FFAD2234W1 Low Humidity 22 Pint Energy Star Dehumidifier

“`html

Specifications

  • Model Numbers: FFAD2234W1, FFAD3534W1
  • Manufacturer: Frigidaire
  • Country of Origin: USA/Canada

Product Information

Welcome to our family! This manual serves as your guide for the
proper use and maintenance of your dehumidifier. Please read
through it thoroughly before operating the appliance. Refer back to
it as needed for quick assistance with troubleshooting and care
instructions.

For additional resources, FAQs, tips, and support, visit our
website at www.frigidaire.com. Our
customer service team is also available via chat or phone to assist
you with any queries or issues you may encounter.

Product Usage Instructions

Important Safety Instructions

Before using the dehumidifier, ensure to read and understand all
safety precautions outlined in the manual. Failure to follow these
instructions may result in serious injury or damage to the
appliance.

Location

Place the dehumidifier in a well-ventilated area with access to
a grounded electrical outlet. Avoid using extension cords or
adapter plugs to prevent fire hazards or electric shock.

How It Works

The dehumidifier operates by removing excess moisture from the
air, helping to maintain a comfortable humidity level in your
space. It works by drawing in humid air, passing it over a cold
coil to condense the moisture, and then releasing dry air back into
the room.

Dehumidifier Features

Features of the dehumidifier include adjustable humidity
settings, a water tank for collected moisture, auto-shutoff when
the tank is full, and indicator lights for filter replacement.

Operating Instructions

To start using the dehumidifier, plug it into a power source,
set your desired humidity level, and turn the unit on. Empty the
water tank regularly to ensure efficient operation. Clean the
filter as recommended in the care instructions.

Care And Cleaning

Regularly clean the water tank, filter, and exterior surfaces of
the dehumidifier to maintain optimal performance. Refer to the care
section of the manual for detailed cleaning instructions.

FAQs

    1. Q: How often should I clean the filter?

A: The filter should be cleaned every two weeks
under normal operating conditions. If used in a dusty environment,
more frequent cleaning may be required.

    1. Q: What should I do if the dehumidifier stops
      working?

A: Check the power source, ensure the water
tank is properly seated, and that the filter is clean. If issues
persist, refer to the troubleshooting section of the manual or
contact customer support.

“`

use care Dehumidifier &

Introduction ……………………………………………..2 Important Safety Instructions ……………….3 Location…………………………………………………… 11 How It Works………………………………………….. 11 Dehumidifier Features………………………….. 12 Operating Instructions …………………………. 12
Frigidaire.com USA 1-800-944-9044

Care And Cleaning ……………………………….. 16 Storage …………………………………………………… 17 Normal Sounds ……………………………………… 17 Before You Call……………………………………… 18 Major Appliance Limited Warranty……. 19
Model: FFAD2234W1 FFAD3534W1
Frigidaire.ca Canada 1-800-265-8352

2

INTRODUCTION

family Welcome to our
Thank you for bringing Frigidaire® into your home! We see your purchase as the beginning of a long relationship together.
This manual is your resource for the use and care of your product. Please read it before using your appliance. Keep it handy for quick reference. If something doesn’t seem right, the troubleshooting section will help you with common issues.
FAQs, helpful tips and videos, cleaning products, and kitchen and home accessories are available at www.frigidaire.com.
We are here for you! Visit our website, chat with an agent, or call us if you need help. We may be able to help you avoid a service visit. If you do need service, we can get that started for you.
Let’s make it official! Be sure to register your product.
Keep your product info here so it’s easy to find.
Model Number
Serial Number
Purchase Date

IMPORTANT SAFETY INSTRUCTIONS

3

WARNING
For Your Safety · Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance. Read product labels for flammability and other warnings. · Discard water from bucket. Water is not potable and cannot be used for drinking.
WARNING

· Do not leave children unattended in an area where the appliance is operating. Do not allow them to sit or stand on the appliance.
· This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
· Children should be supervised to ensure that they do not play with the appliance.

Electrical Information · For your safety and protection, this
dehumidifier is equipped with a three-prong grounding plug on the power cord. Do not, under any circumstances, cut or remove the round ground prong from the plug. · Your dehumidifier must be plugged directly into a properly grounded and polarized three-prong receptacle. lf the wall receptacle you intend to use will not accept a three-prong plug, or if you are not sure the outlet is adequately grounded or protected by a time delay fuse or circuit breaker, have a qualified electrician install the proper outlet according to the National Electrical Code and applicable local codes and ordinances. Do not use an extension cord or an adapter plug. · Never unplug the dehumidifier by pulling on the power cord. Always grip the plug firmly and pull straight out from the receptacle. · Do not pinch, bend, or knot the power cord.
WARNING
Child Safety Precautions
· Destroy the carton, plastic bags, and any packing materials immediately after the dehumidifier is unpacked. Children should never use these items for play.

SAFETY PRECAUTIONS
DANGER! Avoid Serious Injury or Death
· This dehumidifier contains no user-serviceable parts. Always call an authorized Electrolux servicer for repairs.
· Do not insert or place fingers or objects into the air discharge area or back grille of the unit.
· Do not start or stop the dehumidifier by unplugging the power cord or turning off the power at the electrical box.
· Do not cut or damage the power cord. Do not pull on the power cord.
· If the power cord is damaged, it should only be replaced by an authorized Electrolux servicer.
· In the event of a malfunction (sparks, burning smell, etc.), immediately stop the operation, disconnect the power cord, and call an authorized Electrolux servicer.
· Do not operate the dehumidifier with wet hands. Do not drink any water from the dehumidifier.
· If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
· The appliance shall be installed in accordance with national wiring regulations.

4

IMPORTANT SAFETY INSTRUCTIONS

SAFETY PRECAUTIONS

WARNING

CAUTION! Avoid Injury or damage to the unit or other property · Do not direct airflow at fireplaces or other
heat related sources as this could cause flare ups. · Do not climb on or place objects on the unit. Do not hang objects off the unit. · Do not place containers with liquids on the unit. · Turn off the dehumidifier at the power source when it will not be used for an extended period of time. · Operate the unit with air filter in place. · Do not block or cover the intake grille, discharge area and outlet ports. · Ensure that any electrical/electronic equipment is one yard away from the unit. · Do not use or store flammable gases near the unit.
WARNING
Avoid fire hazard or electric shock. Do not use an extension cord or an adaptor plug. Do not remove any prong from the power cord.
Grounding type wall receptacle
Do not, under any circumstances, cut, remove, or bypass the grounding prong.
Power supply cord with 3-prong grounding plug

FOR FLAMMABLE REFRIGERANT · Servicing shall only be performed as
recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants. · DO NOT modify the length of the power cord or use an extension cord to power the unit. · DO NOT share a single outlet with other electrical appliances. Improper power supply can cause fire or electrical shock. · Please follow the instruction carefully to handle, install, clear, service the air conditioner to avoid any damage or hazard. · Flammable Refrigerant R32 is used within air conditioner. When maintaining or disposing the air conditioner, the refrigerant (R32) shall be recovered properly, shall not discharge to air directly. · Compliance with national gas regulations shall be observed. · Keep ventilation openings clear of obstruction. · The appliance shall be stored so as to prevent mechanical damage from occurring. · A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. · Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.
Examples for such working procedures are: · breaking into the refrigerating circuit; · opening of sealed components; · opening of ventilated enclosures.

IMPORTANT SAFETY INSTRUCTIONS

5

· No any open fire or device like switch which may generate spark/arcing shall be around air conditioner to avoid causing ignition of the flammable refrigerant used. Please follow the instruction carefully to store or maintain the air conditioner to prevent mechanical damage from occurring.
· Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
· The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance) and ignition sources or (for example: an operating electric heater) close to the appliance.
· Do not pierce or burn. · Be aware that the refrigerants may not
contain an odour.
1. Transport of equipment containing flammable refrigerants.
See transport regulations.
2. Marking of equipment using signs
See local regulations.
3. Disposal of equipment using flammable refrigerants
See national regulations.
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.
6. Information on servicing
a)Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior

to conducting work on the system.

b)Work procedure

Work shall be undertaken under a

controlled procedure so as to minimise

the risk of a flammable gas or vapour

being present while the work is being

performed.

c) General work area

All maintenance staff and others working

in the local area shall be instructed on

the nature of work being carried out.

Work in confined spaces shall be

avoided. The area around the workspace

shall be sectioned off. Ensure that the

conditions within the area have been

made safe by control of flammable

material.

d)Checking for presence of refrigerant

The area shall be checked with an

appropriate refrigerating detector prior

to and during work, to ensure the

technician is aware of potentially

flammable atmospheres. Ensure that the

leak detection equipment being used is

suitable for use with flammable

refrigerants,

i.e.

non-sparking,

adequately sealed or intrinsically safe.

e) Presence of fire extinguisher

If any hot work is to be conducted on the

refrigeration equipment or any

associated parts, appropriate fire

extinguishing equipment shall be

available to hand. Have a dry powder or

CO2 fire extinguisher adjacent to the

charging area.

f) No ignition sources

No person carrying out work in relation

to a refrigerating system which involves

exposing any pipe work that contains or

has contained flammable refrigerant

shall use any sources of ignition in such a

manner that it may lead to the risk of fire

or explosion. All possible ignition

sources, including cigarette smoking,

should be kept sufficiently far away from

the site of installation, repairing,

removing and disposal, during which

flammable refrigerant can possibly be

released to the surrounding space. Prior

to work taking place, the area around the

6

IMPORTANT SAFETY INSTRUCTIONS

equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.
g)Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
h) Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed; The ventilation machinery and outlets are operating adequately and are not obstructed; If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; Refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
i) Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical

supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include: That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; That there no live electrical components and wiring are exposed while charging, recovering or purging the system; That there is continuity of earth bonding.
7. Repairs to sealed components
a) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
b)Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
8. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without

IMPORTANT SAFETY INSTRUCTIONS

7

ensuring that this will not exceed the

permissible voltage and current

permitted for the equipment in use.

Intrinsically safe components are the only

types that can be worked on while live in

the presence of a flammable atmosphere.

The test apparatus shall be at the correct

rating. Replace components only with

parts specified by the manufacturer.

Other parts may result in the ignition of

refrigerant in the atmosphere from a leak.

9. Cabling

Check that cabling will not be subject to

wear, corrosion, excessive pressure,

vibration, sharp edges or any other

adverse environmental effects. The check

shall also take into account the effects of

aging or continual vibration from sources

such as compressors or fans.

10.Detection of flammable refrigerants

Under no circumstances shall potential

sources of ignition be used in the

searching for or detection of refrigerant

leaks. A halide torch (or any other

detector using a naked flame) shall not be

used.

The following leak detection methods are

deemed acceptable for systems

containing flammable refrigerants.

Electronic leak detectors shall be used to

detect flammable refrigerants, but the

sensitivity may not be adequate, or may

need

re-calibration.

(Detection

equipment shall be calibrated in a

refrigerant-free area). Ensure that the

detector is not a potential source of

ignition and is suitable for the refrigerant

used. Leak detection equipment shall be

set at a percentage of the LFL of the

refrigerant and shall be calibrated to the

refrigerant employed and the appropriate

percentage of gas (25 % maximum) is

confirmed. Leak detection fluids are

suitable for use with most refrigerants but

the use of detergents containing chlorine

shall be avoided as the chlorine may react

with the refrigerant and corrode the

copper pipe-work. If a leak is suspected,

all naked flames shall be removed/extinguished. If a leakage of

refrigerant is found which requires

brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Removal of refrigerant shall be according to Removal and evacuation.
11. Removal and evacuation
When breaking into the refrigerant circuit to make repairs ­ or for any other purpose­conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration. The following procedure shall be adhered to:
a) safely remove refrigerant following local and national regulations;
b)purge the circuit with inert gas; c) evacuate (optional for A2L); d)purge with inert gas (optional for A2L);
e) open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. For appliances containing flammable refrigerants, the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process might need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. For appliances containing flammable refrigerants, refrigerants purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum (optional for A2L). This process shall be repeated until no refrigerant is within the system (optional for A2L). When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available.

8

IMPORTANT SAFETY INSTRUCTIONS

12.Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. Cylinders shall be kept in an appropriate position according to the instructions. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
13. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b)Isolate system electrically.
c) Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protective equipment is available and being used correctly; The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders conform to the appropriate standards.
d)Pump down refrigerant system, if possible.

e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g)Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
14. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
15. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

IMPORTANT SAFETY INSTRUCTIONS

9

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
Do not mix refrigerants in recovery units and especially not in cylinders.

If compressors or compressor oils are to

be removed, ensure that they have been

evacuated to an acceptable level to make

certain that flammable refrigerant does

not remain within the lubricant. The

evacuation process shall be carried out

prior to returning the compressor to the

suppliers. Only electric heating to the

compressor body shall be employed to

accelerate this process. When oil is

drained from a system, it shall be carried

out safely.

Non-duct

connected

appliances

containing A2L refrigerants with the

supply and return air openings in the

conditioned space may have the body of

the appliance may be installed in open

areas such as false ceilings not being used

as return air plenums, as long as the

conditioned air does not directly

communicate with the air of the false

ceiling.

CAUTION: Risk of fire flammable materials
IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.

CAUTION

This symbol shows that the operation manual should be read carefully.

CAUTION

This symbol shows that information is available such as the operating manual or installation manual.

CAUTION

This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.

10 IMPORTANT SAFETY INSTRUCTIONS

Wiring Diagram

16020100001654 Notes: Display and Fan’s conntors must be match the actual indicates.

Notes: This symbol indicates the element is optional,

FAN CAPACITOR

BLUE
BROWN Y/G

PUMP
RED
BLACK(or BLUE)

OPTIONAL

CN2

CN1

DC POWER

BOARD

FAN

TOP M STEP
TOUCH/LIGHT PANEL
WIFI

CN5 DISPLAY BOARD
CN11 CN10
(or CN13)
CN12

WATER PIPE HUMI. SWITCHTEMP. SENSOR

WIFI

SWITCH SWITCH

RED BLACK(or BLUE)
WHITE

the actual

shape shall

prevail
BLUE

Y/G ION

RED

BLACK

COMP.

BLUE BLACK

~ M M
SC

Y/G

COMP.

OverLoad

CAPACITOR

Protector

WHITE(OR BLUE OR BLACK)(N)

P4 P9 P6
P10

CN4 CN3 CN2 CN1 CN10 CN7 CN6B
MAIN BOARD CN5
(or CN6/CN6A/CN6B/CN6C/CN10)

P7 P2 P1 CN14

P8

13

CN15 12

Y/G(or GREEN)
POWER

RED

BLACK(OR BROWN OR RED)(L)

3 POWER 1 1 BOARD 2
CN1 CN2

11 LOCATION & HOW IT WORKS

Location

How It Works

Selecting a Location
IMPORTANT:
1. Dehumidifier must be operated in an enclosed area to be most effective. Close all doors, windows, and other outside openings to the room. The effectiveness of the dehumidifier depends on the rate at which new moisture-laden air enters the room.
2. Place dehumidifier in a location that does not restrict the airflow of the air intake and air outlet.
3. A dehumidifier operating in a basement will have little or no effect in drying an adjacent enclosed storage area, such as a closet, unless there is adequate circulation of air in and out of the area. lt may be necessary to install a second dehumidifier in the enclosed area for satisfactory drying.
4. The dehumidifier must be installed on a level floor that will support it with a full bucket of water.
5. There should be a minimum of 12 inches clearance around the dehumidifier. The unit will produce heat while in operation and should not be operated in an enclosed small space like a closet.

When the unit is started, the fan begins to pull moisture-laden air across the dehumidifying coils. The coils condense or draw moisture from the air, and air flows through the air outlet louvers into the room as dry, warm air. Moisture removed from air is collected in a bucket on the front of the dehumidifier.
The unit is designed to operate between 41°F (5°C), and 89°F (32°C) and between 30%(RH) and 80%(RH). The unit will not work properly if the temperature is out of this temperature range, or the performance of the unit will fall greatly.
The “Compressor” circuit has an automatic 3 minute time delayed start if the unit is turned off and on quickly. This prevents overheating of the compressor and possible circuit breaker tripping. Make sure the tank is fitted correctly otherwise unit will not turn on.

Do not Block at least 24″

12″ 12″

12 DEHUMIDIFIER FEATURES & OPERATING INSTRUCTIONS

Dehumidifier Features

ELECTRONIC CONTROL Before you begin, thoroughly familiarize yourself with the control panel and all its functions (as shown below).

B

C

A

G

A Check Filter Reset Button B Bucket Full Indicator C Displays Humidity D Turns Unit On Or Off

F

E

D

E Sets Fan Speed F Adjusts Humidity G Sets Timer

Operating Instructions
Allow the unit to reach room temperature before operating. To begin operating the dehumidifier, follow these steps:

NOTE
Unit must be upright for one hour prior to operating.
1. Plug the power cord into a properly grounded 115 volt AC outlet.
NOTE

2. To turn the unit on, press the ON/OFF button. The unit will run in the factory setting of CONTINUOUS and high fan speed. In the CONTINUOUS mode, the unit will only display CO and not the room humidity. It is recommended you leave the unit running in the CONTINUOUS setting for the first three or four days until the sweating and dampness odors have stopped.

If the “BUCKET FULL” light is on, remove the bucket and re-install to reset the float switch.

13 OPERATING INSTRUCTIONS

3. After a few days when the Relative Humidity has declined, press the HUMIDITY ( ) or ( ) buttons to choose a value between 35% to 85%, so the room is kept at a comfortable humidity. Pressing the ( ) or ( ) buttons will change the humidity selection in 5% increments. 5 seconds after you have set the desired humidity, the readout will display the actual room humidity. If at any time you want to return to the CONTINUOUS Mode, pressing the HUMIDITY ( ) button will lower the Relative Humidity through 5% decrements until the display reads CO.
4. You can also use the FAN SPEED button to change the fan speed to Hi, Med or Lo. The indicator light will show the setting you have selected. A higher fan speed will result in quicker moisture removal.

6. The TIMER function enables you to either Delay Start or Delay Stop the unit in the choice from 0.5 hour to 24 hours. If the unit is running, then selecting Timer will turn the unit off in the hours that will be set (Delay Stop). If the unit is off, then selecting Timer will turn the unit on in the hours that will be set (Delay Start). TIMER setting: First press TIMER button, then adjust timer setting, by tapping or holding the ( ) or ( ) button to change the delay timer at 0.5 hour increments, up to 10 hours, then by 1 hour increments up to 24 hours. The control will count down the time remaining (8h, 7.5h, 7h etc.) until the unit either starts or stops. For the Delay Start, the fan speed and humidity maintained will be the same as previous setting. After TIMER setting finishes, pressing TIMER button again at any time will stop the TIMER function. The Delay Start/Stop Feature will work until the unit either starts or stops. Once that happens the above steps have to be repeated.

5. The Filter reset light will illuminate after 250 hours of operation. At this time refer to the care and cleaning section to remove and clean the filter. Once the filter has been cleaned and replaced, simply press the Filter reset button to extinguish the light.

NOTE
1. Before entering TIMER setting, make sure power is being supplied to the unit.
2. Before entering TIMER setting, make sure pressing HUMIDITY ( ) or ( ) button sets one desired room humidity first.

7. To shut the unit down, press the ON/OFF button.

Note: After a power outage, the unit will memorize the last setting and return the unit to the same setting once power is restored.

14 OPERATING INSTRUCTIONS

Fault Codes
1. If the display reads “AS” or “ES” , a sensor has failed. Contact your Authorized Frigidaire® Service Center.

b. Do not move the unit at this time otherwise water may spill on the floor.
c. Press sides of bucket gently to unclip the bucket from the unit.
d. Remove the bucket as shown in the photographs below and empty the bucket.

2. If the display reads “EC” , check the following operating conditions. Outlet voltage should be 115V±10% and the surrounding temperature should be with in the range of 41 °F to 89 °F. Unplug the unit and plug it in again under normal operating conditions. If the “EC” code persists, contact your Authorized Frigidaire® Service Center.

3. If the display reads “E4″, the communication between display PCB and main control PCB is faulty. Contact your Authorized Frigidaire® Service Center.

Removing Collected Water
1. Emptying the Bucket: a. When the bucket is full, the unit will shut
down and the BUCKET FULL indicator will illuminate.

15 OPERATING INSTRUCTIONS

WARNING
Discard water from bucket. Water is not potable and cannot be used for drinking.
e. Replace the empty bucket back into the unit and once seated correctly, the unit will start up again.
f. You should hear a click when the bucket is in the correct position.
If the bucket full light does not extinguish, check that the float is correctly snapped in place.

fig. 1
c. Insert the female threaded end of the hose onto the drain connector of the unit. (fig.2)

2. Continuous Drainage:
a. For continuous drainage operation, you will need a garden hose and a drain nearby to discharge the water into.
b. Unscrew the drain cap on the back side of the unit. (fig.1)

fig. 2
d. Screw the garden hose onto the threaded portion of the drain connector. (fig.3)

16 OPERATING INSTRUCTIONS & CARE AND CLEANING

NOTE

1. Check the seal between the hose and the drain connector. If there is a small leak then replace the hose gasket and re-tighten the hose.
2. It is recommended that a Dehumidifier Drain Hose – 1/2” (12.7 mm) or larger be used. Make sure there are no kinks or elevations in the hose.
3. When a hose is not attached to the drain connector, please ensure drain cap is screwed securely to the connector to prevent leakages.

fig. 3
e. Make sure the hose is secure so there are no leaks.
f. Direct the hose toward the drain, making sure that there are no kinks that will stop the water flowing.
g. Place the end of the hose into the drain. (fig.4)

Care and Cleaning
1. Filter Clean the filter every two weeks based on normal operating conditions. To remove the filter: a. Open the back grille.

b. Detach the filter from the back of the grille by pressing the tabs as shown below.
fig. 4
h. Select the desired humidity setting and fan speed on the unit for continuous draining to start.

17 STORAGE & NORMAL SOUNDS
Normal Sounds

2

3

Tabs
c. Wash the filter with clean water then dry. d. Re-install the filter.
2. Cabinet a. Dust cabinet with an oil-free cloth, or using
a damp cloth. b. Vacuum grill using brush attachment. 3. Water Bucket Clean the Water Bucket every two weeks based on normal operating conditions. a. Clean bucket with warm water and
detergent.
Storage
When unit is not in use, unplug and use the cord wrap shown for your model type.

1

4

1 Dripping Sound The sound of dripping water may be heard during the dehumidification cycle.
2 Sound of Rushing Air At the top of the unit, you may hear the sound of rushing air being moved by the fan.
3 Gurgle/Hiss “Gurgling or hissing” noise may be heard due to refrigerant passing through evaporator during normal operation.
4 High pitched Chatter Today’s high efficiency compressors may have a high pitched chatter during the dehumidification cycle.

18 BEFORE YOU CALL

Before calling for service, review this list. It may save you time and expense. This list includes common occurrences that are not the result of defective workmanship or materials in this appliance.

OCCURRENCE
Dehumidifier does not operate.
Dehumidifier runs too much.
Dehumidifier is operating but room is not dry enough.
Frost appears on coils behind the filter Fan noise.

SOLUTION
· Wall plug disconnected. Push plug firmly into wall outlet. · House fuse blown or circuit breaker tripped. Replace fuse with time delay
type or reset circuit breaker. · The dryness level you selected has been reached. Dehumidifier automatically
shuts off when selected amount of moisture has been removed from the air. If you want to remove more moisture, Select ‘CONTINUOUS’ by using the humidity button or knob. After the dehumidifier starts, reset the control to the desired setting. · Bucket not installed properly. See “Removing Collected Water”. · Water in the bucket has reached its preset level. Dehumidifier automatically turns off when this occurs. Empty bucket and return bucket to position. · Dehumidifier is not turned on. Turn unit on. · “BUCKET FULL” light is on. Remove bucket, empty water and re-install correctly.
· Windows or doors near dehumidifier are open to outdoors. Close all windows or doors to outside.
· Area to be dehumidified is too large. Check with your dealer to see if capacity is adequate.
· Air movement through dehumidifier is blocked. Grill may be dirty. Use brush attachment of vacuum cleaner to clean grill. See “Care and Cleaning”. Dehumidifier must be placed in a space that does not restrict air flowing into the rear coil or out of the front grill.
· Dehumidifier has been installed or restarted recently. The higher the moistuire in the room, the longer the dehumidifier will operate.
· Dehumidifier is in the CONTINUOUS mode and will remain on in this mode, use the humidity button or knob to set a RH% higher level.
· Humidity setting is too high. Press the HUMIDITY button or rotate knob to a lower setting or choose CONTINUOUS for maximum dryness.
· Dehumidifier has been installed or restarted recently. The higher the moisture in the room air, the longer it takes for the room air to become dry.
· Dehumidifier does not have sufficient clearance to operate. Air flow to the air outlet is blocked. See “Selecting a Location”.
· Room temperature is too low. Unit will not operate satisfactorily if the room temperature is below 41°F(5°C). See “Operating Conditions”.
· Refer to causes under DEHUMlDIFIER RUNS TOO MUCH.
· Dehumidifier has been turned on recently. This is normal due to refrigerant rushing through the coil. Frost will usually disappear within 60 minutes.
· Room Temperature is too low. All models will operate satisfactorily at temperatures greater than 41°F (5°C).
· Air is moving through the dehumidifier. This is a normal sound.

If These Solutions Fail, Call 1-800-944-9044(US)/1-800-265-8352(Canada) For Frigidaire® Service.

19 MAJOR APPLIANCE LIMITED WARRANTY

Your appliance is covered by a limited one-year warranty for functional repairs only. For one year from your original date of purchase, Electrolux will pay all costs for repairing or replacing any parts of this appliance that prove to be defective in materials or workmanship when such appliance is installed, used and maintained in accordance with the provided instructions. After one year from your original date of purchase, the consumer will be responsible for diagnostic, labor and parts costs as well as any removal, transportation and reinstallation expenses which are incurred during service on components.
Exclusions This warranty does not cover the following:
1. Products with original serial numbers that have been removed, altered or cannot be readily determined. 2. Product that has been transferred from its original owner to another party or removed outside the USA or Canada. 3. Rust on the interior or exterior of the unit. 4. Products purchased “as-is” are not covered by this warranty. 5. Food loss due to any refrigerator or freezer failures. 6. Products used in a commercial setting. 7. Service calls which do not involve malfunction or defects in materials or workmanship, or for appliances not in ordinary household use or used other than in accordance with the provided instructions. 8. Service calls to correct the installation of your appliance or to instruct you how to use your appliance. 9. Expenses for making the appliance accessible for servicing, such as removal of trim, cupboards, shelves, etc., which are not a part of the appliance when it is shipped from the factory. 10. Service calls to repair or replace appliance light bulbs, air filters, water filters, other consumables, or knobs, handles, or other cosmetic parts. 11. Surcharges including, but not limited to, any after hour, weekend, or holiday service calls, tolls, ferry trip charges, or mileage expense for service calls to remote areas, including the state of Alaska. 12. Damages to the finish of appliance or home incurred during installation, including but not limited to floors, cabinets, walls, etc. 13. Damages caused by: services performed by unauthorized service companies; use of parts other than genuine Electrolux parts or parts obtained from persons other than authorized service companies; or external causes such as abuse, misuse, inadequate power supply, accidents, fires, or acts of God.

DISCLAIMER OF IMPLIED WARRANTIES; LIMITATION OF REMEDIES

CUSTOMER’S SOLE AND EXCLUSIVE REMEDY UNDER THIS LIMITED WARRANTY SHALL BE PRODUCT REPAIR OR REPLACEMENT AS PROVIDED HEREIN. CLAIMS BASED ON IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE YEAR OR THE SHORTEST PERIOD ALLOWED BY LAW, BUT NOT LESS THAN ONE YEAR. ELECTROLUX SHALL NOT BE LIABLE FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES SUCH AS PROPERTY DAMAGE AND INCIDENTAL EXPENSES RESULTING FROM ANY BREACH OF THIS WRITTEN LIMITED WARRANTY OR ANY IMPLIED WARRANTY. SOME STATES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, OR LIMITATIONS ON THE DURATION OF IMPLIED WARRANTIES, SO THESE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. THIS WRITTEN WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE.

If You Need Keep your receipt, delivery slip, or some other appropriate payment record to establish the

Service

warranty period should service be required. If service is performed, it is in your best interest to

obtain and keep all receipts. Service under this warranty must be obtained by contacting

Electrolux at the addresses or phone numbers below.

This limited warranty only applies in the USA and Canada. In the USA, your appliance is warranted by

Electrolux Major Appliances North America, a division of Electrolux Home Products, Inc. In Canada, your

appliance is warranted by Electrolux Canada Corp. Electrolux authorizes no person to change or add to any

obligations under this warranty. Obligations for service and parts under this warranty must be performed by

Electrolux or an authorized service company. Product features or specifications as described or illustrated are

subject to change without notice.

USA 1.800.944.9044 Electrolux Major Appliances 10200 David Taylor Drive Charlotte, NC 28262

Canada
1.800.265.8352
Electrolux Canada Corp. 5855 Terry Fox Way
Mississauga, Ontario, Canada L5V 3E4

home welcome

Our home is your home. Visit us if you need help with any of these things:

owner support
accessories
service
registration
(See your registration card for more information.)
Frigidaire.com 1-800-944-9044 Frigidaire.ca 1-800-265-8352

16120300A28953 (July 2019)

Documents / Resources

FRIGIDAIRE FFAD2234W1 Low Humidity 22 Pint Energy Star Dehumidifier [pdf] User Manual
FFAD2234W1 Low Humidity 22 Pint Energy Star Dehumidifier, FFAD2234W1, Low Humidity 22 Pint Energy Star Dehumidifier, 22 Pint Energy Star Dehumidifier, Energy Star Dehumidifier, Star Dehumidifier, Dehumidifier

References

Leave a comment

Your email address will not be published. Required fields are marked *