Sonos DC Sounder
Installation Instructions
Sonos PSS-0089 DC Sounder
TONE | TONE TYPE | TONE DESCRIPTION/ APPLICATION | DIP SWITCH 1 – 2 – 3 – 4 – 5 | dBA @ 1m | mA |
1. | 970Hz | O – O – O – O – O | 99 | 21 | |
2. | 800Hz/970Hz @ 2Hz | O – O – O – O – I | 100 | 20 | |
3. | 800Hz – 970Hz @ 1Hz | O – O – O – I – O | 100 | 20 | |
4. | 970Hz 1s OFF/1s ON | O – O – O – I – I | 99 | 14 | |
5. | 970Hz, 0.5s/ 630Hz, 0.5s | O – O – I – O – O | 99 | 19 | |
6. | 554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001 ) | O – O – I – O – I | 97 | 13 | |
7. | 500 – 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000 Dutch Slow Whoop) | O – O – I – I – O | 99 | 16 | |
8. | 420Hz 0.6s ON/0.6s OFF (Australia AS1670 Alert tone) | O – O – I – I – I | 96 | 9 | |
9. | 1000 – 2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation) | O – I – O – O – O | 104 | 14 | |
10. | 550Hz/440Hz @ 0.5Hz | O – I – O – O – I | 97 | 14 | |
11. | 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 ) | O – I – O – I – O | 98 | 12 | |
12. | 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201) | O – I – O – I – I | 94 | 21 | |
13. | 1200Hz – 500Hz @ 1Hz (DIN 33 404) | O – I – I – O – O | 99 | 17 | |
14. | 400Hz | O – I – I – O – I | 95 | 13 | |
15. | 550Hz, 0.7s/1000Hz, 0.33s | O – I – I – I – O | 98 | 17 | |
16. | 1500Hz – 2700Hz @ 3Hz | O – I – I – I – I | 104 | 34 | |
17. | 750Hz | I – O – O – O – O | 99 | 18 | |
18. | 2400Hz | I – O – O – O – I | 106 | 45 | |
19. | 660Hz | I – O – O – I – O | 96 | 17 | |
20. | 660Hz 1.8s ON/1.8s OFF | I – O – O – I – I | 96 | 12 | |
21. | 660Hz 0.15s ON/0.15s OFF | I – O – I – O – O | 96 | 11 | |
22. | 510Hz, 0.25s/ 610Hz, 0.25s | I – O – I – O – I | 98 | 15 | |
23. | 800/1000Hz 0.5s each (1Hz) | I – O – I – I – O | 100 | 21 | |
24. | 250Hz – 1200Hz @ 12Hz | I – O – I – I – I | 98 | 13 | |
25. | 500Hz – 1200Hz @ 0.33Hz | I – I – O – O – O | 99 | 17 | |
26. | 2400Hz – 2900Hz @ 9Hz | I – I – O – O – I | 101 | 40 | |
27. | 2400Hz – 2900Hz @ 3Hz | I – I – O – I – O | 104 | 40 | |
28. | 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation) | I – I – O – I – I | 98 | 10 | |
29. | 800Hz – 970Hz @ 9Hz | I – I – I – O – O | 99 | 20 | |
30. | 800Hz – 970Hz @ 3Hz | I – I – I – O – I | 100 | 20 | |
31. | 800Hz, 0.25s ON/1s OFF | I – I – I – I – O | 99 | 8 | |
32. | 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) | I – I – I – I – I | 99 | 17 |
Type | CPR Reference | CPD Number |
PSS-0084 | Reference 0832-CPR-0298 | 0832-CPD-0298 |
PSS-0089 | Reference 0832-CPR-0298 | 0832-CPD-0298 |
Technical Data Doc.18-186213
Type A: For indoor use (Shallow Base)
Fire Alarm Device – Sounder
Type B: For outdoor use (Deep Base)
Declared Performance | |||
Essential Characteristics | EN54-3:2001+A1:2002 A2:2006 Sub clause | TYPE A | TYPE B |
Reproducibility | 5.2 | PASS | PASS |
Operational performance | 5.3 | PASS | PASS |
Durability | 5.4 | PASS | PASS |
Dry Heat (operational) | 5.5 | PASS | PASS |
Dry Heat (endurance) | 5.6 | PASS | PASS |
Cold (operational) | 5.7 | PASS | PASS |
Damp heat, cyclic (operational) | 5.8 | PASS | PASS |
Damp heat, steady state (endurance) | 5.9 | PASS | PASS |
Damp Heat, cyclic (endurance) | 5.10 | N/A | PASS |
SO2 corrosion (endurance) | 5.11 | PASS | PASS |
Shock (operational) | 5.12 | PASS | PASS |
Impact (operational) | 5.13 | PASS | PASS |
Vibration (operational) | 5.14 | PASS | PASS |
Vibration (endurance) | 5.15 | PASS | PASS |
Electrostatic discharge (operational) | 5.16 | PASS | PASS |
Radiated electromagnetic fields (operational) | 5.16 | PASS | PASS |
Voltage transients, fast transient bursts (operational) | 5.16 | PASS | PASS |
Enclosure Protection | 5.17 | PASS | PASS |
Installation
If required, the mechanism for locking the sounder to the base can be activated by removing the thin section of plastic shown in Fig. 1a with side cutters or a similar tool. To open a locked head, remove the small rubber bung from the hole on the side of the sounder, insert a tool into the hole and depress the clip whilst twisting the head. The O-ring and bung must be re-fitted to maintain the weatherproofing.
An alternative locking method is shown in Fig. 1b. Drive the hexagonal locking screw forward by turning a 1.5mm hexagonal key clockwise until the head is locked.
Wiring
Line | Terminal Marking |
Positive Supply (9 to 60V DC) | (3) IN+ |
Negative Supply (OV) | (2) – or COM – |
2nd Stage Alarm Control (if required) | (1) |
The second stage alarm (‘remote tone switching’) is activated by connecting terminal to Negative (OV) Supply.
A separate earth terminal is provided on the deep base for connecting the screen or functional earth. On the shallow base, terminal 5 can be used for this purpose.
Tone Selection and Volume Control
a) The tone is selected using the 5 way dipswitch on the bottom of the sounder head. Refer to the table overleaf for details of the available tones and the switch settings required to select them.
b) The sound output of the unit can be reduced by adjusting the potentiometer on the bottom of the sounder.
Technical Specification
Supply Voltage | 9 – 60V DC |
Current | 4- 41mA* |
Peak Sound Level | 94 – 106 dBA at 1m* |
Number of tones | 32 |
Frequency Range | 400 – 2850 Hz* |
Rating | Continuous |
Operating Temperature | – 25˚C to + 70˚C |
Casing | High Impact Polycarbonate |
IP Rating | IP21/IP65 (deep base) |
Synchronization | Automatic |
*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17v DC only.
Telecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK.
Tel: +44 1706 233879
Issue 20 (Dec 2014) INS533-20
Copyright © Telecom Ltd.
sales@klaxonsignals.com
www.klaxonsignals.com
Documents / Resources
KLAXON Sonos PSS-0089 DC Sounder [pdf] Installation Guide PSS-0084, PSS-0089, Sonos PSS-0089 DC Sounder, DC Sounder |