PIONEER logoDUCTLESS MINI SPLIT SYSTEM AIR CONDITIONER / HEAT PUMP
WYF-25 Inverter Series

For 9,000-24,000 BTU/hr Systems

WYF-HYP-IMUM-2023 Hyperformance Mini Split Heat Pump

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat PumpInstallation & User’s Manual

IMPORTANT NOTICE:
Please read this manual carefully before installing or operating your new air conditioning system.
Be sure to save this manual for future reference. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 1

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Assembly 1 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Assembly 2

Safety Precautions

Read and Understand All Safety Precautions Prior to Installation
Improper installation due to negligence of instructions may result in serious damage or injury.
The magnitude of potential damages or injuries is classified as either a WARNING or a CAUTION.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2WARNING This symbol indicates that ignoring the related instructions may cause death, or serious injury.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 3CAUTION This symbol indicates that ignoring the related instructions may cause moderate injury to nearby persons, and/or damage to your appliance or other property.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 4DANGER This symbol indicates that you must never perform the action shown.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 WARNING
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 5 Do not power the system using an extension cable or with wiring smaller than the specified gauge.
Do not share the electrical circuit with other appliances. Improper or insufficient power supply can cause undesirable operation, fire, or electrical shock.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 5 When connecting refrigerant piping, do not let any substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can also cause explosion and injury, as well as permament equipment failure. Remember: No dust, humidity or air is allowed to enter.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 5 Do not allow children to play with or around the air conditioner. Children near the unit must be supervised at all times.

  1. Installation must be performed by a licensed and trained technician. Defective installation can cause water leakage, electrical shock, or fire. The usage of proper tools is a requirement.
  2. Installation must be performed according to the installation instructions. Improper installation can cause water leakage, undesired performance, electrical shock, or fire.
    (In North America, installation must be performed in accordance with the requirements of NEC and CEC, by authorized personnel only.)
  3. Contact a qualified and licensed HVAC technician for any repairs or maintenance of this unit.
  4. Only use the included accessories, parts, and specified items for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause total unit failure.
  5. Install the unit on top of a firm structure that can fully support its weight. If the chosen location cannot support the unit’s weight, or the installation is not done properly, the unit may fall and cause serious injury and damage.
  6. For all electrical work, follow all local and national wiring standards, regulations, and especially this Installation Manual. You must use an independent circuit and a dedicated breaker to supply power.
    Do not connect other appliances to the same circuit. Insufficient electrical capacity or defects in electrical work can cause electrical shock or fire.
  7. For all electrical work, use the specified cables. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminals. Improper electrical connections can overheat and cause fire, and may also cause shock.
  8. All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock.
  9. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended. This is intended as a general comfort cooling system.
  10. If the supply cord is damaged, it must be replaced by a certified service agent or similarly qualified technicians, in order to avoid a hazard.
  11. This appliance can be used by children aged 8 years and above, as well as persons with reduced physical, sensory, or mental capabilities, or lack of experience or knowledge, if they have been given supervision or instruction concerning use of the appliance in a safe way, and understand the hazards involved. Children shall not play with or near the appliance. Cleaning and user maintenance shall not be done or attempted by children or untrained personnel without proper supervision.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 3 CAUTION
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 5 For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 5 Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause fire.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 5 Do not operate your air conditioner in a highly humid space, such as bathrooms or laundry rooms. Exposure to high humidity or water can cause electrical components to short circuit.

  1. The product must be properly grounded at the time of installation, else electrical shock may occur.
  2. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.

Note about Fluorinated Gasses

  1. This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.
  2. Installation, service, maintenance, and repair of this unit must be performed by a certified HVAC technician.
  3. Product uninstallation and recycling must be performed by a certified HVAC technician.
  4. If the system has a leak-detection feature installed, it must be checked for leaks at least every 12 months.
  5. When the unit is being checked for leaks, proper logging and record-keeping of all checks is strongly recommended.

System Components

High Wall-Mounted Air Conditioner
The system is made up of two or more units connected together via insulated copper pipes and an electrical communication cable. The indoor unit is mounted onto one of the walls in the room that is to be conditioned. The outdoor unit is installed on the ground outside or on the wall of the dwelling using suitable mounting brackets. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - INDOOR UNIT

No. Description
1 Front Panel
2 Air Filters
3 Signal Receiver
4 LED Display
5 Indoor Unit Rating Label
6 Emergency (Manual) Button
7 Terminal Block Cover
8 Wi-Fi Module (Optional)
9 Deflectors
10 Airflow Direction Louver

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - OUTDOOR UNIT

No. Description
11 Air Outlet Grille
12 Outdoor Unit Nameplate
13 Terminal Block Cover
14 Liquid Line Valve
15 Gas (Suction) Line Valve

Note: Serial Numbers are sometimes located behind the electronic control box cover cap of either unit.
Note: The illustrations above are only intended to be a simple diagram of the appliance, and may not fully correspond to the actual appearance of the system. Technical data is printed on the system’s labels.

Included Accessories

Accessories and Components:
The air conditioning system comes with the following accessories (the asterisk items are sold separately). Use all of the installation parts/accessories to install the air conditioner. Improper installation may cause the equipment to fail, or result in water leakage, electrical shock, or fire.

Name Appearance
1x Installation and Owner’s Manual PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 1
1x Warranty Card PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 2
1x Communication/Signal Cable* PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 3
1x Insulated Copper Pipe Set* PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 4
1x Remote Controller PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 5
1x Remote Controller Holder PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 6
2x Remote Controller Batteries PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 7
1x Indoor Unit Mounting Plate (Pre-attached to air handler rear) PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 8
1x Set of Mounting Plate Screws PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 9
1x Plastic Drain Joint Plug PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 10
1x Condensate Drain Hose* PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 11
1x Wrapping Tape* PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 12
1x Wall-Hole Packing Sealant* PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 13
1x Wall Sleeve* PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Appearance 14

*Items with an asterisk may be sold separately and are sometimes supplied by the installer. Therefore some items may differ in appearance, shape, or length, depending on what was chosen to be used for the installation. Different scenarios, be sure to select the components that are suitable for your application.

Connecting Pipe Diameters
BTU Capacity Gas Line Liquid Line
9000 3/8″ 1/4”
12000
18000 1/2″ 1/4″
24000 5/8″ 3/8″

Indoor Unit Overview

Front Panel DisplayPIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Unit Overview

No. Meaning Symbol Description
1 WI-FI PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 6 Indicates that the unit is currently Wi-Fi Enabled
2 SLEEP PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 7 Indicates that the system is currently in SLEEP mode
3 TIMER PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 8 Indicates that the TIMER function has been set
4 Receptor PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 9 Receives incoming signals from the remote controller
5 Temp. Display PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 10 Displays the current set temperature or any error codes

warning 2 The shape and position of switches and indicators may vary according to the model, however the functions remain the same.
There may be variances between the amount of digits that are shown on the remote (3) vs. the amount on the indoor unit (2).

Emergency Manual Button And Auto-Restart Function
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 11 The emergency button is located above the terminal block cover of the unit underneath the front panel.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - emergency button

Emergency Manual Button
If the remote controller fails to operate the system, proceed as follows:

  • Open and lift the front panel up at an angle to gain access to the emergency button.
  • Press the manual button once to start the unit in COOL mode.
  • Press the button again within 3 seconds to start the unit in HEAT mode.
  • Press a 3rd time within 5 seconds to turn off the unit.

Auto-Restart Feature
This appliance is programmed with an auto-restart function.
In case of sudden power failure, the control module will remember the settings configured before power loss.
When power is restored, the unit will restart automatically, and will be set to the previous settings, which were preserved with this memory function.

Operating Instructions

Remote Buttons Walkthrough

Button Description
MODE Selects the mode of operation (Smart Auto, Cool, Dry, Fan, and Heat modes)
ON/OFF Turns the air conditioner on or off
FAN Configures the fan speed (Auto, High, Med, and Low)
TURBO Activates/deactivates the TURBO feature, which allows the system to reach set temperatures quicker
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 12 Activates the left-right louver motor
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 13 Activates the up-down louver motor
TEMP — Decreases set temperature, set timing, or navigates the functional menu
TEMP + Increases set temperature, set timing, or navigates the functional menu
MUTE Puts the system into silent mode
SLEEP Toggles the system’s Sleep Mode
LIGHT Turns the LED display on or off
TIMER ON Configures the automatic on times
TIMER OFF Configures the automatic off times
CLOCK Used to set the current time
ECO Activates/deactivates the ECO feature
I FEEL Activates the system’s Follow Me mode

*Any blank buttons have no function and are reserved for future use.
warning 2 The display and some features of the remote control may vary according to the model of the system.
warning 2 The shape and positions of the buttons and indicators may vary according to the model of the system, but the features and functionality would remain the same.
warning 2 The unit will confirm the successful reception of each button command with a beep.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Remote Buttons Walkthrough

Remote Controller LED Screen and Icons OverviewPIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icons Overview

No. Icon Description No. Icon Description
1 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 1 Economy Mode Indicator 11 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 11 Fan Only Mode
2 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 2 Turbo Mode Indicator 12 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 12 Smart Auto Mode
3 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 3 I FEEL/Follow Me Indicator 13 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 13 Dry Mode
4 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 4 Nanoe Indicator (optional) 14 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 14 Left-Right Louver Swing
5 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 5 8°C/46°F Vacation Mode 15 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 15 Up-Down Louver Swing
6 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 6 Mute Mode 16 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 16 Display Set or Current Time
7 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 7 Signal Transmission 17 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 17 Sleep Mode (1, 2, 3, 4)
8 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 8 Child Lock Activated 18 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 18 Fan Speed Configuration
9 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 9 Temperature Display 19 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 19 Heat Mode
10 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 10 Unit of Temperature (°F/°C) 20 PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 20 Cool Mode

NOTE ON ILLUSTRATIONS
The illustrations in this manual are strictly for explanatory purposes. The actual display and some functions of the remote controller may vary according to the model purchased.

Replacement of Batteries
Remove the battery cover from the rear of the remote controller, by sliding it downward in the direction of the arrow as depicted below. Install batteries according to the depicted directions (+ and -) as shown on the remote controlller. The cover then slides back into place.
warning 2 Use 2x AAA batteries. Do not use re-chargeable batteries. Replace old batteries with new ones of the same type when the display is no longer legible. Do not dispose of batteries as unsorted municipal waste. Disposal of such waste separately for special treatment is necessary. If the system will not be used for a long time, remove batteries to prevent leakage. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Replacement of Batteries

Note
Please remove batteries to avoid leakage damage when not being used for a long time.

Storage and Tips for Using the Remote Controller
The remote controller may be stored mounted on a wall using a suitable holder.
Note: The remote controller holder may be an optional part sold separately.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Remote Controller

Operating the Remote Controller Sucessfully and Safely

  • Ensure no objects come between the remote controller and signal receptor of indoor unit. The signal transmission range is 25 ft.
  • Keep the remote at least 3 ft away from televisions and other electrical appliances that emit or accept signals.
  • Always direct the remote controller toward the air conditioner.
  • Don’t leave the remote exposed to sunrays.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Signal receptor

Regarding the Airflow of the Indoor Unit
The air that is pulled in by the fan (the “return air”) enters the grille and is passed through the filter. It is then
cooled/dehumidified/heated through the heat exchanger.
The direction of the air output is manipulated up and down by the motorized louver, and left to right via manually controlled vertical deflectors. Some models may come with “dual-swing” capability,
which offers both a horizontal and vertical motorized air flow swing.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Filter

Controlling the System’s Airflow

  1. Pressing the SWING buttons activates the louver.
    • Press the Swing PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 13 button to trigger the horizontal flaps to swing up and down. Press this button again to stop swing movement at the current angle.
    • Press the Swing PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 12 button to trigger the vertical flaps to swing left and right. Press this button again to stop swing movement at the current angle.
  2. If the vertical deflectors (which are located underneath the flaps) are adjusted manually, they can be used to fix the airflow in a certain vertical position before turning the system on.
    Note: The SWING buttons can also be used to set a fixed angle of airflow by pressing the button once the louver moves to the desired angle.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Airflow

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 3 CAUTION

  • Do not manipulate the louvers themselves manually, or serious damage may occur.
  • Deflector adjustments should be made only when the system is switched off.
  • Never poke fingers, sticks, or other objects into the air inlet/outlet vents.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Vertical Deflectors

COOLING Mode
Cooling mode allows the air conditioner to cool the room while also reducing the humidity of the air in the room.
To put the system into cooling mode, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 21 button until the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 20 symbol appears on the remote’s display.
The TEMP – and + buttons can then be used to set a temperature lower than that of the room.
Note: In cooling mode, be sure to avoid keeping the vertical louver at too sharp of a downward angle, which can lead to condensation buildup and dripping.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - COOLING Mode

HEATING Mode
Heating mode allows the air conditioner to heat the room by reversing the cooling cycle. To put the system into heating mode, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 21 button until the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 19 symbol appears on the remote’s display.
The TEMP – and + buttons can then be used to set a temperature higher than that of the room.
Upon enabling heat mode, the indoor unit will take between 2-5 minutes for pre-heating, after which the unit will begin blowing warm air. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - HEATING Mode

warning 2 NOTE
In heating mode, the appliance will periodically enter a defrost cycle, which is essential in order to clean frosting off the condenser and recover heat exchange capability. This process is normal and lasts for 2-10 minutes.
During defrosting, the indoor unit’s fan will cease operation. After the cycle is completed, the system will resume its normal heat mode operation automatically.

DRY Mode
Dry mode is a limited function that can rapidly reduce the humidity/moisture of the room. To put the system into dry mode, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 21 button until the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 13 symbol appears on the remote’s display.
An automatic preset of this mode is then activated. Note that the fan speed will remain on AUTO and cannot be adjusted in this mode.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - DRY Mode

FAN-ONLY Mode
Fan-Only mode is used to set the system to use only air ventilation and no heating or cooling.
To put the system into Fan-Only mode, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 21 button until the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 22 symbol appears on the remote’s display.
Use the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 23 button to then set the desired fan speed. There are 5 speed levels to choose from.
Note: There is no AUTO setting in Fan-Only mode. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - FAN-ONLY Mode

SMART-AUTO Mode
Smart-Auto mode uses preset logic to allow the system determine the ideal temperature output and fan speed, based on the current room temperature.
To put the system into Smart-Auto mode, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 21 button until the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 24 symbol appears on the remote display. The Smart-Auto logic is shown to the right.
The system will then automatically determine the necessary air output. You can use the TEMP – and + buttons to offset this output anywhere from -7 to +7. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - SMART-AUTO Mode

Changing the Fan Speed in Cool/Heat Modes
The fan speed can be changed between AUTO, HIGHER, HIGH, MEDIUM, LOW, and LOWER speeds in Cool/Heat.
To do so, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 23 button. The running fan speed can then be set. It follows the cycle of:PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 14PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Heat ModesTurning the Display On or Off

The LED display on the front panel of the system can be turned on or off as desired.
To do so, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 25 button in order to switch off the LED display on the front panel.
This button can be pressed again to turn the LED display back on. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Turning the Display

SLEEP Mode
SLEEP mode is generally meant for periods of lower cooling requirements, such as during typical sleeping hours. This mode will result in decreased energy use, and can only be activated in Cool, Heat, or Dry modes.
Fan speed is automatically set to LOW. After 8 hours in SLEEP mode, the air conditioner will stop operation.
To put the system into SLEEP mode, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 26 button, and the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 27 symbols will appear on the remote’s display in the following sequence:PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 28The table to the right outlines the operational logic of the four different SLEEP mode settings.

Sleep Mode

Operation Mode Target Temp. Increase/Decrease After 1, 2, 6, or 7 hours
1 Hour 2 Hours 6 Hours 7 Hours

Mode 1PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 29

Cool/Dry +2°F
Heat – 2°F

Mode 2PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 30

Cool/Dry +2°F – 1°F – 1°F
Heat – 2°F +1°F +1°F

Mode 3PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 31

Cool/Dry +1°F +2°F – 2°F – 1°F
Heat – 2°F – 2°F +2°F +2°F

Mode 4PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 32

Cool/Dry No Change – Turns off after 8 hours
Heat No Change – Turns off after 8 hours

Energy Saver (ECO) Option

In this mode, the appliance will automatically manage the operation in order to save energy.
To turn the ECO feature on, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 33 button on the remote, and the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 1 icon will appear. The system is now running in ECO, and the process can be repeated to turn it off.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Energy Saver

NOTE
The ECO feature is available in both COOLING and HEATING modes, but not in AUTO mode.

TURBO Option
In this mode, the appliance will operate using the highest fan speed in order to maximize output and reach the set temperature the quickest.
To turn the TURBO feature on, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 34 button on the remote, and the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 2 icon will appear. The system is now running in TURBO, and the process can be repeated to turn it off.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - TURBO Option

Child-Lock Function
Pressing PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 35 and PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 46 buttons together for 3 seconds will activate the child-lock function. When this function is active, the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 8 icon will be displayed, and no single button will be active.
Press and hold the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 35 and PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 46 buttons together for 3 seconds once more to de-activate the child-lock function.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Clock FunctionClock Function
Use the CLOCK button to set the current time, which is useful for TIMER control (explained on next page).

Using the Timer – TIMER ON
The TIMER feature allows you to set a time delay for the system to turn itself on or off.
To set a time delay for the system to turn itself ON in X amount of hours: PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Using the Timer

  1. Begin by pressing the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 35 button while the system is powered off. The PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 36 symbol will then display flashing. The default setting is 12 o’clock.
  2. Use the TEMP – and + buttons to set the needed time delay in 1, 10, or 60 minute increments.
  3. Press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 35 button a second time to confirm.
  4. Press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 21 button to select the desired operating mode that the unit should start up in.
  5. Set the desired fan speed that the unit should start up in by pressing the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Icon 23 button.
  6. Use the TEMP – and + buttons to set the desired operation temperature. The unit is now primed.

Using the Timer – TIMER OFF
The TIMER OFF feature allows the appliance to turn itself off after X amount of hours have passed.
The symbol PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 47 will appear. To set a time delay for the system to turn itself off in X amount of hours:

  1. Confirm that the appliance is on and running.
  2. Press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 46 button to enter the prompt for switching off the system. Use the TEMP – and + buttons to configure the time delay setting.
  3. Press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 46 button again to confirm. It can also be pressed once more to cancel the setting.

NOTE Regarding Timers

  • Press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 48 buttons to cancel at any time in Timer Modes.
  • The programming will cancel if no buttons are pressed after 10 seconds. This may require restarting the process.

46°F Freeze Protection Function
This feature is meant to be used to prevent freezing while the user is away from home.
When turned on, it sets the system to keep a temperature of 46°F. If the unit is in standby, then the setting will automatically start the heating mode when the room temperature is equal to or lower than 46°F.
It will set the system back to standby when the room temperature reaches 48°F.
Press and hold the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 37 and PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 38 buttons together in heat mode for 3 seconds in order to activate this feature. The PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 39 symbol will then appear to show that the 8°C/46°F heating feature is activated.
Press any button other than TIMER ON/OFF, I FEEL, or SWING to de-activate.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Freeze Protection Function

MUTE Mode
When the system is muted, the remote controller will display LOW fan speed, and the indoor unit will operate at its lowest fan speed in order to minimize operation noise.
Press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 40 button in order to activate this mode.
The PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 41 icon will display to indicate that the system is muted.
This mode can be cancelled by pressing either the FAN, TURBO, or SLEEP buttons.
Note: The MUTE feature cannot be activated when the system is in DRY mode. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - MUTE Mode

I FEEL – To Ensure Comfort
The I FEEL feature enables the remote to act as the temperature sensor and relay the current air temperature of where the remote is physically placed within the room. In some cases, this can aid with reducing thermal drift between the set temperature and the actual room temperature.
In order to activate this feature, press the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 42 button, and the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 43 icon will appear on the display.
Note: The remote must be within 25 feet and line of sight with the AC unit in order to transmit signals.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Ensure Comfort

SELF-CLEAN Feature
This feature helps carry away accumulated dust, dirt, bacteria, and other microbial contents away from the indoor evaporator, and can be activated in Cool Mode.
To activate this feature, press and hold the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 40 button for 5 seconds. The PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 44 icon will then appear on the remote’s display. Once the procedure is completed, the system will return to the previous mode, and the PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 44 icon will remain for 10 minutes.
The PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - icon 45 button can be pressed to cancel this feature during the process. Two beeps will be emitted from the machine when it is finished, or cancelled.
This procedure can result in some uncommon noise coming from the machine. This noise is normal as a side effect of the plastics expanding and contracting due to reactions with heat and cold.
It is recommended to use this function only when indoor temperature is under 86°F and outside temperature is between 41°F and 86°F.
It is suggested to run this feature once every 3 months.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - SELF-CLEAN Feature

An Important Note Regarding Operating Temperatures
The system is designed to run within a certain range of temperatures, which are listed below.
There are built-in protections with the system that may stop the appliance when the ambient temperatures goes outside of these ranges.
Inverter Air Conditioner Operational Conditions

Operating Mode Temperature COOLING Mode HEATING Mode DRYING Mode
Current Room Temperature 70°F – 90°F 45°F – 81°F 64°F – 90°F
Ambient Outdoor Temperature 5°F – 131°F -22°F – 75°F 70°F – 131°F

warning 2 NOTE
After stopping and restarting the air conditioner, or after the mode is changed during operation, the system does not restart immediately, and will come on when three minutes have elapsed (as a protection for the compressor).
Full system-rated capacity and efficiency is obtained at the standard rating conditions as developed by the testing and rating agencies. Deviations from the rating conditions, especially the atmospheric conditions, will be compensated by the variable speed compressor, within certain limitations.
Heat pump systems function by exchanging energy, in the form of heat, between the indoor air and the outdoor ambient air (atmospheric). The system’s net cooling or heating capacities and efficiencies change by atmospheric conditions, as well as the indoor air conditions (such as temperatures and humidity levels).
Capacity of the system required for a specific area or application must be determined professionally using detailed calculations, which are based on several internal and external factors.

To further optimize the performance of your unit, be sure to do the following:

  • Keep doors and windows closed.
  • Limit energy usage by using TIMER ON and TIMER OFF functions.
  • Do not block air inlets or outlets.
  • Regularly inspect and clean air filters.

Maintenance of the Air Conditioner

Periodic Maintenance Is Essential For The System!
Maintaining the air conditioner will ensure that is stays efficient. Before carrying out any sort of maintenance, always ensure that the power supply to the system is turned off.
Indoor Unit
Anti-Dust Filters (Clean once every 2 weeks)

  1. Open the front panel by pulling outward and upward at the indicated location.
  2. Keep the front panel raised with one hand and take out the air filters with the other.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Indoor Unit 1
  3. The filters are washable and should be cleaned with warm water (under 113°F).
  4. Leave the filters to dry in a cool, dry place.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Indoor Unit 2
  5. Keeping the front panel raised with one hand, insert the air filters with the other.
  6. Close the front panel.

Any electrostatic or deodorizing filters, if installed, are not washable and should be replaced once every 6 months.
Interior of the Indoor Air Handler
In addition to the filters, the interior of the indoor unit itself as well as the inner coil should be inspected every season. The front panel can be disconnected and removed from the top hinge where the pegs connect. This will allow for easier inspection of the interior and behind the air filters. The interior should be cleaned with damp cloth and neutral soaps. Do not use any sort of aggressive solvents or detergents. Only a soft cloth that is lightly damp should be used.
INDESIT IFW 6841 JH IX Oven - Icon 1 BEFORE CLEANING OR MAINTENANCE
ALWAYS TURN OFF YOUR AIR CONDITIONER SYSTEM AND DISCONNECT ITS POWER SUPPLY BEFORE PERFORMNG CLEANING OR MAINTENANCE. DO NOT SPRAY WATER DIRECTLY NEAR THE INDOOR UNIT, AS IT CAN DAMAGE INSULATION AND ELECTRICAL COMPONENTS.

Indoor Unit Installation Instructions

Indoor Unit Installation Location Selection
Follow the below best practices for selecting an optimal space for installation the indoor unit:

  • DO NOT install the unit on a wall that is subject to vibrations.
  • DO NOT install the system near sources of heat, steam, or flammable gases.
  • DO NOT install the indoor unit in a location that is exposed to direct sunlight.
  • DO ensure that the inlet and outlet vents are not obstructed. The system should be able to output air all across the room.
  • DO minimize the distance between the indoor and outdoor unit and install the unit in a place where connecting the indoor and outdoor unit will be as simple as possible.
  • DO install the unit on a strong wall and where it is easy to drain the condensate water.
  • DO install the unit in a location where it will be easy to service the machine and perform any necessary maintenance.
  • DO obey the following tolerances depicted in the illustration below:

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Ceiling

Indoor Unit Installation Instructions

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Unit

Installation Diagram
Before proceeding, it is important to consider the following height and length restrictions:

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Diagram

Before starting the installation, decide on the position of both the indoor and outdoor units. Take into account the minimum clearance requirements for both the indoor and outdoor units, which can be found in their respective sections of this manual.
Install the indoor unit inside the room to be air conditioned, avoiding corridors and communal areas. Install the indoor unit at a height of at least 8 ft. off of the ground.
INDESIT IFW 6841 JH IX Oven - Icon 1 NOTE
Only persons and/or companies qualified and experienced in the installation, service, and repair of refrigerant products should be permitted to do so. The purchaser must ensure the system is installed carefully and correctly.
Installation of the Mounting Plate

  1. Place the included mounting plate against the wall where the system will hang that fulfills the constraints on page 22. Use a level to ensure that the plate is horizontally level.
  2. Drill 1.3” deep holes for each screw to enter, the locations are flexible but should be spaced well.
  3. Insert the plastic anchors into each of the holes.
  4. Fix the mounting plate to the wall by using the included tapping screws. Check that it is secured.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Mounting Plate

Note: The actual appearance of the mounting plate may differ slightly but the process is similar.
Drilling the Wall Hole for Piping
CHECK PAGES 43-44 FOR MOUNTING HOLE GUIDELINES ACCORDING TO THE BRACKET.

  1. With the mounting plate firmly affixed to the wall, mount the indoor unit onto the mounting plate temporarily in order to determine the location of the wall hole in the next steps.
  2. Using a pencil, lightly trace the bottom corner of the indoor unit, depending on which side exit the piping will go through (see Page 26).PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Piping
  3. Take the inside unit off of the plate, and make a mark of where the hole will be (PG. 43-44), to ensure ample clearance between the tracing and bracket.
  4. Drill a 2.5” wall hole at a slight downward angle using a core drill, being careful to avoid wires, plumbing, and other sensitive materials. The bottom of the inside hole should be ~1/4” above the bottom of the outside hole.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Piping 2

Electrical Connections – Indoor Unit
All systems will include a wiring diagram affixed to the indoor unit. See Page 44 for more details.

  1. Lift up the front panel of the indoor unit.
  2. Remove the cover as indicated in the illustration.
  3. For the electrical wiring, consult the circuit diagram affixed to the elecrical cover.
  4. Connect the cables to the wiring terminal by following the numbering. Use wire gauge suitable for the electrical power input. (see name plate on the unit).

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Electrical Connections

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 1BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS

  1. All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician.
  2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
  3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and suspend all installation until the safety issue is properly resolved.
  4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
  5. Connect power through fixed wiring, install a surge protector and a disconnect switch box, and a dedicated circuit breaker with a capacity of 1.5 times the maximum current of the unit.
  6. A properly rated HACR-type fuse or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring.
    The qualified technician must use an approved circuit breaker or fuse.
  7. Only connect the unit to an individual branch circuit. Do not connect another appliance to that outlet. This equipment requires its own dedicated and protected circuit.
  8. Make sure to properly ground the air conditioner.
  9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
  10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.

INDESIT IFW 6841 JH IX Oven - Icon 1 WARNING: BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.
Preparing the Refrigerant Piping of the Indoor Unit
The piping “pigtails” pre-attached to the indoor unit can be run in 3 different ways as shown in the illustration. Decide which type of configuration is most suitable before continuing.
By default it is routed for a left side exit as shown in #1. This method can either use the left side knockout for a side exit, or a wall hole can be drilled on the left side of the unit’s rear.
Routing it straight through the back of the system (#2) will facillitate the connections to the copper pipe extensions to be made outside. This is recommended to simplify the process.
#3 is a right side exit, but is not recommended as it involves a 180° bend of the piping, which increases the risk of kinking or collapsing the lines dramatically. Bend slowly and cautiously.
If a side-exit is chosen, there are knock-out panels on either side of the unit that can be cut out along the groove to provide a notch for the pipe to exit from. Use a cutting tool to do this.
For the method chosen, run the piping in the direction of the wall hole. Bind the copper pipes, drain pipe, and power cables together with tape, with the drain pipe at the bottom so that water can flow freely. Ensure that the bundle is exiting at a continuous downward pitch.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Unit 2

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 1 CAUTION

  • Do not remove the cap from the pipe until it is time to connect it, to avoid dampness or dirt from entering.
  • If the pipe is bent/pulled too often, it will become stiff. Do not bend the pipe more than three times at one point. Be extremely careful not to kink any piping.
  • When extending the coiled copper pipes, straighten them by unwinding gently, as shown in the picture.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - piping 3Unwind the coil gently rather than pulling at ends

Connecting the Drain Hose
By default, the drain hose is attached to the left-hand side of unit (”left” when facing the back of the unit). However, it can also be attached to the right-hand side.

  1. To ensure proper drainage, attach the drain hose on the same side that your refrigerant piping exits the unit.
  2. Attach any drain hose extensions (sold separately) to the end of drain hose.
  3. Wrap the connection point firmly with Teflon tape to create a good seal, and to prevent leaks.
  4. For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent condensation.
  5. Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Drain Hose

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 1 NOTE ON DRAIN HOSE PLACEMENT
Make sure to arrange the drain hose according to the illustrations.
eta ZERO 2 in 1 Robot Vacuum Cleaner - Icon 2 DO NOT kink the drain hose.
eta ZERO 2 in 1 Robot Vacuum Cleaner - Icon 2 DO NOT create a water trap (siphon).
eta ZERO 2 in 1 Robot Vacuum Cleaner - Icon 2 DO NOT put the end of the drain hose in water or in a container that will collect water.

DUAL DRAIN HOLE LOCATIONS EXIST
The indoor unit has 2 drain connections on left and right sides. Either one can be utilized. One side will have a hose connected, while the other is plugged.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Drainage Ports

Connecting the Signal Cable
Color selection does not matter as much as matching number to number does. Consult the diagram affixed to the indoor and outdoor unit respectively for specific wiring instructions. There are 3 terminals (1, 2 , 3) and ground (G). Do not mix up the wires between each ends. It is vital that the colors between the indoor and outdoor unit match for each terminal. A simplified wiring diagram is included in the Appendix section of this manual on Page 44. On the indoor unit, the wiring diagram is located underneath the front panel as shown below:

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Signal Cable

Cable Wire Specifications (For Uncommon Configurations)

Pioneer WYT Series Mini Split 9K 12K 18K 24K
Sectional Area (AWG)
Power Supply Cable N(L2) 14AWG 14AWG 12AWG 10AWG
L(L 1) 14AWG 14AWG 12AWG 10AWG
Earth 14AWG 14AWG 12AWG 10AWG
Connection Supply Cable 3(L) 16 AWG 16 AWG 16 AWG 16 AWG
2(N)
1(S)
Earth

Consult the nameplate on the system for detailed electrical specifications. Confirm wire size on Page 32.
Connecting the Refrigerant Piping to the Indoor Unit
Once the copper piping kit coil is unwound, refer to the below instructions to proceed:

  1. Bring the ends of both the copper line and the indoor unit line together. Align the centers of the pipes that will be connected.
  2. Remove the indoor unit piping cap, and check that no debris is inside. Some gas may be heard escaping, it is just nitrogen.
  3. Use any leak guard or leak sealant on the flares of the piping if available. Attach the flare nut and tighten as much as possible by hand. Torque correctly to the specifications found on the next page using two wrenches. Repeat the process for the other copper ine.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Indoor Unit 3

TIGHTENING TORQUE FOR PROTECTION CAPS AND FLANGE CONNECTION

PIPE TIGHTENING TORQUE CORRESPONDING STRESS (using a 20 cm wrench)
[N x m] [Ft x lb]
1/4″ Φ 6.35) 15 -20 11 -15 Wrist Strength
3/8″ Φ 9.52) 30 -35 22 -26 Arm Strength
1/2″ Φ 12.7) 50 -55 37 -41 Arm Strength
5/8″ Φ 16) 60 -65 44 -48 Arm Strength
TIGHTENING TORQUE [N x m] TIGHTENING TORQUE [Ft x lb]
Service Port Nut 7 – 9 5 – 7
Protection Caps 25 – 30 18 – 22

Note: Over-tightening may damage flare connections and cause leaks.
Wrapping the Lines and Mounting the Indoor Unit
For mounting the indoor unit, proceed as follows:

  1. Arrange the pipes, cables, and drain hose well.
  2. Lag the pipe joints with insulation material, and secure with vinyl tape as depicted in the figure.
  3. Run the bound bundle through the wall hole,and mount the indoor unit securely onto the mounting plate. Press/push the lower part of the indoor unit so it clicks onto the mounting plate.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Wrapping

Outdoor Unit Installation Instructions

Outdoor Unit Installation Location Selection
Follow the below best practices for selecting an optimal space for installation the indoor unit:

  • DO NOT install the unit near sources of heat, steam, or flammable gases.
  • DO NOT install the system in areas prone to extreme winds or dust.
  • DO NOT install the outdoor unit in an area that has many passersby.
  • DO select a location where the air discharge and operating sound level will not disturb others.
  • DO install the system in a shaded area or utilize a cover/sun protection that will not interfere with air flow. This will also protect the system from rain or snow.
  • DO install the unit in a safe and sturdy location.
  • DO install rubber vibration absorbers if the system will be subject to vibrations.
  • DO obey the following tolerances depicted in the illustration below to ensure air flow:

Minimum Required Installation Space

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Installation SpaceSPECIAL CONSIDERATIONS FOR EXTREME WEATHER CONDITIONS
If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds.
If the unit is frequently exposed to heavy rain or snow: Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit. If the unit is frequently exposed to salty air (seaside air): Use specifically approved anti-corrosion coating sprays onto the heat exchanger surface in order to resist corrosion.
Outdoor Unit Installation Instructions

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Outdoor Unit

Mounting the Outdoor Unit to the Selected Location
The outdoor unit should be installed either on a pad or on a solid wall and fastened securely. Follow the procedure below before connecting any pipes or cables:

  • Decide what the best position on the wall or on the ground is, and leave enough space to be able to carry out maintenance easily. Anchoring dimensions are provided on Page 42.
  • If wall mounting, fasten the support brackets to the wall using hardware that is particularly suited for the type of wall. Use the appropriate amount of hardware for the application.
  • The unit must be installed following all national regulations.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - dimensions

Outdoor Unit Condensate Water Drainage
The condensate water and the ice formed in the outdoor unit during heat mode can be directed away using the optional drain joint + pipe included with the system.

  1. Fasten the drain joint depicted in the diagram to the 1 inch port located in the bottom part of the unit.
  2. Connect the drain joint and the drain pipe together.
  3. Ensure the condensate will drain to a suitable place.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Water Drainage

INDESIT IFW 6841 JH IX Oven - Icon 1 BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE REGULATIONS

  1. All wiring must comply with local and national electrical codes, and must be installed by a fully-licensed electrician.
  2. All electrical connections must be made according to the Electrical Connection Diagram located on the side panels of the indoor and outdoor units.
  3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and suspend all installation of the unit until the safety issue is properly resolved.
  4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause electrical shock or fire.
  5. Connect power through fixed wiring, install a surge protector, and disconnect switch box. Use a dedicated circuit breaker with a capacity of 1.5 times the maximum current of the unit.
  6. A properly rated HACR-type fuse or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
  7. Only connect the unit to a dedicated individual branch circuit breaker. Do not connect another appliance to that same circuit.
  8. Be sure to properly ground the air conditioner9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
  9. Do not let wires touch or rest against refrigerant tubing, the compressor, or any other moving parts within the unit.

WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM.

  1. Prepare the cable for connection:

USE THE RIGHT CABLE

  • Outdoor Power Cable: H07RN-F
  • Signal Cable: H07RN-F

Minimum Cross-Sectional Area of Power and Signal Cables
North America

Appliance Amps (A) AWG
10 18
13 16
15 14
20 12
30 10

INDOOR UNIT TERMINAL POSITION #1 connects to OUTDOOR UNIT TERMINAL POSITION #1.
INDOOR UNIT TERMINAL POSITION #2 connects to OUTDOOR UNIT TERMINAL POSITION #2.
INDOOR UNIT TERMINAL POSITION #3 connects to OUTDOOR UNIT TERMINAL POSITION #3.
INDOOR UNIT TERMINAL POSITION “GROUND” connects to OUTDOOR UNIT GROUNDING LUG
Using wire strippers, strip the rubber jacket from both ends of cable to reveal about 40mm (1.5 in) of the wires inside. Strip the insulation from the ends of the wires. Using a wire crimper, crimp u-lugs on the ends of the wires. Note that some cables come with preinstalled u-lugs from factory.
Power/Signal Electrical Wiring to the Outdoor Unit
On the outdoor unit, the wiring diagram is located in the inner side of the handle cover.
The outside unit’s terminal block is protected by an electrical wiring cover on the side of the unit. A comprehensive wiring diagram is printed on the inside of the wiring cover.

  1. Unscrew and remove the handle on the right side plate of the outdoor unit.
  2. Wire the system using the appropriate gauge wire found on page 28/32 and the wiring diagram found on the handle cover. See page 44 for more details.
  3. Fasten the power connection wires into place using the supplied wire clamps.
  4. Check the wiring against the diagram to ensure it is wired correctly. A proper ground must be established.
  5. Rescrew and reinstall the cover handle.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Electrical Wiring PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - cover handle

Connection of the Refrigerant Piping
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16 ft).
Refer to the table below for specifications on the maximum length and drop height of piping.

Pioneer WYF Series Mini Split
25 SEER series MODEL/Capacity (Btu/h)
9K 12K 18K 24K
Liquid Pipe Diameter 1/4”
(Φ 6.35)
1/4”
(Φ 6.35)
1/4”
(Φ 6.35)
3/8”
(Φ 9.52)
Gas Pipe Diameter 3/8”
(Φ 9.52)
3/8”
(Φ 9.52)
1/2”
(Φ 12.7)
5/8”
(Φ 15.88)
Length of Pipe Supported by Standard Factory Pre-Charge 7.5m / 25ft 7.5m / 25ft 7.5m / 25ft 7.5m / 25ft
Maximum Distance Between Indoor and Outdoor Unit 20m / 65ft 20m / 65ft 20m / 65ft 20m / 65ft
Additional Refrigerant Charge (For each add’l foot after 16 ft.) 20g/m
0.22oz/ft
20g/m
0.22oz/ft
20g/m
0.22oz/ft
30g/m
0.32oz/ft
Max. Difference in Height Between Indoor and Outdoor Unit 10m / 33ft
(5m / 16ft when ODU above IDU)
10m / 33ft
(5m / 16ft when ODU above IDU)
10m / 33ft
(5m / 16ft when ODU above IDU)
10m / 33ft
(5m / 16ft when ODU above IDU)
Type of Refrigerant R410A R410A R410A R410A

Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.

  1. Measure the distance between the indoor and outdoor units.
  2. Using a pipe cutter, cut the pipe a little longer than the measured distance.
  3. Make sure that the pipe is cut at a perfect 90° angle. Refer below for bad cut examples:

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - pipe

DO NOT DEFORM PIPE WHILE CUTTING 
Be extra careful not to damage, kink, or deform the pipe while cutting. This will drastically reduce the efficiency and capacity of the unit and may cause internal damage.
Step 2: Remove any burrs carefully.
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed. Follow these steps for proper deburring:

  1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
  2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - cut section

Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.

  1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
  2. Sheath the pipe with insulating material.
  3. Place flare nuts on both ends of pipe. Make sure they are facing the correct direction, because they cannot be put on or have their direction chaged after flaring. PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - flaring
  4. Remove PVC tape from ends of pipe when ready to perform flaring work.
  5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the following table:PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - dimensions 2PIPING EXTENSION BEYOND FLARE FORM
    Outer Diameter of Pipe (mm) A (mm)
    Min. Max.
    Ø 6.35 (Ø 1/4”)   0.7 (0.03”) 1.3 (0.05”)
    Ø 9.52 (Ø 3/8”) 1.0 (0.04”) 1.6 (0.06”)
    Ø 12.7 (Ø 1/2”) 1.0 (0.04”) 1.8 (0.07”)
    Ø 16    (Ø 5/8”) 2.0 (0.08”) 2.2 (0.09”)
    Ø 19    (Ø 3/4”) 2.0 (0.08”) 2.4 (0.1”)

    PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - FLARE FORM

  6. Place flaring tool onto the form.
  7. Turn the handle of the flaring tool clockwise until the pipe is fully flared.
  8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and successful, even flaring.

Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque, or to deform the piping in any way. One should first connect the low-pressure pipe, then the high-pressure pipe.
If provided by the supplier, apply leak guard material on all flared mating surfaces.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Connect pipes

Instructions for Connecting Piping to Outdoor Unit

  1. Unscrew the cover from the packed valve on the side of the outdoor unit.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Connecting Piping
  2. Remove protective caps from the valve ends.
  3. Align flared pipe end with each valve, and tighten the flare nut as tightly as possible by hand.
  4. Using a spanner, grab the body of the valve. Do not grab the nut that seals the service valve.
    USE SPANNER TO GRAB THE BODY OF THE SERVICE VALVE
    Torque from tightening the flare nut can snap off other parts of valve.
  5. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the correct torque values.
  6. Loosen the flaring nut slightly, then tighten again.
  7. Repeat Steps 3 to 6 for the remaining pipe.
    PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - remaining pipe

MINIMUM BEND RADIUS
When bending connective refrigerant piping, the minimum bending radius is 10 cm (4”).

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - BEND RADIUS

DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must not exceed the torque requirements shown in the table shown on page 29.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - EXCESSIVE TORQUE

Air Evacuation and Bleeding the Circuit
The air and/or humidity left inside the refrigeration circuit can contaminate the refrigerant and cause abnormal spikes in pressure, leading to eventual compressor malfunction.
herefore, after having connected the indoor and outdoor units to create a closed system, it is necessary to bleed the air and humidity out of the circuit through the use of a vacuum pump.
Evacuation should be performed upon initial installation or when the unit is relocated.
BEFORE PERFORMING EVACUATION
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Check to make sure that both high-pressure and low-pressure pipes between the indoor and outdoor units are connected properly in accordance with the “Refrigerant Piping Connection” section of this manual.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Check to make sure all wiring is connected properly.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - EVACUATION

Evacuation Instructions
Before using a vacuum pump and manifold gauge, read their operation manuals to become familiarized with using them properly.

  1. Unscrew and remove the caps from the 2-way and 3-way valves.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - vacuum pump
  2. Unscrew and remove the cap from the service port.
  3. Connect the blue (low) hose of the manifold gauge to service port on the outdoor unit’s 3-way valve (use an adapter if needed). Ensure that the pin fully engages the schrader valve.
  4. Connect the yellow (middle) hose from the manifold gauge to the vacuum pump.
  5. Open the low pressure knob of the manifold gauge. Keep the high pressure knob closed.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - vacuum pump 2
  6. Turn on the vacuum pump to evacuate the system.
  7. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-100 kPa or -30 inHg).
  8. Close the low pressure knob of the manifold gauge, and turn off the vacuum pump.
  9. Wait for 5 minutes, then verify that there has been no rise in the vacuum reading.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Compound Meter
  10. If there is a rise in the system vacuum, refer to “Gas Leak Check” section for information on how to check for leaks. If no change in vacuum reading, unscrew the cap from the service valve (high pressure valve).PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - service valve
  11. Insert a hexagonal wrench into the service valve (2-way valve) and open the valve by turning the wrench in a 1/4 counterclockwise turn. Wait and listen for gas to exit the system, then close the valve after 5 seconds.
  12. Watch the pressure gauge for a few minutes to make sure that there is no drop in pressure. The Pressure Gauge should now show higher than the atmospheric pressure and hold that value.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - atmospheric pressure
  13. Remove the charge hose from the service port.
  14. Using the hexagonal wrench, fully open both the high pressure and low pressure valves fully counterclockwise.PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Tighten further
  15. Tighten valve caps on all three valves (service port, high pressure, low pressure) by hand. Tighten further using a torque wrench if needed.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 1 OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it comes into contact with stopper. Do not try to force the valve to open further.

Electrical/Gas Leak Check and Test Run

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Leak Check

ELECTRICAL SAFETY CHECKS
After installation, confirm that all electrical wiring is installed in accordance with local and national regulations, and according to the Installation Manual.
BEFORE TEST RUN
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Check Grounding Work
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Measure grounding resistance by visual detection or with a grounding resistance tester. Grounding resistance must be less than 4Ω.
Note: This may not be required in some locations.
DURING TEST RUN
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Check for Electrical Leakage
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 During the Test Run, use an electroprobe and and multi-meter to perform a comprehensive electrical leakage test.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage.
Note: This may not be required in some locations.
WARNING – RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN.
GAS LEAK CHECKS
There are 2 methods to check for gas leakage:
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit. The presence of bubbles indicates a leak.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper usage instructions.
AFTER PERFORMING GAS LEAK CHECKS
After confirming that the all pipe connection points DO NOT leak, replace the valve cover on the outside unit.

Test Run
BEFORE TEST RUN
Only perform a test run after the following steps have been completed:
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Electrical Safety Checks
Confirm that the unit’s electrical system is safe and is operating properly.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Gas Leak Checks
Check all flare nut connections and confirm that the system is not leaking.
PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Symbol 2 Opened Valves
Confirm that both the gas and liquid valves (high/low) are 100% fully opened.

TEST RUN INSTRUCTIONS
The following test run should be performed for 30 minutes:

  1. Connect power to the unit.
  2. Press the ON/OFF button on the remote controller to turn it on.
  3. Press the MODE button to scroll through the following functions, one at a time:
    • COOL – Select lowest possible temperature
    • HEAT – Select highest possible temperature
  4. Let each function run for 5 minutes, and perform the following checks:

PASS/FAIL?
No Electrical Leaks or Abnormal Noises
 Unit is Properly Grounded
 All Electrical Terminals Properly Covered
 Indoor and Outdoor Units Securely Installed
 All Pipe Connections Points Do Not Leak
 Water Drains From Drain Hose Properly
 All Piping is Properly Insulated
 Indoor Unit Responds to Remote Controller
 Indoor Unit Louvers Work Properly
System Works in Both HEAT + COOL mode
AFTER TEST RUN COMPLETION
After the 10 boxes above have been checked as having PASSED, perform the following operation:

  1. Using the remote control, return the system to a normal desired operating temperature.
  2. Using insulation tape, wrap the indoor unit refrigerant pipe connections that were left uncovered during the indoor unit installation process.

IF AMBIENT TEMPERATURES ARE TOO HIGH TO RUN A HEATING TEST:
If outside temperatures are too low to permit HEATING mode on the remote, do the following:

  1. Turn the unit on and put it in heat mode using the emergency button as depicted on Page 8.
  2. Run the heating mode test as normal, and turn the unit back off using the button when complete.

DOUBLE CHECK ALL PIPE CONNECTIONS
During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during your initial leak check. Take time during the Test Run to double-check that all copper pipe connection points are leak-free. Refer to the Leak Check page for instructions. Cooling mode pressures should be 120-155 PSI. Heating mode pressures should be 320-440 PSI.

Troubleshooting

MALFUNCTION POSSIBLE CAUSES 
If the appliance does not operate or respond… There is a power failure/plug pulled out
The indoor/outdoor unit fan motor was damaged
There is a faulty compressor or thermomagnetic circuit breaker
There is a faulty protective device or fuses
The electrical connections are loose
The system has entered a protection mode
The system has entered an overvoltage or undervoltage protection
The TIMER-ON function is active
The electronic control board was damaged
  If there are strange odors… The air filter is dirty
  If there’s running water… There was a backflow of liquid into the refrigerant circulation.
If a fine mist is coming from the air outlet… This occurs when the air in the room becomes very cold, for example in “COOLING” or “DEHUMIDIFICATION/DRY” modes
If strange noises are being emitted… This noise is made by the expansion or contraction of the front panel due to variations in temperature, and if so, is normal
If the airflow is insufficient, and the air is not hot or cold
enough…
The temperature setting is unsuitable
The air conditioner intakes and outlets may be obstructed
The air filter may be dirty
The fan speed may be set at the minimum
There may be too many other heat sources in the room
The system may be getting low on refrigerant, pressures should be checked
If the appliance does not respond to commands… The remote control may not be close enough to the indoor unit
The batteries of remote control may need to be replaced
There are obstacles between remote control and indoor unit signal receiver
If the display is off… The DISPLAY button has been pressed
There has been a power failure
 Switch off the air conditioner immediately and cut off the power supply in the event of… Strange noises not due to expansion/contraction are heard during operation
The electronic control board is faulty or malfunctioning
Any fuses or switches are faulty or malfunctioning
The sound of spraying water or objects are heard inside the appliance
The cables or plugs have overheated
There are very strong odors being emitted from the appliance

ERROR SIGNALS ON THE DISPLAY
In case of error, press SLEEP button 10 times in 10 seconds to display any common error codes:

Display Description of the error
1 Outdoor Coil Temp. Sensor Fault
2 Compressor Exhaust Temp. Sensor Fault
5 IPM Module Protection
7 Communication Failure Between Units
13 Compressor Exhaust High Temp. Fault
14 Outdoor Ambient Temp. Sensor Fault
23 Refrigerant Leakage Detection
33 IndoorRoom Temp. Sensor Fault
34 Indoor Unit Coil Temp. Sensor Fault
38 Indoor Unit EEPROM Fault
39 Indoor Unit Fan Motor Fault
EA Indoor Display/Control Comm. Fault

Appendix

Anchoring the Outdoor Unit
The outdoor unit can be anchored to the ground or to wall-mounted brackets. The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions found below:

Pioneer WYF Series Mini Split
Outdoor MODEL/Capacity (Btu/h)
A B D H W1 W2
YN009GHFI25RPH (9,000 BTU – 208/230V) 510 mm
20-1/16 in.
310 mm
12-3/16 in.
280 mm
11 in.
585 mm
23 in.
810 mm
31-7/8 in.
885.5 mm
34-7/8 in.
YN012GHFI25RPH (12,000 BTU – 208/230V) 510 mm
20-1/16 in.
310 mm
12-3/16 in.
280 mm
11 in.
585 mm
23 in.
810 mm
31-7/8 in.
885.5 mm
34-7/8 in.
YN018GHFI25RPH (18,000 BTU – 208/230V) 542 mm
21-5/16 in.
341 mm
13-7/16 in.
310 mm
12-3/16 in.
650 mm
25-9/16 in.
860 mm
33-7/8 in.
935 mm
36-13/16 in.
YN024GHFI25RPH (24,000 BTU – 208/230V) 608 mm
23-15/16 in.
368 mm
14-1/2 in.
340 mm
13-3/8 in.
750 mm
29-1/2 in.
900 mm
35-7/16 in.
974 mm
38-3/8 in.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Anchoring

If installing the unit on the ground or on a concrete mounting platform, do the following:

  1. Mark the positions for four expansion bolts based on dimensions in the “Unit Mounting Dimensions” chart.
  2. Pre-drill holes for expansion bolts.
  3. Clean concrete dust away from holes.
  4. Place a nut on the end of each expansion bolt.
  5. Hammer expansion bolts into each hole.
  6. Remove the nuts from expansion bolts, and place the outdoor unit onto the bolts.
  7. Put washers onto each expansion bolt, then replace each of the nuts.
  8. Using a wrench, tighten each nut until snug.

WHEN DRILLING INTO CONCRETE,
WEAR EYE PROTECTION AT ALL TIMES!

Guidelines for Drilling the Wall Hole
Below are the suggested locations for the wall hole for systems between 9,000 – 24,000 BTU.
Both left side/right side exits are considered. Confirm holes are appropriate by corner tracing.

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Wall HolePIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Wall Hole 2

Simplified Wiring Diagram (230V)

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - Wiring Diagram

European Disposal Guidelines
This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste.
When disposing of this appliance, you have the following options:

  • Dispose of the appliance at a designated municipal electronic waste collection facility.
  • When buying a new appliance, the retailer takes back the old appliance free of charge.
  • The manufacturer takes back the old appliance free of charge.
  • Sell the appliance to certified scrap metal dealers.

Special Notice
SONY MDR-RF855RK Wireless Stereo Headphone System - warning Disposing of this appliance improperly, or in other natural surroundings, endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain. Please follow proper disposal protocol.
The design and specifications of this product are subject to change without prior notice as development continues. Consult with the sales agency or manufacturer for details. Refer to the equipment nameplate for all other applicable specifications.
Pioneer product line, parts, and supplies are available online for convenient ordering at: www.highseer.com
www.pioneerminisplit.com
Scan the below code to visit our support page where you can find more installation materials:

PIONEER WYF HYP IMUM 2023 Hyperformance Mini Split Heat Pump - QR Codehttps://www.pdhvac.com/gosupport/
PIONEER LOGO 2is a registered trademark of Parker Davis HVAC International, Inc.

Parker Davis HVAC International, Inc.
3250 NW 107 Avenue, Doral, FL 33172 – USA
Tel : (305) 513-4488
Fax : (305) 513-4499
E-mail : info@pdhvac.com
Website: www.pdhvac.com
Copyright 2023, Parker Davis HVAC International, Inc.,
All rights reserved.

Documents / Resources

PIONEER WYF-HYP-IMUM-2023 Hyperformance Mini Split Heat Pump [pdf] User Manual
WYF-HYP-IMUM-2023 Hyperformance Mini Split Heat Pump, WYF-HYP-IMUM-2023, Hyperformance Mini Split Heat Pump, Split Heat Pump, Heat Pump, Pump

References

Leave a comment

Your email address will not be published. Required fields are marked *