BEHLER logoFX4D Fan Coils
Instruction Manual

NOTE: Read the entire instruction manual before starting the installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal  injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product.
Refer to the individual instructions packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings  or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies  hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property  damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
ELECTRICAL OPERATION HAZARD
Failure to maintain proper clearances could result in personal injury or death.
Before installing or servicing unit, always turn off all power to unit.
There may be more than 1 disconnect switch. Turn off accessory heater power if applicable. Lock out and tag switch with a suitable warning label.
CAUTION
CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts.
INTRODUCTION
Model FX4D is designed for flexibility and can be used for upflow, horizontal, or downflow (kit required) and manufactured and mobile home applications. These units are designed to meet the low air leak requirements currently in effect. Because of this, the units need special attention in the condensate pan and drain connection area and when brazing tubing. These units are designed specifically for Puronr refrigerant and must be used only with Puronr refrigerant air conditioners and heat pumps as shipped. These units are available for systems of 18,000 through 60,000 Btuh nominal cooling capacity.
Factory-authorized, field-installed electric heater packages are available in sizes 5 through 30kW. See Product Data literature for available accessory kits.
HEATER PACKAGES
This unit may or may not be equipped with an electric heater package.
For units not equipped with factory-installed heat, a factory-approved, field-installed, UL listed heater package is available from your equipment supplier. See unit rating plate for a list of factory-approved heaters. Heaters that are not factory approved could cause damage which would not be covered under the equipment warranty. If fan coil contains a factory-installed heater package, minimum circuit ampacity (MCA) and maximum fuse/breaker may be different than units with a same size field-installed accessory heater. The difference is not an error and is due to calculation differences per UL guidelines.

INSTALLATION

CHECK EQUIPMENT
Unpack unit and move to final location. Remove carton taking care not to damage unit. Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete. Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.
MOUNT UNIT
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living area, building codes may require a field-supplied secondary condensate pan to be installed under the entire unit. Some localities may allow as an alternative, the running of a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.
NOTE: Nuisance sweating may occur if the unit is installed in a high humidity environment with low airflow.
UPFLOW INSTALLATION
If return air is to be ducted through a floor, set unit on floor over opening and use 1/8 to 1/4-in (3 to 6 mm) thick fireproof resilient gasket between duct, unit, and floor.
Side return is a field option on slope coil models. Cut opening per dimensions. (See Fig. 1.) A field-supplied bottom closure is required.
DOWNFLOW INSTALLATION
In this application, field conversion of the evaporator is required using accessory downflow kit along with an accessory base kit. Use fireproof resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick, between duct, unit, and floor.
FX4D: Installation InstructionsBEHLER YOUNG FX4D Fan Coils - FigFig. 1 – Slope Coil Unit in Upflow Application
CAUTION
PRODUCT OR PROPERTY DAMAGE HAZARD
Failure to follow this warning caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and Slope-coil units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, and must be used for downflow. During conversion process, remove plastic cap covering vertical drains only and discard. Remove plug from overflow hole and discard. At completion of downflow installation, caulk around vertical pan fitting to door joint to retain low air leak performance of the unit.
NOTE: To convert units for downflow applications, refer to Installation Instructions supplied with kit for proper installation. For slope fan coils, use kit Part No. KFADC0201SLP. For A-coils, use kit Part No.
KFADC0401ACL. Use fireproof resilient gasket, 1/8 to 1/4-in (3 to 6 mm) thick, between duct, unit, and floor.
NOTE: Gasket kit number KFAHD0101SLP is also required for all downflow applications to maintain low air leak/low sweat performance.
NOTE: Modular units can be disassembled and components moved separately to installation area for reassembly. This process accommodates small scuttle holes and limiting entrances to installation sites. (See Fig. 2.)
HORIZONTAL INSTALLATION
Units must not be installed with access panels facing up or down. All other units are factory built for horizontal left installation. (See Fig. 3 and 4.) When suspending unit from ceiling, dimples in casing indicate suitable location of screws for mounting metal support straps. (See Fig. 3.)
For horizontal applications having high return static and humid return air, the Water Management Kit, KFAHC0125AAA, may need to be used to assist in water management.
Horizontal Right Conversion of Units with Slope Coils
NOTE: Gasket kit number KFAHD0101SLP is required for horizontal slope coil conversion to maintain low air leak/low sweat performance.BEHLER YOUNG FX4D Fan Coils - Fig1Fig. 2 – Modular Unit Assembly
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
For optimum condensate drainage performance in horizontal installations, unit should be leveled along its length and width.

  1. Remove blower and coil access panels and fitting panel. (See Fig. 5.)
  2. Remove coil mounting screw securing coil assembly to right side casing flange.
  3. Remove coil assembly.
  4. Lay fan coil on its right side and reinstall coil assembly with condensate pan down (See Fig. 5.)
  5. Attach coil to casing flange using previously removed coil mounting screw.
  6. Make sure pan cap in fitting door is properly seated on fitting door to retain low air leak rating of the unit.
  7. Add gaskets from kit – KFAHD.
  8. Align holes with tubing connections and condensate pan connections. Reinstall access panels and fitting panel.
    BEHLER YOUNG FX4D Fan Coils - Fig2Fig. 3 – Slope Coil in Horizontal Left Application (Factory Configuration) BEHLER YOUNG FX4D Fan Coils - Fig3Fig. 4 – A-Coil in Horizontal Left Application (Factory Configuration)
  9. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install grommets after brazing.

Horizontal Right Conversion of Units with A-Coils

  1. Remove blower and coil access panels. (See Fig. 6.)
  2. Remove metal clip securing fitting panel to condensate pan.
    Remove fitting panel.
  3. Remove 2 snap-in clips securing A-coil in unit.
  4. Slide coil and pan assembly out of unit.
  5. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit. (See Fig. 7.)
  6. Convert air seal assembly for horizontal right.
    a. Remove air seal assembly from coil by removing 4 screws. (See Fig. 6)
    b. Remove air splitter (B) from coil seal assembly by removing 3 screws. (See Fig. 6 inset)
    c. Remove filler plate (A) and install air splitter (B) in place of filler plate.
    d. Install filler plate (A) as shown in horizontal right application.
    e. Remove condensate troughs (C) and install on opposite tube sheets.
    f. Install hose onto plastic spout.
  7. Install horizontal pan on right side of coil assembly.
  8. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails.
  9. Reinstall 2 snap-in clips to correctly position and secure coil assembly in unit. Be sure clip with large offset is used on right side of unit to secure horizontal pan.
  10. Remove two oval fitting caps from left side of the coil, access panel, and fitting panel.
  11. Remove insulation knockouts on right side of coil access panel.
  12. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel.
  13. Install condensate pan fitting caps (from Step 10) in right side of coil door making sure that cap snaps and seats cleanly on back side of the coil door. Make sure no insulation interferes with seating of cap.
  14. Reinstall access and fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to reinstall metal clip between fitting panel and vertical condensate pan.
  15. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.

BEHLER YOUNG FX4D Fan Coils - Fig4Fig. 6 – Conversion for Horizontal Right Applications – A-CoilBEHLER YOUNG FX4D Fan Coils - Fig5Fig. 7 – Drain Pan Support Bracket

MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS

  1. Fan coil unit must be secured to the structure using field-supplied hardware.
  2. Allow a minimum of 24 inches (610mm) clearance from access panels.
  3. Recommended method of securing for typical applications:
    a. If fan coil is away from wall, attach pipe strap to top of fan coil using No. 10 self tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16” lag screws. Typically both sides of the fan coil.
    b. If fan coil is against wall, secure fan coil to wall stud using 1/8” (3mm) wide right-angle brackets. Attach brackets to fan coil using No. 10 self tapping screws and to wall stud using 5/16” lag screws (refer to Fig. 8).

AIR DUCTS

Connect supply-air duct over the outside of 3/4-in (19 mm) flanges provided on supply-air opening. Secure duct to flange, using proper fasteners for type of duct used, and seal duct-to-unit joint. If return-air flanges are required, install factory-authorized accessory kit.
Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat-resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.
Units equipped with 20-30kW electric heaters require a 1-in (25 mm) clearance to combustible materials for the first 36-in (914 mm) of supply duct.BEHLER YOUNG FX4D Fan Coils - Fig6

DUCT WORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 feet of main duct before first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous duct work may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous duct work shall comply with National Fire Protection Association as tested by UL Standard 181 for Class 1 air ducts.
ELECTRICAL CONNECTIONS
All products from the factory protect the low voltage circuit with a 5 amp automotive type fuse inline on the wire harness. Speed selections are made at the fan motor by selecting taps 1, 2 or 3 with the blue wire (see section E). The motor is pre-programmed with the time delay circuit on some of the speed taps ( see section E for clarification).
When a factory-approved accessory control package has been installed, check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation. If a different control package is required, see unit rating plate.
Before proceeding with electrical connections, make certain that supply voltage, frequency, phase, and ampacity are as specified on the unit rating plate. See unit wiring label for proper field high- and low-voltage wiring. Make all electrical connections in accordance with the NEC and any local codes or ordinances that may apply. Use copper wire only.
WARNING
ELECTRICAL SHOCK OR UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death, and/or unit damage.
If a disconnect switch is to be mounted on unit, select a location where drill and fasteners will not contact electrical or refrigeration components.
The unit must have a separate branch electric circuit with a field-supplied disconnect switch located within sight from, and readily accessible from, the unit.
On units with a factory-installed disconnect with pull-out removed, service and maintenance can be safely performed on only the load side of the control package.
WARNING
ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
Field wires on the line side of the disconnect found in the fan coil unit remain live, even when the pull-out is removed. Service and maintenance to incoming wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off. Lock out and tag switch with a suitable warning label.
LINE VOLTAGE CONNECTIONS
If unit contains an accessory electric heater, remove and discard power plug from fan coil and connect male plug from heater to female plug from unit wiring harness. (See Electric Heater Installation Instructions.)
For units without electric heat:

  1. Connect 208/230V power leads from field disconnect to yellow and black stripped leads.
  2. Connect ground wire to unit ground lug.

NOTE: Units installed without electric heat should have a field-supplied sheet metal block-off plate covering the heater opening. This will reduce air leakage and formation of exterior condensation.
MANUFACTURED HOUSING
In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40_F (4_C), except for a heat pump defrost cycle. Refer to Fig. 14 for typical low voltage wiring with outdoor thermostat.
TRANSFORMER INFORMATION
Transformer is factory wired for 230V operation. For 208V applications, disconnect the black wire from the 230V terminal on transformer and connect it to the 208V terminal (refer to Fig. 15).

BEHLER YOUNG FX4D Fan Coils - Fig7 BEHLER YOUNG FX4D Fan Coils - Fig8
BEHLER YOUNG FX4D Fan Coils - Fig9 BEHLER YOUNG FX4D Fan Coils - Fig10

HEATER STAGING

The controls are factory circuited for single-stage operation. For 2-stage operation, use outdoor thermostat kit Part No. KHAOT0301FST, and for 3-stage use both kits Part No. KHAOT0201SEC and KHAOT0301FST.
When 2 stages are desired, cut W3 at the W2 wire nut, strip and reconnect per the thermostat kit instruction. (See Fig. 13.) When 3 stages are desired, cut the W2 wire nut off and discard. Strip W2, W3, and E and reconnect per thermostat kit instructions. (See Fig. 13.)
NOTE: When 3 stages are used or anytime the E terminal is not tied to W2, the emergency heat relay, part of outdoor kit Part No.
KHAOT0201SEC must be used.

BEHLER YOUNG FX4D Fan Coils - Fig11 BEHLER YOUNG FX4D Fan Coils - Fig12

BEHLER YOUNG FX4D Fan Coils - Fig13

CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
If W2, W3, and E on any 3 stage heater (18, 20, 24, or 30kW) are individually connected – as with outdoor thermostats or any other situation – emergency heat relay must be used. This relay is in kit Part No. KHOT0201SEC and is used normally with kit Part No.
KHAOT0301FST.

GROUND CONNECTIONS

NOTE: Use UL listed conduit and conduit connectors for connecting supply wire(s) to unit to obtain proper grounding. Grounding may also be accomplished by using grounding lugs provided in control box.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground could result in personal injury and/or death.
According to NEC, NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must be used.
MINIMUM CFM AND MOTOR SPEED SELECTION
The fan speed selection is done at the motor connector. Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure that the fan speed selected is not lower than the minimum fan speed indicated.
Table 1 – Motor Speed Selection

Tap 1 Low 90 sec off delay
Tap 2 Medium 90 sec off delay
Tap 3 High 90 sec off delay
Tap 4 Electric heat  † 0 sec off delay
Tap 5 Max  ‡ 0 sec off delay

† electric heat airflow is same CFM as Tap 3, except 0 sec off delay
‡ high static applications, see airflow tables for max airflow
To change motor speeds disconnect the BLUE fan lead from motor connector terminal #2 (factory default position) and move to desired speed-tap; 1, 2, 3, or 5.
Speed-taps 1, 2, and 3 have a 90 second blower off time delay pre-programmed into the motor. Speed-tap 4 is used for electric heat only (with 0 second blower time delay)  and the WHITE wire should remain on tap 4. Speed-tap 5 is used for high static applications, but has a 0 second blower time delay pre-programmed into the motor. See Airflow Performance tables for actual CFM. Also, see Fig. 16 for motor speed selection location.
NOTE: In low static applications, lower motor speed tap should be used to reduce possibility of water being blown off coil.
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are being brazed to the unit connections to prevent damage to the unit surface and condensate pan fitting caps.
REFRIGERANT TUBING CONNECTION AND EVACUATION
Use accessory tubing package or field-supplied tubing of refrigerant grade. Suction tube must be insulated. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow-control device. ALWAYS evacuate the coil and field-supplied tubing to 500 microns before opening outdoor unit service valves.
Units have sweat suction and liquid tube connections. Make suction tube connection first.

  1. Cut tubing to correct length.
  2. Insert tube into sweat connection on unit until it bottoms.
  3. Braze connection using silver bearing or non-silver bearing brazing materials. Do not use solder (materials which melt below 800_F / 427_C). Consult local code  equirements.
    BEHLER YOUNG FX4D Fan Coils - Fig14
  4. Evacuate coil and tubing system to 500 microns using deep vacuum method.

CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property damage.
Wrap a wet cloth around rear of fitting to prevent damage to TXV and factory-made joints.
REFRIGERANT FLOW-CONTROL DEVICE
The FX4D is equipped with PuronR refrigerant TXV. Use outdoor units designed for PuronR refrigerant only.
CAUTION
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
If using a TXV in conjunction with a single-phase reciprocating compressor, a compressor start capacitor and relay are required. Consult outdoor unit pre-sale literature for start assist kit part number.

CONDENSATE DRAINS

To connect drains, the cap openings must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the disk. Clean the edge of the opening if necessary and install the condensate line. Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit.
Units are equipped with primary and secondary 3/4-in. FPT drain connections. For proper condensate line installations see Fig. 1, 3, 4, 5 and 6. To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly-sized condensate traps. (See Fig. 17 and 19.) Factory-approved condensate traps are available. It is recommended that PVC fittings be used on the plastic condensate pan. Finger-tighten plus 1-1/2 turns. Do not over- tighten. Use pipe dope.
NOTE: When connecting condensate drain lines, avoid blocking filter access panel, thus preventing filter removal. After connection, prime both primary and secondary condensate traps.
WARNING
PRODUCT OR PROPERTY DAMAGE HAZARD
Failure to follow this warning caution may result in product or property damage.
The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and Slope-coil units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, and must be used for downflow. During conversion process, remove plastic cap covering vertical drains only and discard. Remove plug from overflow hole and discard. At completion of downflow installation, caulk around vertical pan fitting to door joint to retain low air leak performance of the unit.

BEHLER YOUNG FX4D Fan Coils - Fig15 BEHLER YOUNG FX4D Fan Coils - Fig16

BEHLER YOUNG FX4D Fan Coils - Fig17NOTE: If unit is located in or above a living space where damage may result from condensate overflow, a field-supplied, external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan. Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the use of a separate 3/4-in (19 mm) condensate line (with appropriate trap) to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires servicing or water damage will occur.
Install traps in the condensate lines as close to the coil as possible. (See Fig. 19.) Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living area. Condensate drain lines should be pitched  downward at a minimum slope of 1-in (25 mm) for every 10-ft (3 m) of length. Consult local codes for additional restrictions or precautions.
CAUTION
PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.
Use only full size P-traps in the condensate line (refer to Fig. 17).
Shallow running traps are inadequate and DO NOT allow proper condensate drainage (refer to Fig. 18).
ACCESSORIES
HUMIDIFIER
Connect humidifier and humidistat to fan coil unit as shown in Fig. 20 and Fig. 21. The cooling lockout relay is optional.

SEQUENCE OF OPERATION

CONTINOUS FAN
Thermostat closes R to G. G energizes fan relay on PCB which completes circuit to indoor blower motor. When G is de-energized, there is a 90 second delay before relay  opens.
NOTE: Speed taps 1, 2 and 3 have a 90 second blower off delay. Speed taps 4 and 5 have 0 second blower off delay.
COOLING MODE
Thermostat energizes R to G, R to Y, and R to O (heat pump only). Genergizes fan relay on PCB which completes circuit to indoor blower motor. When G is de-energized, there is a 90 second delay before fan relay opens.
NOTE: Speed taps 1, 2 and 3 have a 90 second blower off delay. Speed taps 4 and 5 have 0 second blower off delay.
HEAT PUMP HEATING WITH AUXILIARY ELECTRIC HEAT
Thermostat energizes R to G, R to Y, and R to W. G energizes fan relay on PCB which completes circuit to indoor blower motor. W energizes electric heat relay(s) which completes circuit to heater element(s). When W is de-energized, electric heat relay(s) open, turning off heater elements. When G is de-energized there is a 90 second delay before fan relay opens.
NOTE: Speed taps 1, 2 and 3 have a 90 second blower off delay. Speed taps 4 and 5 have 0 second blower off delay.
ELECTRIC HEAT OR EMERGENCY HEAT MODE
Thermostat closes R to W. W energizes electric heat relay(s) which completes circuit to heater element(s). Blower motor is energized through normally closed contacts on fan relay. When W is de-energized, electric heat relay(s) opens.BEHLER YOUNG FX4D Fan Coils - Fig18

START-UP PROCEDURES

Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit performance and/or product damage.
Never operate unit without a filter. Factory authorized filter kits may be used when locating the filter inside the unit. For those applications where access to an internal filter is impractical, a field-supplied filter must be installed in the return air duct system.

BEHLER YOUNG FX4D Fan Coils - Fig19

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer as to the proper frequency of maintenance contract.
The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these, contact your dealer for maintenance. The only consumer service recommended or required is filter replacement or cleaning on a monthly basis.
Table 2 – Air Delivery Performance Correction Component Pressure Drop (in. wc) at Indicated Airflow (Dry to Wet Coil)

FX Size

CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900

2000

019 0.034 0.049 0.063
025 0.016 0.027 0.038 0.049 0.059
031 0.049 0.059 0.070 0.080
037 0.055 0.064 0.073 0.081
043 0.049 0.056 0.063 0.070
049 0.038 0.043 0.049 0.054 0.059
061 0.027 0.031 0.035 0.039 0.043

Table 3 – Factory-Installed Filter Static Pressure Drop (in. wc)

FX SIZE

CFM
400 600 800 1000 1200 1400 1600 1800

2000

019 0.020 0.044 0.075
025 – 031 0.022 0.048 0.072 0.100
037-049 0.051 0.070 0.092 0.120 0.152
061 0.086 0.105 0.130

Table 4 – Electric Heater Static Pressure Drop (in. wc)

FX
019 – 037

FX
043 – 061

HEATER ELEMENTS

kW EXTERNAL STATIC PRESSURE CORRECTION HEATER ELEMENTS kW EXTERNAL STATIC PRESSURE CORRECTION
0 0 +.02 0 0

+.04

1

3, 5 +.01 2 8, 10 +.02
2 8, 10 0 3 9, 15

0

3

9, 15 –.02 4 20 –.02
4 20 –.04 6 18, 24, 30

–.10

Table 5 – Airflow Performance (CFM) in Cooling Mode

Model & Size

Blower Speed EXTERNAL STATIC (in. wc)
0.10 0.20 0.30 0.40 0.50

0.60

FX4D 019 Tap 5 776 745 696 660 609 572
Tap 4 683 644 589 548 494 461
Tap 3 683 644 589 548 494 461
Tap 2 631 563 500 443 409 361
Tap 1 625 524 457 417 367 319
FX4D 025 Tap 5 956 920 891 851 816 780
Tap 4 825 795 757 722 674 634
Tap 3 825 795 757 722 674 634
Tap 2 726 695 635 598 543 509
Tap 1 631 563 500 443 409 361
FX4D 031 Tap 5 1189 1151 1104 1050 1003 959
Tap 4 1041 998 944 886 837 772
Tap 3 1041 998 944 886 837 772
Tap 2 924 876 817 752 704 660
Tap 1 779 693 628 571 526 476
FX4D 037 Tap 5 1363 1332 1294 1253 1207 1157
Tap 4 1237 1206 1160 1121 1070 1013
Tap 3 1237 1206 1160 1121 1070 1013
Tap 2 1095 1058 1007 951 888 824
Tap 1 1014 885 773 673 609 549
FX4D 043 Tap 5 1519 1490 1454 1419 1379 1332
Tap 4 1437 1403 1366 1333 1294 1245
Tap 3 1437 1403 1366 1333 1294 1245
Tap 2 1257 1226 1191 1141 1090 1033
Tap 1 1237 1206 1160 1121 1070 1013
FX4D 049 Tap 5 1757 1725 1693 1653 1614 1576
Tap 4 1664 1626 1593 1552 1517 1477
Tap 3 1664 1626 1593 1552 1517 1477
Tap 2 1459 1420 1379 1336 1298 1259
Tap 1 1301 1241 1195 1150 1102 1039
FX4D 061 Tap 5 2030 1995 1961 1927 1888 1842
Tap 4 1811 1775 1740 1703 1664 1613
Tap 3 1811 1775 1740 1703 1664 1613
Tap 2 1665 1632 1593 1556 1507 1453
Tap 1 1462 1418 1371 1327 1278 1228

– Shading – Airflow outside 450 cfm/ton.
NOTES:

  1. Airflow based upon dry coil at 230v with factory approved filter and electric heater (2 element heater sizes 019 through 037, 3 element heater sizes 043 through 061).
  2. Airflow at 208 volts is approximately the same as 230 volts because the multi-tap ECM motor is a constant torque motor. The torque doesn’t drop off at the speeds the motor operates.
  3. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
    Return static pressure must be less than 0.40 in. wc.
    Horizontal applications of 043 – 061 sizes must have supply static greater than 0.20 in. wc.
  4. Airflow above 400 cfm/ton on 049 – 061 size could result in condensate blowing off coil or splashing out of drain pan.

© 2022 Carrier. All rights reserved.
A Carrier Company
Edition Date: 10/22
Catalog No: IM-FX4D-04
Replaces: IM-FX4D-03
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Documents / Resources

BEHLER-YOUNG FX4D Fan Coils [pdf] Instruction Manual
FX4D Fan Coils, FX4D, Fan Coils, Coils

References

Leave a comment

Your email address will not be published. Required fields are marked *