V160 Base Axial Fan
User Manual 

VENTS V160 Base Axial Fan Base 

V160 Base Axial Fan

This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about the purpose, technical details,  operating principle, design, and installation of the Base unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety laws as well as construction norms and standards applicable in the territory of the country.
VENTS V160 Base Axial Fan - icon READ THE USER’S MANUAL CAREFULLY BEFORE PROCEEDING WITH INSTALLATION WORKS. COMPLIANCE WITH THE MANUAL REQUIREMENTS ENSURES RELIABLE OPERATION AND THE LONG SERVICE LIFE OF THE UNIT.
KEEP THE USER’S MANUAL AVAILABLE AS LONG AS YOU USE THE UNIT. YOU MAY NEED TO REREAD THE INFORMATION ON THE PRODUCT SERVICING.
VENTS V160 Base Axial Fan - icon FOLLOW THE USER’S MANUAL REQUIREMENTS TO ENSURE DURABLE AND TROUBLE-FREE OPERATION OF THE UNIT

All user’s manual requirements, as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards, must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are allowed for installation. The present user’s manual should be carefully read before beginning work.
Check the unit for any visible damage to the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades. While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jams and excessive noise.
Misuse of the unit and any unauthorized modifications are not allowed. Do not expose the unit to adverse atmospheric agents (rain, sun, etc.). Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials. Do not use the unit in a hazardous or explosive environment
containing spirits, gasoline, insecticides, etc. Do not close or block the intake or extract vents in order to ensure efficient airflow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics,  design, or configuration of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands. Never touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
Connection to the mains must be made through a disconnecting the device is integrated into the fixed wiring system in accordance with the wiring rules for the design of electrical units and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
VENTS V160 Base Axial Fan - icon1 THE PRODUCT MUST BE DISPOSED OF SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE OF THE UNIT AS UNSORTED DOMESTIC WASTE.
DELIVERY SET
Fan — 1 pc.
Screws and dowels— 4 pcs.
Plastic screwdriver (only for the models with a timer T) — 1 pc.
User’s manual — 1 pc.
Packing box — 1 pc.

BRIEF DESCRIPTION

The unit described herein is an axial fan for exhaust ventilation of small to medium-sized premises heated during winter. The fan design can also include a non-return valve to prevent backflow when the fan is switched off.
The fan is designed for connection to ø 100 and 125 mm air ducts.
The name and specifications are stated on the label on the unit used. The fan design is constantly being improved, thus some models may be slightly different from those described in this manual.
WARNING! The decorative front panel must be purchased separately.

OPERATION GUIDELINES

The fan is connected to 220-240 V, 50 Hz, and 220 V, 60 Hz or 12 V/50 Hz single-phase AC power mains depending on the model, and is designed for continuous operation without disconnection from the electric mains. Ingress protection rating against access to hazardous parts and water ingress is IP24.
The fan is rated for operation at ambient temperatures ranging from +1°C to +40 °C.
The unit is rated as a Class II (220-240 V, 50 Hz/220 V, 60 Hz) or Class III (12 V/50 Hz) electrical appliance.

DESIGNATION KEY

VENTS V160 Base Axial Fan - DESIGNATION KEY

Model D [mm] B [mm] N [mm] L [mm] H [mm] C [mm]
100 Base (-I) 99 140 88 101 103 56
125 Base (-I) 124 165 88 101 125 70
150 Base (-I) 149 180 106 121 136 136

VENTS V160 Base Axial Fan - fig

INSTALLATION AND SET-UP

Cut off the power supply and make sure The electricity has been turned off. Fix the fan with the screws. Connect the fan to power mains according to the wiring diagram. Mark the holes for fixing the fan and
the power cable.
VENTS V160 Base Axial Fan - fig1
Lead the power cable to the ventilation hole, drill the mounting holes and install the dowels. Fix the fan with the screws. Connect the fan to power mains according to the wiring diagram. Install the front panel by turning it clockwise.

Installation sequence for the decorative panel of the fan

To install the decorative panel on the fan, remove the plugs. Install the mounts and the decorative panel. Supply power to the fan.
VENTS V160 Base Axial Fan - fig3

The decorative panel is not included in the delivery set and is purchased separately for the fan
The unit with a protection rating against access to hazardous parts and water ingress IP24 is allowed to be installed in zones 2 and 3 according to the IEC 60364-7-701:2019.
VENTS V160 Base Axial Fan - fig4CONNECTION TO POWER MAINS
The fan is rated for connection to single-phase AC 220-240 V/50 (60) Hz power mains. Terminal designations on wiring diagrams:
L — line
LT — timer control line
S — ON\OFF switch
N — neutral
QF— automatic circuit breaker
Base(-I)
VENTS V160 Base Axial Fan - fig5Base(-I) VT/VTH
VENTS V160 Base Axial Fan - fig6
VENTS V160 Base Axial Fan - fig7DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD

ELECTRONICS OPERATION ALGORITHM

The fan with the timer T is started after the actuation of the external switch, e.g. the light switch. The control voltage is supplied
to the input terminal LT (ST). After the control voltage is off, the fan continues to operate within the set time period adjustable
from 2 to 30 minutes by the timer.
The V and VT models are turned on and off by an integrated pull-cord switch.
The fan with the timer and the humidity sensor H — the fan starts after the control voltage is supplied to the input terminal S or if indoor humidity level H exceeds the set point adjustable from ~60 % to ~90 %. After the control voltage is off or the humidity level has decreased, the fan will keep running within the time set by the timer ranging from 2 to 30 minutes. To set the maximum humidity setpoint 90 % set the potentiometer to the Hmax position.
To adjust the fan turn-on delay time, turn the control knob T  clockwise to increase and counter-clockwise to decrease the turn-on delay time respectively. To adjust the fan timer time, turn the control knob T clockwise to increase and counterclockwise to decrease the delay time respectively. To adjust the humidity set point turn the control knob H clockwise to increase and counter-clockwise to decrease the humidity sensor set point..
CAUTION! The timer circuit is live! Disconnect the fan from power mains prior to any adjustment operations. The fan delivery set includes a specially designed plastic screwdriver for fan settings adjustments (only for models equipped with a timer). Use it to change the turn-on and turn-off delay time and the humidity set point.
VENTS V160 Base Axial Fan - fig7 DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD

TECHNICAL MAINTENANCE

The fan maintenance periodicity is at least once per 6 months. Maintenance steps:

Disconnect the fan from the power supply and make sure electricity has been turned off. Remove the front panel. Clean the fan with a soft dry cloth or a brush.
VENTS V160 Base Axial Fan - fig8
ash the front panel under running water. Wipe the fan surfaces dry. Attach the decorative and front panel to the fan. Connect the power supply.
VENTS V160 Base Axial Fan - fig9

CAUTION! Do not allow water or liquid to come into contact with electric components!

TROUBLESHOOTING

Problem Possible reasons Troubleshooting
When the unit is connected to power
mains, the fan does not rotate and
does not respond to any controls.
No power supply. Make sure the power supply line
is connected correctly, otherwise
troubleshoot the connection error.
Internal connection fault. Contact the Seller.
Low airflow. The ventilation system is clogged. Clean the ventilation system.
Increased noise, and vibration. The impeller is clogged. Clean the impeller.
The fan is not secured well or is not
mounted properly.
Troubleshoot the installation error.
The ventilation system is clogged. Clean the ventilation system.

STORAGE AND TRANSPORTATION REGULATIONS

  • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
  • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
  • Follow the handling requirements applicable for the particular type of cargo.
  • The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
  • Avoid sharp blows, scratches, or rough handling during loading and unloading.
  • Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of the Electromagnetic Compatibility (EMC) Directive 2014/30/ EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following a test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 60 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to the elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:

  • routine technical maintenance
  • unit installation/dismantling
  • unit setup

To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the
payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact
the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:

  • User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
  • Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
  • User’s failure to ensure timely technical maintenance of the unit.
  • External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
  • Redesign or engineering changes to the unit.
  • Replacement and use of any assemblies, parts, and components not approved by the manufacturer.
  • Unit misuse.
  • Violation of the unit installation regulations by the user.
  • Violation of the unit control regulations by the user.
  • Unit connection to power mains with a voltage different from the one stated in the user’s manual.
  • Unit breakdown due to voltage surges in power mains.
  • Discretionary repair of the unit by the user.
  • Unit repair by any persons without the manufacturer’s authorization.
  • Expiration of the unit warranty period.
  • Violation of the unit transportation regulations by the user.
  • Violation of the unit storage regulations by the user.
  • Wrongful actions against the unit were committed by third parties.
  • Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
  • Missing seals if provided by the user’s manual.
  • Failure to submit the user’s manual with the unit purchase date stamp.
  • Missing payment paperwork certifying the unit purchase.

VENTS V160 Base Axial Fan - icon FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-FREE OPERATION OF THE UNIT.
VENTS V160 Base Axial Fan - icon USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT, AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

VENTS V160 Base Axial Fan - fig10

Certificate of acceptance
The fan is recognized as serviceable.
V160-1EN-07

Documents / Resources

VENTS V160 Base Axial Fan [pdf] User Manual
V160, Base Axial Fan, V160 Base Axial Fan

References

Leave a comment

Your email address will not be published. Required fields are marked *