INSTALLATION INSTRUCTIONS
GENERAL
These Class 2, electronic, LED drivers are to be installed Indoor in accordance with the National Electric code (NFPA 70) and local regulations. The LED driver must be installed in a well-ventilated area free from explosive gases and vapors. Proper operation requires the free flow of air. Only a qualified electrician should install this hardwired LED driver.
PRECAUTIONS BEFORE INSTALLING
Check the label and ensure the LED driver has the proper input voltage, output voltage and wattage for the job. Check the wire color to ensure they match the wiring diagram on this instruction sheet.
MOUNTING
Select a suitable location capable of supporting the weight of the LED driver.
INPUT CONNECTIONS/GROUNDING
ATTENTION: Ensure input voltage is 120 or 277 VAC.
Remove the wiring compartment knockouts and install strain reliefs.
With power turned off, route the input wires through a strain relief.
Connect Neutral, Live and grounding wires to the each of the white, black and green wires from LED driver respectively.
The LED driver MUST be grounded in accordance with the N.E.C.
OUTPUT AND DIMMER CONNECTIONS
Connect Class 2 output power:
Bring the LED load and dimmer wires through the open knockout.
For multiple output drivers, each load must be less than maximum rating for each output.
Connect the LED positive (+) wire to the red wire from LED driver.
Connect the LED negative (-) wire to the blue wire from LED driver.
Connect with 0-10V, 10V PWM dimmer:
Connect the dimmer positive (+) wire to the purple wire from LED driver.
Connect the dimmer negative (-) wire to the pink wire from LED driver.
Connect with ELV/MLV/TRIAC dimmer:
Refer to the dimmer installation and wiring diagram at AC input.
Only one dimmer should be used for proper dimming function.
The 0-10V dimming leads must be disconnected from all other connections and insulated separately when using ELV, TRIAC or MLV dimmers.
Multi-channel output models:
Refer to their unit label and specification for each output connection.
CAUTION: Interconnecting the outputs are not permitted.
QUICK SPECS
Input Voltage | NON-Dimmed or 0-10V Dimmed : 120V / 277V 50/60Hz Phase Dimmed : 120V 60Hz |
Dimming | Multi-Dim Technology Line Voltage Phase Dimming: ELV, TRIAC, MLV compatible Low Voltage DC: 0-10V, 10V PWM compatible |
Maximum Load Minimum Load Minimum Dim Level | See Model Information chart on page 2. Do not exceed maximum capacity. 40% (recommended for best performance, capable of lower loads) 1% (typical, depends on load) |
Operating Temp | -40° to 140°F (-40° to 60°C) |
Environment | Dry and Damp Location / Indoor |
Compliance | callus Listed, Class 2 FCC Class B |
PARTS INCLUDED:
Constant voltage LED driver wire connectors
INSTALLATION
TURNING OFF POWER
WARNING: Electric Shock Hazard. May result in serious injury or death.
Turn power OFF at circuit breaker prior to installation.
INSTALL COMPONENTS
- Compatible Control
- LD-XD Series Driver
- LED Tape Light/Fixture
REMOVE WIRING COVER. WIRE DRIVER.
Remove cover to access wiring compartment.
Remove knockouts with hammer and punch.
Attach load and control leads.. Only use copper wiring.
Refer to ‘System Diagrams’, and installation guides.
Secure cover in place with screws before turning power on.
TURN POWER ON AT CIRCUIT BREAKER
Install Additional Components, Verify Connections and turn main power ON at breaker.
SYSTEM WORKING IMPROPERLY?
Turn power OFF at circuit breaker and verify all connections. Review WIRING and TROUBLESHOOTING
WIRING DIAGRAMS
The following diagrams are provided as example system designs. Install in accordance with national and local electrical code regulations.
CONNECT WITH ELV/MLV/TRIAC DIMMER (120VAC INPUT ONLY)
A .Some dimmers may require an additional neutral wire connection.
Refer to dimmer installation for proper wiring.
CONNECT WITH 0-10V, 10V PWM DIMMER (120/277VAC INPUT)
Many 0-10V dimmers have switching function as option and need Live/Neutral wire connection. Refer to dimmer installation for proper wiring.
See LED load specifications for maximum series run limits.
Be sure to match driver output voltage to load voltage.
* CAUTION: Do not connect output leads together for drivers with 2 or 3 sets of outputs. Keep each set of output leads separated.
MODEL INFORMATION
Model | OutputVolts/Max Watts | Size(L x W x H) | Weight(lbs.) |
LD-XD-UNV20-12 | 12V / 20W | 7.93″ x 3.36″ x 1.33″ | 1.87 |
LD-XD-UNV20-24 | 24V / 20W | 7.93″ x 3.36″ x 1.33″ | 1.87 |
LD-XD-UNV40-12 | 12V / 40W | 7.93″ x 3.36″ x 1.33″ | 1.87 |
LD-XD-UNV40-24 | 24V / 40W | 7.93″ x 3.36″ x 1.33″ | 1.87 |
LD-XD-UNV60-12 | 12V / 60W | 8.29″ x 4.10″ x 1.59″ | 2.2 |
LD-XD-UNV60-24 | 24V / 60W | 8.29″ x 4.10″ x 1.59″ | 2.2 |
LD-XD-UNV96-24 | 24V / 96W | 8.29″ x 4.10″ x 1.59″ | 2.2 |
LD-XD-UNV180-12 | 12V / 3 x 60W | 9.51″ x 6.35″ x 1.59″ | 4.4 |
LD-XD-UNV200-24 | 24V / 2 x 96W | 9.51″ x 6.35″ x 1.59″ | 4.4 |
LD-XD-UNV300-24 | 24V / 3 x 96W | 9.51″ x 6.35″ x 1.59″ | 4.4 |
TROUBLESHOOTING
Prior to troubleshooting, ensure all items are a compatible system and main power is turned ON.
Fixture does not illuminate |
|
Fixture is flashing or flickering |
|
Fixture does not dim |
|
Different fixture types do not dim in sync |
|
Installation Trips Main Breaker |
|
Documents / Resources
GM Lighting LD-XD-UNVxx-12 LineDRIVE 24VDC Multi Dim LED Power Supplies [pdf] User Guide LD-XD-UNVxx-12 LineDRIVE 24VDC Multi Dim LED Power Supplies, LD-XD-UNVxx-12, LineDRIVE 24VDC Multi Dim LED Power Supplies, 24VDC Multi Dim LED Power Supplies, Dim LED Power Supplies, Power Supplies, Supplies |