e2s-GNExB2X05-Flameproof-Xenon-Beacons-logo

e2s GNExB2X05 Flameproof Xenon Beacons

e2s-GNExB2X05-Flameproof-Xenon-Beacons-product-image

Product Table

 Standard  Model Nom. Voltage  Voltage Range Nom. Operating Current* Max Current
 ATEX / IECEx / UKEX NEC / CEC GNExB2X05DC012 12Vdc 12-14Vdc 585mA 600mA
GNExB2X05DC024 24Vdc 20-28Vdc 295mA 350mA
GNExB2X05DC048 48Vdc 42-54Vdc 145mA 150mA
GNExB2X05AC115 115Vac 110-120Vac 50/60Hz 140mA 200mA
GNExB2X05AC230 230Vac 220-240Vac 50/60Hz 70mA 100mA
GNExB2X10DC024 24Vdc 20-28Vdc 605mA 710mA
GNExB2X10DC048 48Vdc 42-54Vdc 230mA 250mA
GNExB2X10AC115 115Vac 110-120Vac 50/60Hz 220mA 300mA
GNExB2X10AC230 230Vac 220-240Vac 50/60Hz 130mA 180mA
 ATEX / IECEx / UKEX GNExB2X15DC024 24Vdc 20-28Vdc 835mA 920mA
GNExB2X15DC048 48Vdc 42-54Vdc 330mA 360mA
GNExB2X15AC115 115Vac 110-120Vac 50/60Hz 310mA 420mA
GNExB2X15AC230 230Vac 220-240Vac 50/60Hz 170mA 230mA
GNExB2X21DC024 24Vdc 20-28Vdc 1130mA 1240mA
GNExB2X21DC048 48Vdc 42-54Vdc 530mA 560mA
GNExB2X21AC115 115Vac 110-120Vac 50/60Hz 500mA 530mA
GNExB2X21AC230 230Vac 220-240Vac 50/60Hz 195mA 270mA
*Rate at 1Hz
The table shows the input current taken by the various beacons. Nominal current at nominal voltage and 1Hz flash rate.
Max. rated current at worst case supply voltage and flash rate.
Table 1: Electrical Ratings.

Ensure the system power supply is capable of providing the maximum current required for all beacons. Review associated cable size, length and quantity of beacons on each circuit.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(1)Warnings

  • POTENTIAL ELECTROSTATIC CHARGING HAZARD –CLEAN ONLY WITH A DAMP CLOTH.
  • DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT.

ALL ENTRIES M20 X 1.5MM.
USE SUITABLE RATED CABLES AND CABLE GLANDS IF TEMPERATURE EXCEEDS AS PER STANDARDS INDICATIONS BELOW.

FOR ATEX / IECEx / UKEX STANDARDS:
70ºC AT ENTRY OR 80ºC AT BRANCHING POINT.
FOR NEC / CEC STANDARDS:  60ºC AT ENTRY OR 60ºC AT BRANCHING POINT.

Marking & Rating Information

All units have a rating label, which carries the following important information:

  • Unit Model.
  • Voltage Range
  • Nominal Voltage
  • Max. Current

See Table 1 for electrical ratings of each Unit Model.

ATEX / IECEx / UKEX Ratings

Standards
EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7):
Explosive Atmospheres – Equipment. General Requirements EN60079-1:2014 / IEC60079-1:2014 (Ed 7):
Explosive Atmospheres – Equipment Protection by Flameproof Enclosures “d” BS EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2):
Explosive Atmospheres – Equipment Dust Ignition Protection by Enclosure “t”
Ratings
GNExB2: Ex db IIC T5 Gb Ta -50°C to +70°C
X05DC012 Ex db IIC T6 Gb Ta -50°C to +60°C
X05DC024 Ex tb IIIC T89°C Db Ta -50°C to +70°C
X05DC048
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X05AC115 Ex db IIC T5 Gb Ta -50°C to +55°C
X05AC230 Ex db IIC T6 Gb Ta -50°C to +40°C
Ex tb IIIC T110°C Db Ta -50°C to +70°C
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X10DC024 Ex db IIC T5 Gb Ta -50°C to +45°C
X10DC048 Ex tb IIIC T117°C Db Ta -50°C to +70°C
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X10AC115 Ex db IIC T5 Gb Ta -50°C to +40°C
X10AC230 Ex tb IIIC T122°C Db Ta -50°C to +70°C
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X15DC024 Ex tb IIIC T125°C Db Ta -55°C to +70°C
X15DC048
GNExB2: Ex db IIC T3 Gb Ta -50°C to +70°C
X15AC115 Ex db IIC T4 Gb Ta -50°C to +65°C
X15AC230 Ex tb IIIC T134°C Db Ta -55°C to +70°C
GNExB2: X21DC024 X21DC048 Ex db IIC T3 Gb Ta -50°C to +60°C Ex db IIC T4 Gb Ta -50°C to +55°C Ex tb IIIC T135°C Db Ta -50°C to +60°C
GNExB2: Ex db IIC T3 Gb Ta -50°C to +70°C
X21AC115 Ex db IIC T4 Gb Ta -50°C to +60°C
X21AC230 Ex tb IIIC T138°C Db Ta -50°C to +70°C

Certificate No.
DEMKO 15ATEX1448X IECEx UL15.0003X UL21UKEX2136X

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(2)

NEC / CEC Ratings

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(3)

All models are approved for use as Visual Signal Device for use as General Signalling:
UL1638A & CSA C22.2 No 205-17

NEC Class / Zone Ratings US Codes

Standards
UL 60079-0 (Ed. 7) 04/15/2020
Explosive Atmospheres – part 0: Equipment – General Requirements
UL 60079-1 (Ed. 7) 2015
Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures ‘d’
Ratings
GNExB2: X05DC012 X05DC024* X05DC048 Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +70°C Class I Zone 1 AEx db IIC T6 Gb Ta -50°C to +60°C
GNExB2: X05AC115 X05AC230 Class I Zone 1 AEx db IIC T4 Gb Ta -50°C to +70°C Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +55°C Class I Zone 1 AEx db IIC T6 Gb Ta -50°C to +40°C
GNExB2: X10DC024* X10DC048 Class I Zone 1 AEx db IIC T4 Gb Ta -50°C to +70°C Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +45°C
GNExB2: X10AC115 X10AC230 Class I Zone 1 AEx db IIC T4 Gb Ta -50°C to +70°C Class I Zone 1 AEx db IIC T5 Gb Ta -50°C to +40°C
*SIL Suitable

Installation must be carried out in compliance with the National Electric Code.

CEC Class / Zone Ratings Canada

Standards
CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019
Explosive Atmospheres – Part 0: Equipment – General Requirements
CAN/CSA C22.2 No. 60079-1 (Ed. 3) 2016
Electrical Apparatus for Explosive Gas Atmospheres – Part 1: Flameproof Enclosures ‘d’
Rating
GNExB2: Ex db IIC T5 Gb Ta -50°C to +70°C
X05DC012 Ex db IIC T6 Gb Ta -50°C to +60°C
X05DC024
X05DC048
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X05AC115 Ex db IIC T5 Gb Ta -50°C to +55°C
X05AC230 Ex db IIC T6 Gb Ta -50°C to +40°C
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X10DC024 Ex db IIC T5 Gb Ta -50°C to +45°C
X10DC048
GNExB2: Ex db IIC T4 Gb Ta -50°C to +70°C
X10AC115 Ex db IIC T5 Gb Ta -50°C to +40°C
X10AC230

Installation must be carried out in compliance with the Canadian Electric Code.

NEC & CEC Class / Division Ratings for US / Canada, USL CNL

Standards
GNExB2X
Xenon beacons
UL1638A (Ed. 1) 2016
Standard for Visual Signal Appliances for General Signalling Use
CSA C22.2 No. 205-17 (Ed. 3) 2017
Signal Equipment
Ratings
GNExB2: Class I Div 2 Group ABCD T5 Ta -50°C to +70°C
X05DC012 Class I Div 2 Group ABCD T6 Ta -50°C to +60°C
X05DC024
X05DC048
GNExB2: Class I Div 2 Group ABCD T4 Ta -50°C to +70°C
X05AC115 Class I Div 2 Group ABCD T5 Ta -50°C to +55°C
X05AC230 Class I Div 2 Group ABCD T6 Ta -50°C to +40°C
GNExB2: Class I Div 2 Group ABCD T4 Ta -50°C to +70°C
X10DC024 Class I Div 2 Group ABCD T5 Ta -50°C to +45°C
X10DC048
GNExB2: Class I Div 2 Group ABCD T4 Ta -50°C to +70°C
X10AC115 Class I Div 2 Group ABCD T5 Ta -50°C to +40°C
X10AC230

The certification approval has validated continuous use up to 38°C ambient and are for transient use up to 70°C ambient.
Installation must be carried out in compliance with the National Electric Code / Canadian Electric Code.

Zones, Gas Group, Category and Temperature Classification

The units can be installed in locations with the following conditions:

Area Classification
Zone 1 Explosive gas air mixture likely to occur in normal operation.
Zone 2 Explosive gas air mixture not likely to occur in normal operation, and if it does, it will only exist for a short time.
Zone 21 (ATEX / IECEx / UKEX only) Explosive dust air mixture likely to occur in normal operation.
Zone 22 (ATEX / IECEx / UKEX only) Explosive dust air mixture not likely to occur in normal operation, and if it does, it will only exist for a short time.
Gas Groupings
Group IIA Propane
Group IIB Ethylene
Group IIC Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1 450ºC
T2 300ºC
T3 200ºC
(GNExB2X15AC & GNExB2X21AC up to 70°C
ambient; GNExB2X21DC up to 60°C ambient)
T4 135ºC
(GNExB2X05AC, GNExB2X10DC, GNExB2X10AC & GNExB2X15DC up to 70°C ambient; GNExB2X15AC up to 65°C ambient; GNExB2X21DC up to 55°C ambient; GNExB2X21AC up to 60°C ambient)
T5 100ºC (GNExB2X05DC up to 70°C ambient; GNExB2X05AC up to 55°C ambient; GNExB2X10DC up to 45°C ambient; GNExB2X10AC up to 40°C ambient)
T6 85ºC ATEX / IECEx / UKEX: GNExB2X05DC up to 60°C ambient, GNExB2X05AC up to 40°C ambient NEC / CEC: Up to 65ºC ambient
Dust Groupings (ATEX / IECEx / UKEX only)
Group IIIA Combustible Flyings
Group IIIB Non-conductive Dust
Group IIIC Conductive Dust
Maximum Surface Temperature for Dust Applications (ATEX / IECEx / UKEX only)
GNExB2X05DC 89ºC
GNExB2X05AC 110ºC
GNExB2X10DC 117ºC
GNExB2X10AC 122ºC
GNExB2X15DC 125 ºC
GNExB2X15AC 134ºC
GNExB2X21DC 135ºC
GNExB2X21AC 138ºC
Equipment Category
2G / 2D
Ambient Temperature Range
-50°C to +70°C
IP Rating
IP6X to EN/IEC60079-0 IP66 to EN60529

Special Conditions for Safe Use

Repair of the flame path / cemented joints is not permitted.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(4)

Figure 1: Flame Path.
The enclosure is non-conducting and may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build-up of electrostatic charges on non-conducting surfaces. The stainless steel beacon guard is not earthed and may generate an ignition-capable level of electrostatic charges. It has a capacitance of 10pF according to EN/IEC60079-0, clause 7.5. All entries must be fitted with a suitable seal at the interface with enclosure.

Product Mounting and Access

Location and Mounting
The location of the beacons should be made with due regard to the area over which the warning signal must be visible. They should only be fixed to services that can carry the weight of the unit. The beacons should be securely bolted to a suitable surface using the 9.4mm diameter bolt holes in the base of the unit (see figure 2).

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(5)

Access to the Flameproof Enclosure
In order to connect the electrical supply cables to the beacon it is necessary to remove the flameproof cover to gain access to the flameproof chamber. To access the Ex d chamber, loosen the M4 grub screw on the beacon cover. Open the enclosure by turning the beacon cover counterclockwise and remove the cover, taking extreme care not to damage the flameproof threads in the process (see figure 3).

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(6)

On completion of the installation the flameproof threaded joint should be inspected to ensure that they are clean and that they have not been damaged during installation. Flameproof threaded joints are not intended to be repaired. Ensure that the ‘O’ ring seal is in place and undamaged. When fitting the flameproof cover ensure the thread is engaged correctly. Fully tighten the cover all the way, ensure no gap is visible between the cover and base of the beacon enclosure. Tighten the M4 grub screw.

Installation Requirements

Installation Standards Compliance
e2s-GNExB2X05-Flameproof-Xenon-Beacons-(7)Attention: Disconnect from power source before installation or service to prevent electric shock.
The beacons must only be installed by suitably qualified personnel in accordance with the latest issues of the relevant standards.

ATEX / IECEx & UKEx installation standards

  • EN60079-14 / IEC60079-14: Explosive atmospheres – Electrical installations design, selection and erection.
  • EN60079-10-1 / IEC60079-10-1: Explosive atmospheres – Classification of areas. Explosive gas atmospheres.
  • EN60079-10-2 / IEC60079-10-2: Explosive atmospheres – Classification of areas. Explosive dust atmospheres.
  • The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training.

NEC / CEC Installation Standards
Cautions
e2s-GNExB2X05-Flameproof-Xenon-Beacons-(1)Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70 or CSA 22.1 Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32.
e2s-GNExB2X05-Flameproof-Xenon-Beacons-(7)Attention: Disconnect from power source before installation or service to prevent electric shock
The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training.

Cable Selection and Connections
When selecting the cable size, consideration must be given to the input current that each unit draws (see table 1), the number of beacons on the line and the length of the cable runs. The cable size selected must have the necessary capacity to provide the input current to all of the beacons connected to the line. Electrical connections are to be made into the terminal blocks on the PCBA, using solid wire 0.5-4mm2 / AWG 20-12 or stranded wire, sizes 0.5-2.5mm2 / AWG 24-14. Wire insulation needs to be stripped 8mm. Wires may be fitted securely with crimped ferrules.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(8)

Terminal screws need to be tightened down with a tightening torque of 0.45 Nm / 5 Lb-in. A 5-way terminal block is provided on the AC Beacon: 2-off Live, 2-off Neutral and 1-off Earth terminals in total. A 4-way terminal block is provided on the DC Beacon: 2-off +ve and 2-off -ve terminals.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(9)

When connecting wires to the terminals great care should be taken to dress the wires so that when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks. This is particularly important when using cables with large cross-sectional areas such as 2.5mm².

Earthing
Please note that for AC supply voltage product versions the Earth terminal on the PCBA does not provide an earth connection to the product enclosure. The enclosure must be independently earthed using either the external or internal earth fixing point, (see fig 5 and notes below). Internal earthing connections should be made to the Internal Earth terminal in the base of the housing using a ring crimp terminal to secure the earth conductor under the earth clamp. The earth conductor should be at least equal in size and rating to the incoming power conductors. External earthing connections should be made to the M4 earth stud, using a ring crimp terminal to secure the earth conductor to the earth stud. The external earth conductor should be at least 4mm2 in size.

Cable Glands, Blanking Elements & Adapters

Follow the minimum temperature ratings of cables and cable glands according to the approvals applied.

ATEX / IECEx & UKEx Requirements
The cable entry temperature may exceed +70ºC or the cable branching point temperature may exceed 80ºC at high ambient temperatures and therefore suitable heat resisting cables and cable glands must be used, rated as follows:

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(10)

Table 2: ATEX / IECEx & UKEx Min. Ratings of Cables & Cable Glands.

NEC / CEC Requirements Only
For high ambient temperatures the cable entry temperature may exceed 60ºC or the cable branching point temperature may exceed 60ºC and therefore suitable heat resisting cables and cable glands must be used, with a rated service temperature at least as stated below:

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(11)

Table 3: NEC / CEC Min. Ratings of Cables & Cable Glands. Cable Glands & Blanking Plugs
Appropriate cable glands to be customer supplied.

ATEX / IECEx & UKEx Requirements Only
The cable gland entries have an M20 x 1.5 entry thread. Only suitably rated and ATEX / IECEx & UKEx certified cable glands which must be suitable for the type of cable being used and also meet the requirements of the current Ex ‘d’ flameproof installation standards EN 60079-14 / IEC60079-14. If the installation is made using conduit, openings must have a sealing fitting connected as close as practical to the wall of the enclosure, but in no case more than the size of the conduit or 50mm, whichever is the lesser. When only one cable entry is used the other entries must be closed with suitably rated and ATEX / IECEx & UKEx certified blanking plugs.

NEC / CEC Requirements Only
The cable entries have an M20 x 1.5 – 6H entry thread. If the installation is made using cable glands, only suitably rated and certified cable glands must be used. They must be suitable for the type of cable being used and also meet the requirements of the current NEC / CEC installation standards. If the installation is made using conduit, openings must have a sealing fitting connected as close as practical to the wall of the enclosure, but in no case more than the size of the conduit or 50mm, whichever is the lesser. For use in Class I Division II locations, in order to maintain the db type protection, flameproof conduit seals and/or cable glands must be used. Any unused cable entries must be closed with suitably rated and certified blanking plugs.

Ingress Protection
Follow instructions according to the approvals applied.

ATEX / IECEx & UKEx Requirements Only
If a high IP (Ingress Protection) rating is required then a suitable sealing washer must be fitted under the cable glands or blanking plugs. A minimum ingress protection rating of IP6X must be maintained for installations in explosive dust atmospheres.

NEC / CEC Requirements Only
If a high IP (Ingress Protection) rating is required then a suitable sealing washer must be fitted under the cable glands or blanking plugs. A minimum ingress protection rating of IP6X must be maintained for installations in explosive dust atmospheres.

Adapters
The GNEx Beacon Range can be supplied with the following types of adapters:

  • M20 to 1/2” NPT
  • M20 to 3/4” NPT
  • M20 to M25

It is important to note that stopping plugs cannot be fitted onto adapters, only directly onto the M20 entries. Any other adapters used must be suitably rated as per the applicable standards.

Flash Pattern Settings

Warning – high-intensity light source. Avoid looking directly at the light source for extended periods of time.
The GNExB2 beacon can produce different flash patterns as shown in Table 4. The flash patterns are selected by operation of the flash setting DIP switch on the PCB, Fig 6.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(12)

Switch Setting S1 Mode
00 1Hz (60FPM)
01 1.33Hz (80FPM)
10 1.5Hz (90FPM)
11 Double Flash

Table 4: Switch Positions for Flash Patterns

End of Line Monitoring (DC Units)

All DC units have a blocking diode fitted in their supply input lines. An end of line monitoring diode or an end of line monitoring resistor can be connected across the +ve and –ve terminals in the flameproof chamber. If an end of line resistor is used it must have a minimum resistance value of 3k3 ohms and a minimum wattage of 0.5W or a minimum resistance value of 500 ohms and a minimum wattage of 2W. The resistor must be connected directly across the +ve and – ve terminals as shown in the following drawing. The resistor leads should be kept as short as possible.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(13)

Interchangeable & Spare Parts

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(14)Warning – Hot surfaces. External surfaces and internal components may be hot after operation, take care when handling the equipment.

  • The beacon lens is interchangeable, contact European Safety Systems Ltd for a replacement lens available in various colours.
  • The guard is an integral part of the protection and must be reassembled exactly the same way as it was disassembled.
  • To change the lens, unscrew the M5 socket head screws and remove the M5 screws, M5 spring & flat washers.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(15)

Remove the guard and replace the old lens with the new lens.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(16)

Fit the guard back on to the lens and casting, align the holes of the guard, lens and casting. To reattach the lens, the fixings MUST be in the order shown in figure 10.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(17)

Maintenance, Overhaul and Repair
Maintenance, repair and overhaul of the equipment should only be carried out by suitably qualified personnel  in  accordance with the current relevant standards:  EN60079 19/IEC60079-19 Explosive atmospheres Equipment repair, overhaul and reclamation  EN 60079-17/IEC60079-17 Explosive atmospheres Electrical installations inspection and maintenance Units must not be opened while an explosive atmosphere is present. If opening the unit during maintenance operations a clean environment must be maintained and any dust layer removed prior to opening the unit. Repair of the flameproof threaded joints and cemented joints is not permitted.
Electrostatic charging hazard – Clean only with a damp cloth.

SIL 2 Reliability Data

Reliability and Functional safety IEC/EN61508 which has been assessed and is considered suitable for use in low demand safety function:

  1. Random Hardware Failures and Architectural constraints (route 2H).
  2. As an unvoted item (i.e. hardware fault tolerance of 0) at SIL 2.
    The product was assessed against failure modes:
    • Failure respond to an input by lighting a beacon.
    • Spurious light output despite no input.
  3. When employing the device in a SIL2 compliant system the user should ensure frequent or continuous automatic monitoring of continuity.
Integrity in respect of failure to function SIL2 & SIL1
Total Failure rate 0.48 pmh
“Hazardous” failure rate (revealed) 0 pmh
“Hazardous” failure rate (unrevealed) 0.48 pmh
“Safe” failure rate (revealed) 0 pmh
“Safe” failure rate (unrevealed) 0
System type B
Hardware Fault Tolerance 0
Diagnostic Coverage >60%
PFD (hazardous failure) 2.1 x 10-3
Proof Test Interval Up to 1 year

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(18)

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(19)

EU Declaration of Conformity

Manufacturer:
European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom

Authorised Representative:
E2S Warnsignaltechnik UG
Charlottenstrasse 45‐51
72764 Reutlingen
Germany

Equipment Type:
GNExB1X05
GNExB2X05, GNExB2X10, GNExB2X15, GNExB2X21 GNExB2LD2N GNExJ2
Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially Explosive Atmospheres (ATEX)

Notified Body for EU type Examination (Module B):
UL International Demko A/S
Notified Body No.: 0539
Borupvang 5A, 2750 Ballerup, Denmark

EU‐type Examination Certificate (Module B):
DEMKO 15ATEX1448X
Sira Certification Service
Notified Body No.: 2813
CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands

Notified Body for Quality Assurance Notification / Conformity to EU‐type based on quality assurance of the production process (Module D):
Quality Assurance Notification (Module D):
Provisions fulfilled by the equipment:
SIRA 05 ATEX M342
II 2G Ex db IIC T4…T6 Gb
II 2D Ex tb IIIC T80°C…T138°C Db
IP6X Dust Protection to EN60079‐0 / EN60079‐31

Standards applied:
EN IEC 60079‐0:2018
EN 60079‐1: 2014
EN 60079‐31: 2014

Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000‐6‐1:2007 EN 61000‐6‐2:2005
EN 61000‐6‐3:2007 / A1:2011 / AC: 2012 EN 61000‐6‐4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS) The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment, including amendment by Directive 2015/863/EU.

Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.

Other Standards and Regulations
EN 60529:1992+A2:2013 ‐ Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/67
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives, regulations and standards. This Declaration is issued under the sole responsibility of the manufacturer.

e2s-GNExB2X05-Flameproof-Xenon-Beacons-(20)UKCA Declaration of Conformity

Manufacturer:
European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom

Equipment Type:
GNExB1X05 GNExB2X05, GNExB2X10, GNExB2X15, GNExB2X21 GNExB2LD2 GNExJ2
Directive UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres (UKCA)

Notified Body for UK type Examination (Module B):
UL International (UK) Ltd
Notified Body No.: 0843
Unit 1-3 Horizon Kingsland Business Park, Wade Road, Basingstoke, Hampshire RG24 8AH UK

UK-type Examination Certificate (Module B):
UL21UKEX2136X
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Notified Body for Quality Assurance Notification / Conformity to EU-type based on quality assurance of the production process (Module D):
Quality Assurance Notification (Module D):
CSAE 22UKQAN0046
II 2G Ex db IIC T4…T6 Gb
II 2D Ex tb IIIC T80°C…T138°C Db
IP6X Dust Protection to EN60079-0 / EN60079-31

Provisions fulfilled by the equipment:
Standards applied:
EN IEC 60079-0:2018
EN 60079-1: 2014
EN 60079-31: 2014

Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000-6-1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1: 2011
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS) The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment, including amendment by Directive 2015/863/EU. Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH) The product and all the components contained within it are free from substances of very high concern.

Other Standards and Regulations
EN 60529:1992+A2:2013 – Degrees of protection provided by enclosures (IP code) – enclosure rated IP66/67
E2S Telephone: +44 (0)20 8743 8880
Fax: +44 (0)20 8740 4200
Email: sales@e2s.com www.e2s.com DC-098_Issue_A (GNExB, GNExJ UKCA).docx – Page 1 of 2 – QAF_252_Issue_5
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.

Documents / Resources

e2s GNExB2X05 Flameproof Xenon Beacons [pdf] Instruction Manual
GNExB2X05, GNExB2X10, GNExB2X15, GNExB2X21, GNExB2X05 Flameproof Xenon Beacons, GNExB2X05, Flameproof Xenon Beacons, Xenon Beacons, Beacons

References

Leave a comment

Your email address will not be published. Required fields are marked *