 (alpha keypad) is selected, this prompt will appear. Enter the addressable device’s default partition number (01 to maximum number of partitions programmed for system in field 2*00). This is the primary partition for which the device is intended to be used. Enter 9 to make this keypad a “master” keypad for the system. Press [✱] to accept entry.
SOUND OPTION If device type 1 (alpha keypad) is entered, this prompt will appear. Keypads can be
individually programmed to suppress arm/disarm beeps, entry/exit beeps and chime mode beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises. Enter a number 00-03 for the keypad sounding suppression options desired for the keypad as follows:
00 = no suppression.
01 = suppress arm/disarm & entry/exit beeps.
02 = suppress chime mode beeps only.
03 = suppress arm/disarm, entry/exit and chime mode beeps.
Press [✱] to accept entry.
KEYPAD GLBL? If device type 1 (alpha keypad) is entered, this prompt will appear. Each keypad can give users with access to multiple partitions the ability to arm and disarm those partitions from it. To enable this keypad for global arming/disarming, enter 1. To prevent the ability to use this keypad for global arming/disarming, enter 0.
Press [✱] to accept entry.

RF Expander

RF EXPANDER
HOUSE ID XX
If device type 3 (RF Receiver) is selected, this prompt will appear. Enter the 2-digit House
ID (00-31). This is required if using a wireless keypad (5827/5827BD).
Press [✱] to accept entry.

Output Relay Module

SUPERVISED CF? If device type 4 (relay module) is selected, this prompt will appear. Enter 1 if the unit is a 4204CF. If not, enter 0. If 1 is entered, only Relay 1 (Output A) and relay 3 (Output B) on each module are able to be programmed for functions. This module is usually used to add two additional supervised bell outputs to the system.
Press [✱] to accept entry.

Long Range Radio
If device type 6 is chosen, the 6139 Keypad will function similar to the 7720PLRR Programming Tool. See Figure 25-2 for the functions of the keys on the 6139.

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - Long Range Radio

SHIFT function indicated by turning on READY LED.
Figure 25-2 6139 Key Functions for Programming the ECP Radio

Each key has two possible functions: a normal function and a SHIFT function. To perform a normal key function, simply press the desired key. To perform a SHIFT key function, press SHIFT key, then press desired function key.

Normal and SHIFT key Functions:

Key Normal Key Function SHIFT Key Function
BS/ESC [BS]: Press to delete entry
Also, can reset EEPROM defaults *
[ESC]: Press to quit Program Mode.
44 [L]: Scroll down programming [T]: Scroll up programming
N/Y [N]: Press for “NO” answer. [Y]: Press SHIFT-Y for “YES” answer
SHIF T Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is pressed. Press again for each SHIFT function desired.
1/A [1]: For entering the number 1 [A]: Used for entering C.S. ID number
2/B [2]: For entering the number 2 [B]: Used for entering C.S. ID number
3/C [3]: For entering the number 3 [C]: Used for entering C.S. ID number
4/D [4]: For entering the number 4 [D]: Used for entering C.S. ID number
5/E [5]: For entering the number 5 [E]: Used for entering C.S. ID number
6/F [6]: For entering the number 6 [F]: Used for C.S. ID & FAST Mode
7/S [7]: For entering the number 7 [S]: Press to display diagnostic status
8/T [8]: For entering the number 8 [T]: Press to send TEST messages
9/X [9]: For entering the number 9 [X]: Press to reset the 7820
*/SPACE [*]: Not used with 7820 [SPACE]: Not used with 7820
0 [0]: For entering the number 0 No SHIFT function
VENTER [VENTER]: Press to accept entries No SHIFT function

* Active only when the “REVIEW?” prompt is displayed.

The 6139 Keypad will display the following prompts, which are sent by the Long Range Radio transmitter to the control.
Note: These prompts are for the 7820 Radio only. If you are using a different radio, refer to the radio’s instructions for the correct prompts.

DEVICE ADDRESS Enter the device address of the radio. The default address is 3.
ID #
(1234)
Enter the 4-digit customer account number, 0001-9999. This ID number will appear in the
messages generated by the radio. Messages generated by the panel and transmitted by
the radio will contain the ID number programmed into the panel. The radio and the panel
should have the same ID number, if possible.

If a different 4-digit customer account number is used in the radio than is programmed into the alarm control, the radio will transmit radio-specific messages (power-on reset, AC fail, etc.) using the radio customer number, and alarm messages using the control panel’s customer number. If these numbers are different, you will be billed for two AlarmNet radio accounts.

ODD [Y/N] (N) Enter Y for odd system flag; N for even system flag.
Alarmnet (Y/N)
(Y)
Enter Y if an AlarmNet installation. Enter N for private system users (skip to Question 7).
CS ID
(11)
Enter the primary central station’s system ID number, 1-7F (will not be displayed for private
system users).
BAT PRESENT [Y/N] (N) Enter Y if optional battery will be used. Must be Y for UL installations (a battery must be
installed).
USE RADIO # [Y/N] (N) If Y is selected, the Radio ID number will replace the panel Subscriber ID in panel generated messages with the Radio ID number.
If N is selected, the radio will send panel-generated messages with the panel Subscriber ID number.
2 ND CS ID
(12)
This must be programmed with a value, even if it is the same as the primary central
station. The alarm panel has the option to send a selected message to the second central
station.
REVIEW (Y/N)
(N)
Enter Y to review the programming options and to ensure that the correct responses have
been made. Parameters can be changed during review.
Enter N to end programming session.

Fire Display

RST FIRE PTN?. If device type 8 (Fire Display) is selected, this prompt will appear.
Press 0 to disable FSA’s Silence/Reset button (default).
Press 1 to enable FSA’s Silence/Reset button to Silence the fire alarm system when pressed once (Silence only).
Press 2 to enable FSA’s Silence/Reset button to Silence and then Reset the fire alarm system when pressed twice.

VIP Module and VISTA Gateway Module

MODULE PART. If device type 5 (VIP Module) or type 9 (VGM) is selected, this prompt will appear. Enter
the partition number 1-2 in which the module is located.
Press [✱] to accept entry.
Press 00 + [✱] to exit Menu Mode.
Press ✱99 to exit Program Mode.

Output Programming

The system supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each output must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a designated STOP event. The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries.
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the various summary displays of programmed data during programming.

ACTION (A)
The “ACTION” of the device is how the device will respond when it is activated by the “START” programming. You may want the device to activate momentarily, to pulse on and off continuously, or to remain activated until some other event occurs to stop it. There are five different choices of actions:

  • ACTIVATE for 2 SECONDS and then reset.
  • ACTIVATE and REMAIN ACTIVATED until stopped by some other event.
  • PULSE ON and OFF until stopped by some other event (do not use with an FSA device).
  • NO RESPONSE when the device is not used.
  • TOGGLE on and off alternately with each activation of event.

START (STT)

The “START” programming determines when and under what conditions the device will be activated. The following START options are available:

  1. EVENT (EV) is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone list) in order to activate the device. These conditions apply only when a zone list is used. The different choices for “EVENT” are listed below and in “Output Devices  Programming” later in this section.
    ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activate a particular device. Note that there are a total of 15 zone lists that can be programmed; when the selected EVENT (alarm, fault or trouble) occurs in any zone in the selected “Start” ZONE LIST (01-15), activation of the selected device will START.
  2. ZONE # A specific zone going into alarm, fault, trouble, or restore (Event programming) can be used to start the Output action. Enter the 3-digit zone number (000-032).
  3. ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device have the same response type, and there are no other zones of this type which are not to activate this device, then “ZONE TYPE” may be used instead of using a “ZONE LIST” and “EVENT” to activate the device. If a System Operation, such as “DISARMING” or “ANY FIRE ALARM” is to activate the device, the appropriate choice would also be entered under the “ZONE TYPE” option.
    The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the “EVENT/ZONE LIST” combination.
    If a specific “ZONE TYPE” is chosen, any zone of that response type going into alarm, trouble, or fault will cause the device to activate as selected in “ACTION.” If the same “ZONE TYPE” is also chosen for the STOP programming, any zone of that type that restores will de-activate the device. If a “SYSTEM OPERATION” is chosen, that operation will cause the device to activate as selected in “ACTION.” The different choices for “ZONE TYPE” and “SYSTEM OPERATION” are listed in “Output Devices Programming” later in this section, and on the Programming Form.
  4. PARTITION No. (P). The device’s “Start” ZONE TYPE/SYSTEM OPERATION may be limited to an occurrence on one partition (1-2), or any partition (0).

STOP (STP):

The “STOP” programming determines when and under what conditions the device will be de-activated.
The following options are available:

  1. RESTORE ZONE LIST (ZL). If a “ZONE LIST” is used as the “Stop” event, the device will de-activate when all the zones in that list restore from a previous fault, trouble, or alarm condition. This will occur regardless of what is programmed to “START” the device; therefore, a “RESTORE ZONE LIST” would normally only be used when a “ZONE LIST” is used to start the device.
  2. ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a “RESTORE ZONE LIST,” a specific zone (response) type or system operation action can be selected to de-activate the device. If a specific “ZONE TYPE” is chosen, any zone of that response type that restores from a previous alarm, trouble, or fault condition will cause the device to de-activate. If a “SYSTEM OPERATION” is chosen, that operation will cause the device to de-activate. The different choices for “ZONE TYPE” and “SYSTEM OPERATION” are listed in “Output Devices Programming” later in this section, and in the Programming Form. The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the “[RESTORE]ZONE LIST” option.
  3. PARTITION No. (P). The device’s “Stop” Zone Type/System Operation may be limited to an occurrence on one partition (1-2), or on any partition (0).

Output Devices Programming

From Data Field Programming Mode, press #93 to display the “ZONE PROG?” prompt. Press 0 (NO) to each menu option until the “OUTPUT PGM?” prompt appears. Press 1 (YES).
While in this mode, press [✱] to advance to next screen. Press [#] to backup to the previous screen.

ENTER OUTPUT #
(00=QUIT) 01
Enter the Output identification number 01-96. This is a reference number only, used for
identification purposes. The actual module address and relay number on the module are
programmed in the last two prompts.
Press [✱] to continue.
02 A EV ZL ZT P
STT 0 0 00 00 0
Press [✱] to continue.
02 A ZL ZT P
STOP 0 00 00 0
The keypad will display a summary STOP screen.
Press [✱] to continue.
02 OUTPUT ACTION
NO RESPONSE 0
The Output Action is the way in which the Output will respond when activated by the “start” event. Enter the desired action for this Output as follows:
0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off; 4= toggle on/off alternately
02 START EVENT
NOT USED
0
A Output may be activated either by an Event used in conjunction with a Zone List, and/or by a Zone Type/System Operation. If using an Event/Zone List combination, enter the event code as follows: 0=not used; 1=alarm; 2=fault; 3=trouble; 4=restore
If not using a Zone List to activate the Output, enter 0.
Press [✱] to continue.
02 START: ZN LIST
00
A Zone List is a set of zones that can be used to initiate the start or stop Output action. If a zone list is being used to start this Output action, enter the Zone List number 1-15. If a zone list is not being used, enter 0.
Press [✱] to continue.
02 START: ZONE #
000
A specific zone can be used instead of or in addition to an Event/Zone List or Zone
Type/System Operation combination to start the Output action. Enter the 3-digit zone number.
Press [✱] to continue.
02 START: ZN TYPE
NO RESPONSE 00
A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or a specific zone to start the Output action. If a Zone Type/System Operation is being used, enter the 2-digit code as listed below.
Press [✱] to continue.

Choices for Start/Stop Zone Types and System Operation:

00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior W/Delay
16 = Fire With Verification
17 = Fire Waterflow ****
18 = Fire Supervisory
19 = 24-Hr. Trouble
20 = Arming-STAY
21 = Arming-AWAY
22 = Disarming ([Code] + Off)
23 = No Alarm Response
27 = Access Point (allows more than one relay to be controlled by activation if access point request)
28 = MLB Supervision
29 = Momentary on Exit ***
30 = On Second Code + Off
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout **
38 = Chime
39 = Fire Alarm
40 = Bypassing
41 = AC Power Fail
42 = System Battery Low
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
47 = Console Failure
51 = RF Receiver Failure
52 = Kissoff
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field 1*74) *
57 = YY Seconds (enter YY in field 1*75)*
58 = Duress
60 = Audio Alarm Verification (must be selected for both START and STOP operation)
61 = Code + [#] + 67 Key Entry
62 = Bell 2 Timeout
63 = Aux. Relay Timeout

*Stop condition only, **Or at Disarming, whichever occurs earlier, ***Used with VistaKey door access modules, **** If zone type 17 (waterflow) is selected, an event of fault or alarm should be used as the output start option.

If using options 56 or 57 (usually as the STOP Zone Type), data fields 1✱74 and 1✱75 for the respective relay timeouts for minutes and seconds must be programmed.

02 START: ACS PT
(00-31) 00
If the start zone type selected was 27 (access point), this prompt will be displayed. Enter the
access point (00-31) which will start the Output action.
Press [✱] to continue.
02 START: PARTN
ANY PARTITION 0
If the starting event will be limited to occurring on a specific partition, enter the partition number
(1-2) in which the start event will occur. Enter 0 for any partition.
Press [✱] to continue.
02 STOP: ZN LIST
00
If a zone list is being used to stop this Output action, enter the zone list number 1-15. The restore of a zone on the Zone List will stop the Output. If a zone list is not being used, enter 0.
Press [✱] to continue.
02 STOP: ZN TYPE
NO RESPONSE 00
If a Zone Type/System Operation is being used to stop the Output action, enter the 2-digit code as listed in the Choices for Start/Stop System Operation chart.
Press [✱] to continue.
02 STOP: ACS PT
(00-31) 00
If the stop zone type selected was 27 (access point), this prompt will be displayed. Enter the access point (00-31) which will stop the Output action.
Press [✱] to continue.
02 STOP: PARTN
ANY PARTITION 0
This is the partition to which the stop condition will be limited. Enter 0 for any partition. Enter 1-2 for specific partition number.
Press [✱] to continue.
02 OUTPUT GROUP
00
Outputs may be grouped for common activation by time-driven events (commands 06-10).
Enter 00 (no group) or 01-15 for a specific group number.
Press [✱] to continue.
02 RESTRICTION
1=YES 0=NO 0
The system may have some devices, which are not intended to be under end user control, such as Outputs activating fire doors or machinery. Enter 1 if the end user will be restricted from accessing this Output group.
Press [✱] to continue.
02 OUTPUT TYPE
V-PLEX 0
Enter 0 for V-Plex (polling loop) devices. Enter 1 for (ECP) relay modules (4204/4204CF).
Enter 3 for (FSA) Fire System Annunciator.
Press [✱] to continue.
02 V-PLEX ZONE #
000
For polling loop trigger outputs (4101SN), enter the protection zone number (001-032) linked to each output, if used. Be sure to enroll the module’s serial number (see Zone Programming prompt earlier in this section).
Press [✱] to continue.
02 ECP ADDRESS
00
If 1 was selected for relay modules (4204/4204CF), enter the actual relay module’s address (01-15) as set by its DIP switches. Up to 8 modules can be installed in a system.
Press [✱] to continue.
02 MODULE RELAY#
0
For 4204 Relay Outputs, enter the specific relay number on that module (1-4). For 4204CF outputs, enter only module relay number 1 (Output A) or relay number 3 (Output B).
These are the only two programmable relays on the 4204CF Module.
Press [✱] to continue.
The keypad will display the Start and Stop summary screens again.
Press [✱] to continue.
02 ECP ADDRESS
00
If 3 was selected for FSA, enter the actual FSA’s address (08-23) as set by its DIP switches.
Up to 4 modules can be installed in a system.
Press [✱] to continue.
01 LED #
00
Enter the LED number on the FSA module (01-08 for FSA-8; 01-24 for FSA-24).
Press [✱] to continue.
The keypad will display the Start and Stop summary screens again.
Press [✱] to continue.

When all output devices have been programmed, enter 00 at the “ENTER OUTPUT #.” prompt.
If defining a zone list, continue to the next section. If not, enter 00 + [✱] at the next two prompts. You will then be asked “Quit Menu Mode?” Enter 1 for “Yes,” 0 for “No.” Then enter ✱99 to exit programming completely.
If supervision of the 4204CF Relay Output is desired, enter a response type for that output’s corresponding supervisory zone.
This is equal to 600 + [Relay ID No.]. For example, if you are programming Relay ID No. 1, the relay’s supervisory zone would be 601. Program this zone for response type 05 (Day/Night) in Zone Programming.

Zone List Programming

After all Outputs have been programmed, upon entering 00 at the “ENTER OUTPUT #.” prompt, you will be asked to enter a zone list. If a zone list number was used to start or stop a Output, you must define the zones belonging to that list as follows:

ENTER Zn LIST ?
00=QUIT 00
Enter the zone list number 01-15. Enter 00 to quit.
01 ADD ZONE #
000=QUIT 000
Using 3-digit entries, enter each zone to be included in this zone list. Press [∗] after each zone number is entered.
When all zones have been entered, enter 000.
Press [✱] to continue.
01 Del Zn LIST ?
1=YES 0=NO 0
Enter 0 to save the zone list entered. Enter 1 to delete that zone list.
01 DEL ZONES ?
1=YES 0=NO 0
Enter 1 to delete one or more zones in that zone list. Enter 0 if no changes are necessary. If 1 is entered, the following screen will appear, otherwise the “Enter Zone LIST” prompt will reappear.
01 Zn to DELETE ?
000=QUIT 000
Enter each zone number to be deleted from the zone list, pressing [✱] after each number.
VIEW Zn LIST ?
00=QUIT 00
This will appear if 00 is pressed at the “Enter Zone LIST” prompt. Enter the zone list number that you wish to view.
Press [✱] to continue.
01 ASSIGNED ZONE
000=QUIT 000
Press [✱] to scroll through all zones in that list. Enter 000 +[✱] to quit.
Press [1] to exit Menu Mode.
Press ✱99 to exit Program Mode.

Relay Voice Descriptors
If using the 4285/4286 VIP Module, voice descriptors can be programmed for outputs 1-16 (even though the system has 96 outputs, only 1-16 can have a Relay Voice Descriptor programmed). These descriptors will be announced by the voice module when accessing the Outputs via the # 70 Relay Access Mode via telephone.
Each voice descriptor can consist of up to three words selected from the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list (later in this section).
The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary list in the Alpha Programming part of this guide.

To enter relay voice descriptors, do the following:

  1. From Data Field Programming Mode, press #93 to display the “ZONE PROG?” prompt.
  2. Press 0 (NO) to each menu option until the “RLY VOICE DESCR?” prompt is displayed. Follow the instructions below.
    While in this mode, press [✱] to advance to next screen. Press [#] to back up to previous screen.
RLY VOICE DESCR?
1=YES 0=NO 0
Press 1 to program voice descriptors for relays.
ENTER RELAY NO.
00=QUIT 01
Enter the 2-digit relay number (01-16) for the Output desired, or enter 00 to quit Relay Voice Descriptor Programming Mode.
Press [✱]
01 ENTER DESC d1 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3digit index number for the first word of the relay descriptor phrase.
Press [✱] to accept entry.
01 ENTER DESC d2 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3digit index number for the second word of the relay descriptor phrase. If second word is not desired, press 000.
Press [✱] to accept entry.
01 ENTER DESC d3 From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3digit index number for the third word of the relay descriptor phrase. If third word is not desired, press 000.
Press [✱] to accept entry. The “ENTER RELAY NO#.” prompt will appear. Enter the next relay number to be programmed. When all output devices have been programmed, enter 00 to quit.
Enter ✱99 to exit Program Mode.

Relay Voice Descriptors and Custom Word Substitutes Vocabulary

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - Substitutes Vocabulary

Custom Word Substitutes for VIP Module Annunciation
A substitute word can be programmed for each of the 60 custom words used in your alpha zone descriptions. The VIP Module will announce this substitute word in place of the custom word that is displayed on the alpha keypad. For example, an alarm display of “John’s Bedroom” could be announced as “Son’s Bedroom,” since there is no annunciation for the custom word “John.” Note that if a substitute word is not assigned, the VIP Module will not annunciate the zone descriptor at all, but will only annunciate the zone number.
To enter custom word substitutes, do the following:

  1. From Data Field Programming Mode, press #93 to display the “ZONE PROG?” prompt.
  2. Press 0 (NO) to each menu option until the “CUSTOM INDEX ?” prompt is displayed.
CUSTOM INDEX ?
1=YES 0=NO 0
Enter 1 at this prompt.
CUSTOM WORD NO.
00=QUIT
Enter the custom word number (01-60) for which a voice substitute is desired. Enter 00 to quit this Programming Mode.
Press [✱] to accept entry.
01 ENTER INDEX # Enter the 3-digit substitute word index number from the Relay Voice Descriptors and Custom
Word Substitutes Vocabulary list found in the Relay Voice Descriptors part of this section.
Press [✱] to accept entry.
The “CUSTOM WORD NO.” prompt will be displayed. Enter the next custom word number to be substituted or enter 00 to quit.

System Layout Worksheets
As with any security system, you should first define the installation. This includes determining how many partitions will be used, how many zones per partition, and how many users per partition. You will also need to determine what peripheral devices will be needed, and basic system options such as exit/entry delays, etc. The control panel itself should be located in an area that will facilitate wire runs to all partitions, and will allow access to power and telephone circuits.
To help you lay out a partitioned system, use the following worksheet. This will further simplify the programming process.

PARTITIONS
Partition # Descriptor
(4 char max)
Prim. Sub. # Sec. Sub. # Alpha Default Message
(32 character maximum)
Partition 1
Partition 2
Keyswitch Arming Partition Assignment (1-2 or 9):
Wireless Keypad Partition Assignment (1-2):
Voice Module Partition Assignment (1-2):
Use Partition Descriptor (yes/no)?
Common Lobby Partition Assignment (1-2):
COMMUNICATION OPTIONS BY PARTITION
Option Part. 1 Part. 2
Swinger Suppression Count oo-is: 00=no suppression
Cancel Report After Disarm
Dialer Reports for Panic (* + 1)
Dialer Reports for Panic (it + 3)
Dialer Reports for Panic (* + St)
Dialer Reports for Duress
Burglary Alarm Communications Delay (16 sec.)
SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no)
Option Part. 1 Part. 2
Entry Delay #1 (15-225 seconds):
Exit Delay #1 (15-225 seconds):
Entry Delay #2 (15-225 seconds):
Exit Delay #2  (15-225 seconds):
Quick Arming
Multiple Alarms per Arming
Console Panic for zone 995 (✱ + 1)
Console Panic for zone 996 (# + 3)
Console Panic for zone 999 (✱ + #)
Allow Sign-on (GOTO function)
Non-Bypassable Zone*
Sounder Timeout Duration for Bell 1
(2 min. increments)
Sounder Timeout Duration for Bell 2 & Aux Rly
(2 min. increments)
Console Annunciation During Entry**
Console Annunciation During Exit
Confirmation of Arming Ding for Bell 1
Confirmation of Arming Ding for Bell 2 & Aux Rly
Chime on Bell 1
Chime on Bell 2 & Aux Relay
Access Control Relay (field 1✱76)
Affects Lobby (check partitions that apply)
Årms Lobby (check partitions that apply)
Displays Fire Alarms of Other Partitions
Displays Burg & Panic Alarms of Other Partitions
Displays Troubles of Other Partitions

*Can be any zone 001-032.
**no= 3 beeps yes=continuous

PRINTER OPTIONS
12 or 24 hour Time format
Printer On-Line (yes/no)
*1200 or 300 baud Printer Baud Rate

*Note: Must be 1200 if using pager interface

EVENT LOG TYPES
Option No Yes
Alarm
Trouble
Bypass
Open/Close
System
Test
DEVICES (keypads, 4204, rf receivers, vip module, Irr, vgm)
Device
Address
Type Home
Part
Sound
Opt
Supv
CF?
Keypad
Global
Device
Address
Type Home
Part
Sound
Opt
Supv
CF?
Keypad
Global
0 16
1 17
2 18
3 19
4 20
5 21
6 22
7 23
8 24
9 25
10 26
11 27
12 28
13 29
14 30
15 31

Type:
0 = Device Not Used
1 = Alpha Console
3 = RF Receiver
4 = Output Relay Module
5 = Voice Module
6 = Long Range Radio
8 = Fire Display
9 = Vista Gateway Module

Console Sounder Options:
00 = No Suppression
01 = Suppress Arm/Disarm and Entry/Exit Beeps
02 = Suppress Chime Mode Beeps Only
03 = Suppress Arm/Disarm, Entry/Exit and Chime Mode Beeps

Defaults:
Addresses 00-01 = Alpha Keypad; No Suppression

ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 1-2
4-digit Security Code Access Group 0: 1-8 2-Digit
User #
Partition Global
Arm?
1
Auth.
Level
Open Close 2-Digit
User #
Partition Global
Arm?
2 Auth. level Open Close

Authority Levels:
1=master (arm, disarm, bypass, and/or modify lower level users)
2=manager (arm, disarm, bypass, and/or modify lower level users)
3=operator A (arm, disarm, bypass)
4=operator B (arm, disarm)
5=operator C (arm, disarm only if system was armed with this code)
6=duress code (arm, disarm, triggers silent panic alarm)

ZONE DEFINITIONS FOR ZONES 001-027
Zone
No.
Zone
Type
Partition
(1-2)
Input
Type
(1-13)
Serial #
Device
Loop
Bell Relay
Activation
Report Code Zone Information (part numbers) 8
Aloha Descriptor 13 words max .l
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
ZONE DEFINTIONS FOR ZONES 028-032
Zone No. Zone
Type
Partition
(1-2)
Input Type (1-13) Serial # Device Loop Bell Relay
Activation
Report Code Zone Information (part numbers) &
Alpha Descriptor (3 words max.)
28
29
30
31
32
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, & 999
Zone No. Zone
Type
Enter yes/no for each
partition-field ✱22
Zone Information (part numbers) &
Alpha Descriptor (3 words max.)
1 2 Bell Rel Act. Report
Code
995
996
999
ZONE DEFINITIONS FOR SYSTEM ZONES 970-975; 988; 990 & 997
Zone
No.
Zone
Type
Report
Code
Zone Information (part numbers)
& Alpha Descriptor (3 words max.)
970
971
972
973
974
975
988
990
997
ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-616
Zone No. Zone
Type
Report Code Zone Information (part numbers)
& Alpha Descriptor (3 words max.)
Zone
No.
Zone
Type
Report Code Zone Information (part numbers)
& Alpha Descriptor (3 words max.)
601 609
602 610
603 611
604 612
605 613
606 614
607 615
608 616
ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-831
Zone No. Zone
Type
Report Code Zone Information (part numbers)
& Alpha Descriptor (3 words max.)
Zone
No.
Zone
Type
Report Code Zone Information (part numbers)
& Alpha Descriptor (3 words max.)
800 816
801 817
802 818
803 819
804 820
805 821
806 822
807 823
808 824
809 825
810 826
811 827
812 828
813 829
814 830
815 831

Zone Types:

00=zone not used
01=entry/exit 1
02=entry/exit 2
03=perimeter
04=interior (follower)
05=day/night burglary
06=24 hour silent
07=24 hour audible
08=24 hour auxiliary
09=supervised fire
10=interior (delay)
16=fire w/verification
17=fire waterflow
18=fire supervisory
19=24 hour trouble
20=arm stay
21=arm away
22=disarm
23=no alarm response
27=access control
28=MLB supervision
29=Momentary on exit

Input Types:

00=not used
01=hardwired
03=supervised RF transmitter
04=unsupervised RF transmitter
05=RF button transmitter
06=serial number polling loop
07=dip switch type polling loop
08=right loop dip switch polling loop
09=keypad input
10=PassPoint ACS input
11=VistaKey Door Status Monitor (DM)
12=VistaKey Request to Exit (RE)
13=VistaKey General Purpose (GP)

Bells/Auxiliary Relay Activation

0=none
1=bell 1
2=bell 2
3=bells 1 & 2
4=auxiliary relay
5=bell 1 & auxiliary relay
6=bell 2 & auxiliary relay
7=bells 1 & 2 & auxiliary relay

Output Devices Programming

Applicable only if Relays (4204/4204CF), FSA Modules, or V-Plex Relays (4101SN) are used.
Output Devices – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Notes: . For 4204/4204CF and FSA, the Device Programming section must be programmed for the device address. Set the dip switches on the device for that address.

OUTPUT
DEV #
A START STOP Output
Group
Restrict 0=V-Plex
1=4204 3=FSA
V-Plex Zone #or Dev Add 4204 or FSA Relay # for 4204 or LED # for FSA
EV/ZL Zone ZT / P ZL ZT / P
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96

A = DEVICE ACTION
0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 = Toggle alternately between START and STOP events.

EV = EVENT
0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore

ZL = ZONE LIST
1-15, 0 = Not Used.
“START” ZONE LIST: Upon alarm, fault, or trouble of ANY zone in this list, device action will START.
“STOP” ZONE LIST: Upon restore of ALL zones on this list, device action will STOP. It need not be same list as used for START.

ZT = ZONE TYPE/SYSTEM OPERATION
Choices for Start/Stop Zone Types and System Operation:

00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior W/Delay
16 = Fire With Verification
17 = Fire Waterflow ****
18 = Fire Supervisory
19 = 24-Hr. Trouble
20 = Arming-STAY
21 = Arming-AWAY
22 = Disarming ([Code] + Off)
23 = No Alarm Response
27 = Access Point (allows more than
one relay to be controlled by activation if access point request)
28 = MLB Supervision
29 = Momentary on Exit ***
30 = On Second Code + Off
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout **
38 = Chime
39 = Fire Alarm
40 = Bypassing
41 = AC Power Fail
42 = System Battery Low
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
47 = Console Failure
51 = RF Receiver Failure
52 = Kissoff
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field
1*74) *
57 = YY Seconds (enter YY in field
1*75) *
58 = Duress
60 = Audio Alarm Verification (must
be selected for both START
and STOP operation)
61 = Code + [#] + 67 Key Entry
62 = Bell 2 Timeout
63 = Aux. Relay Timeout

* Stop condition only
** Or at Disarming, whichever occurs earlier
*** Used with VistaKey door access modules.
**** If zone type 17 (waterflow) is selected, an event of fault or alarm should be used as the output start option.

P = PARTITION NO. 1-2, 0 = Any

ZONE LISTS FOR OUTPUT DEVICES – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence. Up to 15 zone lists may be created.
Note: Record desired zone numbers below. More or fewer boxes than shown may be needed, since any list may include any or all of system’s zone numbers.

Zone List 1: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 2: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 3: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 4: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 5: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 6: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 7: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 8: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 9: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 10: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 11: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 12: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 13: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 14: Started or stopped by zone numbers (enter 000 to end entries).

Zone List 15: Started or stopped by zone numbers (enter 000 to end entries).

Scheduling Menu Prompts

To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the menu driven programming functions. Only users with an Installer or Master level user code may enter the #80 mode.
Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.
Menu selections are as follows:

Time Window ?
1 Yes 0 = No 0
For defining up to 20 time windows each with a start and a stop time programmed by entering the hours and minutes.
O/C Schedules ?
1 Yes 0 = No 0
For defining the daily open and close schedules for the 2 partitions. Each partition can be programmed with an opening and closing window for each day of the week and holidays.
Holidays ?
1 Yes 0 = No 0
For defining up to 16 holidays for which partitions they apply.
Timed Events ?
1 Yes 0 = No 0
For defining up to 20 time driven events with the following parameters:
• Time window
• Action desired
• Action specifier
• Activation time
• Days of the week
Access Sched. ?
1 Yes 0 = No 0
For defining the limitation of access schedules for the user codes. Each schedule can be programmed with two window for each day of the week and holidays

#80 & #81 MENU MODE KEY COMMANDS
The following is a list of commands used while in the menu mode.

#80 or #81 Enters Menu mode
[✳] Serves as ENTER key. Press to have keypad accept entry.
[#] Backs up to previous screen.
0 Press to answer NO
1 Press to answer YES
 01-09 All data entries are either 2-digit entries.
0 Exits menu mode, back normal operation mode, when entered at the first question for each category.

Scheduling Worksheets

Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times.
They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Time Window
Number
Start Time (HH:MM) Stop Time (HH:MM)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

(Keep this worksheet handy, as you will be asked for a given time window number later in this section).

Since the time windows are shared among all partitions, it is important to make sure that changing a time window does not adversely affect desired actions in other partitions.

Daily Open/Close Schedule Worksheet: Using the time windows previously defined, fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Part Mon Tues Wed Thur Fri Sat Sun HoI
Op CI Op CI Op CI Op CI Op CI Op CI Op CI Op CI
1
2

Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

HOL Partition
Month: Day 1 2
1 /
2 /
3 /
4 /
5 /
6 /
7 /
8 /
9 /
10 /
11 /
12 /
13 /
14 /
15 /
16 /

Time-Driven Event Worksheet: The system provides up to 20 time driven events that can be programmed for the system.
Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Sched
Num.
Time
Window
Day(s) Action
Desired
Action
Specifier
Activation
Time
M T W T F S S H
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

Below is a list of the “Action” codes (desired actions) used when programming time driven events. Note that these codes are independent of the “Output codes” programmed during the #93 Menu Mode–Output Programming mode. If using Time Driven Events to control Outputs, the following menu items must first be programmed using #93 Menu Mode – Output Programming:

Enter Output No.
Output Group Restriction
Output Type
Zone No.
ECP Address
Relay No.
LED No.
(reference identification number)
(if applicable)
(V-Plex, 4204/4204CF, or FSA)
(V-Plex)
(4204/4204CF or FSA)
(4204/4204CF)
(FSA)

Relay commands:
Action Specifier for commands 01-05 is Relay #, for commands 06-10 is Relay Group #.

01 = Relay On
03 = Relay Close for 2 seconds
05 = Relay Close YY seconds (field 1*75)
07 = Relay Group Off
09 = Relay Group Close XX minutes (field 1*74)
02 = Relay Off
04 = Relay Close XX minutes (field 1*74)
06 = Relay Group On
08 = Relay Group Close for 2 seconds
10 = Relay Group Close YY seconds (field 1*75)

Arm/Disarm commands:
Action Specifier for commands 20-24 is Partition(s), Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for auto-arming and disarming functions.

20 = Arm-Stay
22 = Disarm
24 = Force Arm Away (Auto-bypass faulted zns)
21 = Arm Away
23 = Force Arm Stay (Auto-bypass faulted zns)

Bypass commands:
Action Specifier for commands 30-31 is Zone List #, Activation times 1 (Beginning), 2 (End), 3 (During) are the only valid choices for bypass commands.
30 = Auto bypass – Zone list
31 = Auto unbypass – Zone list

Open/Close Windows:
Action Specifier for commands 40-41 is Partition(s), for 42 is Access Group, and for 50 no specifier is programmed.
Activation time 3 (During) is the only valid choice for these commands.
40 = Enable Opening Window
41 = Enable Closing Window
42 = Enable Access Window
50 = Off-Normal Reminder (Starts local keypad beeping if fire off-normal condition exists)

Access Control Commands (to be used with VistaKey modules only)
Action Specifier for commands 55-60 is Access Point, for 61-66 is Group, for 67-72 is Partition, and for 73-74 is Trigger.

55 = Access Point Grant
57 = Access Point Protect
59 = Access Point Lock
61 = Access Point Group Grant
63 = Access Point Group Protect
65 = Access Point Group Lock
67 = Access Point Partition Grant
69 = Access Point Protect by Partition
71 = Access Point Lock by Partition
73 = Access Point Trigger On
56 = Access Point Grant with Override
58 = Access Point Bypass
60 = Access Point Exit
62 = Access Point Group Grant with Override
64 = Access Point Group Bypass
66 = Access Point Group Exit
68 = Access Point Partition Grant with Override
70 = Access Point Bypass by Partition
72 = Access Point Exit by Partition
74 = Access Point Trigger Off

Additional Commands
Action Specifier for command 75 is Macro, for 76 is Script, for 77-78 is Group, and for 79 no specifier is programmed.

75 = Run Macro
77 = Access Point Group Enable
76 = Run Script
78 = Access Point Group Disable

Activation time:
Refers to when the action is to take place relative to the time window.
1 = Beginning of time window
2 = End of time window
3 = During time window active period only (On at beginning of window, off at end).
4 = Beginning and end of time window (ex. -Coffee break buzzer).

Limitation of Access Worksheet The system provides up to 8 Access Schedules that can be programmed for the system.
Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Acc
Sch
Mon Tues Wed Thurs Fri Sat Sun Hol
W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2
1
2
3
4
5
6
7
8

Temporary Schedule #81 Menu Mode The system provides a Temporary Schedule for each partition. Enter the temporary scheduling mode by pressing [Installer Code] + #81. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.

Partition/Windows Mon Tue Wed Thu Fri Sat Sun
1 Disarm Window
Start Time HH:MM
Stop Time HH:MM
Arm Window
Start Time HH:MM
Stop Time HH:MM
2 Disarm Window
Start Time HH:MM
Stop Time HH:MM
Arm Window
Start Time HH:MM
Stop Time HH:MM

NOTE: As shipped, Vista-32FB is suitable for UL Commercial Fire Installations. Cabinet supports up to 14AH Batteries. Use Vista-ULKT Cabinet Kit to house up to 34.4AH Batteries. Also use this kit along with 1451 Transformer for UL Listed Commercial Burglary Installations.

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - Scheduling Worksheets 1ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - Scheduling Worksheets 2

ADEMCO - logo165 Eileen Way, Syosset, NY, 11791
Copyright © 2000 PITTWAY CorporationADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System - barcodeK3840V1 9/00
www.PDF-Zoo.com
firealarmresources.com

Documents / Resources

ADEMCO VISTA 32FB Commercial Fire and Burglary Partitioned Security System [pdf] User Guide
VISTA 32FB Commercial Fire and Burglary Partitioned Security System, VISTA 32FB, Commercial Fire and Burglary Partitioned Security System, Partitioned Security System

References

Leave a comment

Your email address will not be published. Required fields are marked *